Table 7 – LEDs
The LEDs on the RTU Open show the status of certain functions
If this LED is on...
Status is...
Power
The RTU Open has power
Rx
The RTU Open is receiving data from the network segment
Tx
The RTU Open is transmitting data over the network segment
BO#
The binary output is active
The
Run
and
Error
LEDs indicate control module and network status
If Run LED shows...
And Error LED shows...
Status is...
2 flashes per second
Off
Normal
2 flashes per second
2 flashes, alternating with
Run
LED
Five minute auto---restart delay after system error
2 flashes per second
3 flashes, then off
Control module has just been formatted
2 flashes per second
4 flashes, then pause
Two or more devices on this network have the
same MSTP network address
2 flashes per second
On
Exec halted after frequent system errors or
control programs halted
5 flashes per second
On
Exec start---up aborted, Boot is running
5 flashes per second
Off
Firmware transfer in progress, Boot is running
7 flashes per second
7 flashes per second, alternating with
Run
LED
Ten second recovery period after brownout
14 flashes per second
14 flashes per second,
alternating with
Run
LED
Brownout
On
On
Failure. Try the following solutions:
S
Turn the RTU Open off, then on.
S
Format the RTU Open.
S
Download memory to the RTU Open.
S
Replace the RTU Open.
NOTE
: Refer to the RTU Open multi--protocol controller
Controls, Start--Up, Operation and Troubleshooting
manual
for complete configuration of RTU Open, operating
sequences and troubleshooting information. Contact your
Bryant applications engineer for details on configuration
and troubleshooting of connected networks.
Outdoor Air Enthalpy Control
(PNO 33CSENTHSW)
The enthalpy control (33CSENTHSW) is available as a
field--installed accessory to be used with the EconoMi$er
R
2
damper system. The outdoor air enthalpy sensor is part of
the enthalpy control. (The separate field--installed accessory
return air enthalpy sensor (33CSENTSEN) is required for
differential enthalpy control. See Fig. 57.)
Locate the enthalpy control in the economizer next to the
Actuator Motor. Locate two GRA leads in the factory
harness and connect the gray lead labeled “ESL” to the
terminal labeled “LOW”. See Fig. 57. Connect the enthalpy
control power input terminals to economizer actuator power
leads RED (connect to 24V) and BLK (connect to GND).
7
CTB ECON
(P’LINK: to J4-2) or
(RTU Open: to J2-6)
LOW
GND
24V
Enthalpy
Switch
GRA
BLK
RED
Factory Wiring Harness
PL6-1 (24-V)
PL6-4 (COM)
C11160
Fig. 57 -- Enthalpy Switch (33CSENTHSW) Connections
The outdoor enthalpy changeover setpoint is set at the
enthalpy controller.
Differential Enthalpy Control —
Differential enthalpy control is provided by sensing and
comparing the outside air and return air enthalpy
conditions. Install the outdoor air enthalpy control as
described above. Add and install a return air enthalpy
sensor.
582J
Summary of Contents for 582J 04 Series
Page 5: ...5 C14270 Fig 2 Unit Dimensional Drawing 582J ...
Page 6: ...6 C14271 Fig 2 Unit Dimensional Drawing cont 582J ...
Page 12: ...12 C14272 Fig 6 Rigging Label 582J ...
Page 27: ...27 C14247 Fig 39 RTU Open System Control Wiring Diagram 582J ...
Page 28: ...28 C14248 Fig 40 RTU Open System Control Wiring Diagram with Perfect Humidityt 582J ...