ARI* CAPACITIES (cont)
HEATING CAPACITIES AND EFFICIENCIES
UNIT
583A
HEATING INPUT
(Btuh)
OUTPUT CAPACITY
(Btuh)
TEMPERATURE RISE
RANGE (°F)
AFUE (%)
024040
40,000
32,040
20-50
80.1
030040
80.0
024060
60,000
47,040
35-65
78.4
030060
47,040
35-65
80.1
036060
47,220
25-55
78.7
042060
47,220
15-45
78.7
036090
88,000
71,910
45-75
79.9
042090
90,000
71,910
35-65
79.9
048090
90,000
70,740
25-55
78.6
060090
90,000
70,740
25-55
78.6
048115
115,000
93,265
35-65
81.1
060115
048130
130,000
104,390
40-70
80.3
060130
LEGEND
AFUE — Annual Fuel Utilization Efficiency
NOTE: Before purchasing this appliance, read important energy cost and efficiency information available from your retailer.