14
4. Carefully lift the hood assembly (with metal tray)
through the filter access opening and assemble per the
steps outlined in
Economizer Hood and Two–Position
Hood,
below.
Economizer Hood and Two--Position Hood —
NOTE
: If the power exhaust accessory is to be installed
on the unit, the hood shipped with the unit will not be
used and must be discarded. Save the aluminum filter for
use in the power exhaust hood assembly.
1. The indoor coil access panel will be used as the top of
the hood. Remove the screws along the sides and bot-
tom of the indoor coil access panel. See Fig. 10.
TOP
PANEL
INDOOR
COIL
ACCESS
PANEL
INDOOR
COIL
ACCESS
PANEL
CAULK
HERE
TOP
PANEL
C06025
Fig. 10 -- Indoor Coil Access Panel Relocation
2. Swing out indoor coil access panel and insert the hood
sides under the panel (hood top). Use the screws
provided to attach the hood sides to the hood top. Use
screws provided to attach the hood sides to the unit. See
Fig. 11.
B
TOP
PANEL
INDOOR COIL
ACCESS PANEL
19 1/16”
SCREW
HOOD DIVIDER
LEFT
HOOD
SIDE
33 3/8”
(848mm)
(483mm)
C06026
Fig. 11 -- Economizer Hood Construction
3. Remove the shipping tape holding the economizer
barometric relief damper in place (economizer only).
4. Insert the hood divider between the hood sides. See
Fig. 11 and 12. Secure hood divider with 2 screws on
each hood side. The hood divider is also used as the
bottom filter rack for the aluminum filter.
5. Open the filter clips which are located underneath the
hood top. Insert the aluminum filter into the bottom
filter rack (hood divider). Push the filter into position
past the open filter clips. Close the filter clips to lock
the filter into place. See Fig. 12.
6. Caulk the ends of the joint between the unit top panel
and the hood top.
7. Replace the filter access panel.
DIVIDER
BAROMETRIC
RELIEF
CLEANABLE
ALUMINUM
FILTER
FILTER
HOOD
FILTER
CLIP
OUTSIDE
AIR
C08634
Fig. 12 -- Economizer Filter Installation
Step 9 — Units with Hinged Panels Only
Relocate
latch
shipped
inside
the
compressor
compartment behind the hinged compressor door to
location shown in Fig. 13 after unit installation.
If the unit does not have hinged panels, skip this step and
continue at step 10.
C12101
Fig. 13 -- Compressor Door Latch Location
582J
Summary of Contents for 582J 04 Series
Page 5: ...5 C14270 Fig 2 Unit Dimensional Drawing 582J ...
Page 6: ...6 C14271 Fig 2 Unit Dimensional Drawing cont 582J ...
Page 12: ...12 C14272 Fig 6 Rigging Label 582J ...
Page 27: ...27 C14247 Fig 39 RTU Open System Control Wiring Diagram 582J ...
Page 28: ...28 C14248 Fig 40 RTU Open System Control Wiring Diagram with Perfect Humidityt 582J ...