18
Step 12 — Install External Condensate Trap
and Line
The unit has one
3
/
4
-in. condensate drain connection on
the end of the condensate pan and an alternate connection
on the bottom. See Fig. 22. Unit airflow configuration
does not determine which drain connection to use. Either
drain connection can be used with vertical or horizontal
applications.
To use the alternate bottom drain connection, remove the
red drain plug from the bottom connection (use a
1
/
2
--in.
square socket drive extension) and install it in the side
drain connection.
The piping for the condensate drain and external trap can
be completed after the unit is in place. See Fig. 23.
DRAIN
(FACTORY-INSTALLED)
PLUG
CONDENSATE PAN (SIDE VIEW)
STANDARD
SIDE DRAIN
ALTERNATE
BOTTOM DRAIN
C08021
Fig. 22 -- Condensate Drain Pan (Side View)
NOTE: Trap should be deep enough to offset maximum unit static
difference. A 4” (102) trap is recommended
.
MINIMUM PITCH
1” (25mm) PER
10’ (3m) OF LINE
BASE RAIL
OPEN
VENT
TO ROOF
DRAIN
DRAIN PLUG
ROOF
CURB
SEE NOTE
2˝ (51) MIN
C08022
Fig. 23 -- Condensate Drain Piping Details
All units must have an external trap for condensate
drainage. Install a trap at least 4-in. (102 mm) deep and
protect against freeze-up. If drain line is installed
downstream from the external trap, pitch the line away
from the unit at 1-in. per 10 ft (25 mm in 3 m) of run. Do
not use a pipe size smaller than the unit connection
(
3
/
4
-in.).
Step 13 — Make Electrical Connections
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal
injury or death.
Do not use gas piping as an electrical ground.
Unit
cabinet must have an uninterrupted, unbroken
electrical ground to minimize the possibility of
personal injury if an electrical fault should occur. This
ground may consist of electrical wire connected to
unit ground lug in control compartment, or conduit
approved for electrical ground when installed in
accordance with NEC (National Electrical Code);
ANSI/NFPA 70, latest edition (in Canada, Canadian
Electrical
Code
CSA
[Canadian
Standards
Association] C22.1), and local electrical codes.
!
WARNING
NOTE
: Field--supplied wiring shall conform with the
limitations of minimum 63
_
F (33
_
C) rise.
Field Power Supply —
If equipped with optional Powered Convenience Outlet: The
power source leads to the convenience outlet’s transformer
primary are not factory connected. Installer must connect
these leads according to required operation of the
convenience outlet. If an always--energized convenience
outlet operation is desired, connect the source leads to the
line side of the unit--mounted disconnect. (Check with local
codes to ensure this method is acceptable in your area.) If a
de--energize via unit disconnect switch operation of the
convenience outlet is desired, connect the source leads to the
load side of the unit disconnect. On a unit without a
unit--mounted disconnect, connect the source leads to
compressor contactor C and indoor fan contactor IFC
pressure lugs with unit field power leads.
Refer to Fig. 30 for power transformer connections and the
discussion on connecting the convenience outlet on page 15.
Field power wires are connected to the unit at line--side
pressure lugs on compressor contactor C and indoor fan
contactor IFC (see wiring diagram label for control box
component arrangement) or at factory--installed option
non--fused disconnect switch. Max wire size is #2 AWG
(copper only). See Fig. 24 and unit label diagram for field
power wiring connections.
NOTE
: TEST LEADS -- Unit may be equipped with
short leads (pigtails) on the field line connection points on
contactor C or optional disconnect switch. These leads are
for factory run--test purposes only; remove and discard
before connecting field power wires to unit connection
points. Make field power connections directly to line
connection pressure lugs only.
582J
Summary of Contents for 582J 04 Series
Page 5: ...5 C14270 Fig 2 Unit Dimensional Drawing 582J ...
Page 6: ...6 C14271 Fig 2 Unit Dimensional Drawing cont 582J ...
Page 12: ...12 C14272 Fig 6 Rigging Label 582J ...
Page 27: ...27 C14247 Fig 39 RTU Open System Control Wiring Diagram 582J ...
Page 28: ...28 C14248 Fig 40 RTU Open System Control Wiring Diagram with Perfect Humidityt 582J ...