PERFORMANCE DATA (cont)
NET COOLING CAPACITIES (cont)
583A--048
Temp (F)
Air Ent
Condenser
Evaporator Air — Cfm/BF
1400/0.050
1600/0.085
1800/0.119
Evaporator Air — Ewb (F)
62
67
72
62
67
72
62
67
72
85
TC
45.2
49.7
54.7
46.4
50.9
56.0
47.5
51.9
57.1
SHC
41.4
34.6
27.6
44.6
37.2
29.2
47.5
39.6
30.8
kW
4.04
4.08
4.12
4.05
4.09
4.13
4.06
4.10
4.14
95
TC
43.5
47.8
52.5
44.6
48.0
53.7
45.7
49.8
54.6
SHC
40.4
33.7
26.7
43.4
34.9
28.3
45.7
38.6
29.8
kW
4.45
4.50
4.55
4.46
4.62
4.56
4.47
4.53
4.58
105
TC
41.3
45.4
49.8
42.3
46.4
50.9
43.4
47.2
51.7
SHC
39.0
32.5
25.6
41.6
34.9
27.1
43.4
37.2
28.6
kW
4.91
4.95
5.00
4.93
4.97
5.02
4.93
4.98
5.03
115
TC
37.6
42.4
46.4
39.0
43.3
47.5
40.6
44.0
48.3
SHC
35.4
30.9
24.1
38.3
32.9
25.6
40.6
35.0
27.0
kW
5.39
5.46
5.51
5.41
5.48
5.43
5.44
5.49
5.55
125
TC
33.9
36.1
42.5
35.8
37.8
43.4
37.4
38.8
44.1
SHC
27.8
25.5
22.1
33.7
28.0
23.4
37.4
30.1
24.6
kW
6.30
5.94
6.05
6.18
5.97
6.06
6.15
5.98
6.08
583A--060
Temp (F)
Air Ent
Condenser
Evaporator Air — Cfm/BF
1750/0.082
2000/0.130
2250/0.162
Evaporator Air — Ewb (F)
62
67
72
62
67
72
62
67
72
85
TC
55.2
60.9
66.4
56.1
61.5
66.4
56.6
61.6
66.9
SHC
49.9
42.1
33.8
53.2
44.3
33.9
55.9
46.3
35.3
kW
4.92
4.97
5.00
5.14
5.23
5.28
5.41
5.55
5.59
95
TC
52.2
58.0
63.7
53.2
58.5
64.1
53.9
58.4
64.0
SHC
48.2
41.0
32.7
51.8
43.2
33.6
53.9
44.8
34.2
kW
5.39
5.57
5.50
5.64
5.75
5.77
5.90
6.03
6.09
105
TC
49.1
54.4
60.4
49.9
54.9
60.7
50.9
55.0
60.5
SHC
47.3
39.4
31.5
49.9
41.6
32.4
50.9
43.5
33.0
kW
5.87
5.98
6.02
6.13
6.22
6.30
6.34
6.57
6.62
115
TC
45.9
50.2
55.2
46.8
50.3
55.5
47.3
50.2
55.3
SHC
45.3
37.4
29.4
46.8
39.4
29.8
47.3
41.0
30.8
kW
6.39
6.48
6.54
6.57
6.75
6.81
6.85
7.07
7.14
125
TC
42.5
46.5
50.6
43.7
46.9
50.6
44.9
46.2
50.2
SHC
42.5
36.1
27.3
43.7
38.4
28.2
44.9
39.5
28.6
kW
7.03
7.13
7.13
7.22
7.38
7.40
7.51
7.67
7.72
LEGEND
BF
— Bypass Factor
Ewb — Entering Wet-Bulb
kW
— Total Unit Power Input
SHC — Sensible Heat Capacity (1000 Btuh)
TC
— Total Capacity (1000 Btuh) (net)
NOTES:
1. Ratings are net; they account for the effects of the evaporator-fan motor power and heat.
2. Direct interpolation is permissible. Do not extrapolate.
3. The following formulas may be used:
sensible capacity (Btuh)
t
= t
−
ldb
edb
1.10 x cfm
t
= Wet-bulb temperature corresponding to enthalpy of air leaving
lwb
evaporator coil (h
)
lwb
total capacity (Btuh)
h
= h
−
lwb
ewb
4.5 x cfm
Where: h
= Enthalpy of air entering evaporator coil
ewb
4. The SHC is based on 80 F edb temperature of air entering evaporator coil.
Below 80 F edb, subtract (corr factor x cfm) from SHC.
Above 80 F edb, add (corr factor x cfm) to SHC.
Correction Factor = 1.10 x (1 − BF) x (edb − 80).
14