PERFORMANCE DATA (cont)
NET COOLING CAPACITIES (cont)
583A--036
Temp (F)
Air Ent
Condenser
Evaporator Air — Cfm/BF
1050/0.111
1200/0.142
1350/0.181
Evaporator Air — Ewb (F)
62
67
72
62
67
72
62
67
72
85
TC
31.4
36.2
40.6
32.4
37.1
41.2
33.1
37.6
41.5
SHC
28.7
24.4
19.7
30.9
26.0
20.4
33.1
27.3
20.9
kW
2.82
2.88
2.93
2.93
3.01
3.06
3.03
3.16
3.20
95
TC
30.0
34.3
39.0
30.7
35.0
39.6
31.7
35.7
39.9
SHC
28.0
23.7
19.2
30.1
25.2
19.9
31.7
26.7
20.5
kW
3.12
3.21
3.26
3.22
3.37
3.38
3.34
3.48
3.53
105
TC
28.6
32.6
37.3
29.4
33.4
37.9
30.4
34.0
38.2
SHC
27.3
23.1
18.6
29.4
24.7
19.4
30.4
26.1
20.0
kW
3.45
3.56
3.60
3.53
3.68
3.73
3.67
3.83
3.88
115
TC
27.0
30.8
35.7
28.2
31.5
36.2
29.1
32.0
36.4
SHC
26.4
22.4
18.0
28.2
23.9
18.8
29.1
25.4
19.4
kW
3.77
3.93
3.97
3.87
4.06
4.11
4.03
4.20
4.26
125
TC
25.5
29.0
33.9
26.7
29.4
34.4
27.8
29.8
34.6
SHC
25.5
21.7
17.4
26.7
23.2
18.2
27.8
24.6
18.8
kW
4.09
4.29
4.37
4.22
4.44
4.50
4.40
4.58
4.65
583A--042
Temp (F)
Air Ent
Condenser
Evaporator Air — Cfm/BF
1225/0.057
1400/0.075
1575/0.099
Evaporator Air — Ewb (F)
62
67
72
62
67
72
62
67
72
85
TC
39.2
42.9
46.1
39.8
43.3
46.3
40.2
43.3
46.2
SHC
35.4
29.5
23.4
37.4
30.7
23.8
39.1
31.6
24.0
kW
3.81
3.82
3.79
3.93
3.97
3.93
4.06
4.15
4.09
95
TC
37.6
41.6
44.9
38.3
42.0
45.1
38.7
42.0
45.1
SHC
34.4
29.0
23.0
36.6
30.3
23.5
38.7
31.3
23.8
kW
3.80
3.82
3.80
3.91
4.04
3.94
4.03
4.16
4.11
105
TC
35.9
40.0
43.6
36.6
40.3
43.7
37.3
40.3
43.6
SHC
33.6
28.4
22.5
35.6
29.7
23.0
37.3
30.8
23.4
kW
3.79
3.83
3.80
3.89
3.98
3.95
3.99
4.17
4.12
115
TC
34.2
38.2
42.0
34.9
38.5
42.1
35.8
38.5
42.0
SHC
32.7
27.7
21.9
34.9
29.1
22.5
35.8
30.2
22.9
kW
3.77
3.83
3.81
3.86
3.99
3.95
3.93
4.18
4.13
125
TC
32.5
36.4
40.1
33.5
36.6
40.2
34.3
36.6
40.1
SHC
31.8
26.9
21.2
33.5
28.3
21.8
34.3
29.4
22.2
kW
3.75
3.83
3.81
3.82
3.99
3.95
3.91
4.18
4.13
LEGEND
BF
— Bypass Factor
Ewb — Entering Wet-Bulb
kW
— Total Unit Power Input
SHC — Sensible Heat Capacity (1000 Btuh)
TC
— Total Capacity (1000 Btuh) (net)
NOTES:
1. Ratings are net; they account for the effects of the evaporator-fan motor power and heat.
2. Direct interpolation is permissible. Do not extrapolate.
3. The following formulas may be used:
sensible capacity (Btuh)
t
= t
−
ldb
edb
1.10 x cfm
t
= Wet-bulb temperature corresponding to enthalpy of air leaving
lwb
evaporator coil (h
)
lwb
total capacity (Btuh)
h
= h
−
lwb
ewb
4.5 x cfm
Where: h
= Enthalpy of air entering evaporator coil
ewb
4. The SHC is based on 80 F edb temperature of air entering evaporator coil.
Below 80 F edb, subtract (corr factor x cfm) from SHC.
Above 80 F edb, add (corr factor x cfm) to SHC.
Correction Factor = 1.10 x (1 − BF) x (edb − 80).
13