background image

43

Table 14 – CADM Troubleshooting

Miswired Module Indication

Recommended Troubleshooting Action

Green LED is not on,

module does not power up

Determine if both R and C module terminals are connected. Verify voltage in present at module’s R

and C terminals.

NOTE:

The CADM requires a constant nominal 24VAC power supply. The wiring to the module’s R

and C terminals must be directly from the control transformer. The module cannot receive its power

from another device that will interrupt the 24VAC power supply. See the 569J Wiring Diagram(s)

(Figs. 29 --- 31).

Green LED Intermittent,

module powers up only

when compressor runs

Determine if R and Y terminals are wired in reverse. Verify module’s R and C terminals have a con-

stant source. See “

NOTE

” above for details on R and C wiring.

TRIP LED is on but system

and compressor check OK

Verify Y terminal is wired properly per the 569J wiring diagram (see Figs. 29 --- 31). Verify voltage at

contactor coil falls below 0.5VAC when off. Verify 24VAQC is present across Y and C when thermo-

stat demand signal is present. If not, R and C are reverse wired.

TRIP LED and ALERT LED

flashing together

Verify R and C terminals are supplied with 19-28VAC.

ALERT Flash Code 3

(Compressor Short Cycling)

displayed incorrectly

Verify Y terminal is connected to 24VAC at contactor coil. Verify voltage at contactor coil falls below

0.5VAC when off.

ALERT Flash Code 5 or 6

(Open Circuit, Missing Phase)

displayed incorrectly

Check that compressor T1 and T3 wires are through module’s current sensing holes. Verify Y ter-

minal is connected to 24VAC at contactor coil. Verify voltage at contactor coil falls below 0.5VAC

when off.

Alert Flash Code *

(Welded Contactor)

displayed incorrectly

Determine if module’s Y terminal is connected. Verify Y terminal is connected to 24VAC at contactor

coil. Verify 24VAC is present across Y and C when thermostat demand signal is present. If not, R

and C are reverse wired. Verify voltage at contactor coil falls below 0.5VAC when off.

Compressor Protection

Compressor Overtemperature Protection (IP) —

A thermostat installed on the compressor motor winding

reacts to excessively high winding temperatures and shuts

off the compressor.

Crankcase Heater —

The heater minimizes absorption of liquid refrigerant by

oil in the crankcase during brief or extended shutdown

periods. The heater is wired to cycle with the compressor;

the heater is off when compressor is running, and on when

compressor is off.

The crankcase heater will operate as long as the power

circuit is energized. The main disconnect must be on to

energize the crankcase heater.

IMPORTANT:

Never open any switch or disconnect

that energizes the crankcase heater unless unit is

being serviced or is to be shut down for a prolonged

period. After a prolonged shutdown on a service job,

energize the crankcase heater for 24 hours before

starting the compressor.

Advanced Scroll Temperature Protection (ASTP) —

See “Advanced Scroll Temperature Protection (ASTP)” on

page 27.

Low-Pressure Switch —

The 569J low-pressure switch is stem-mounted on the

suction line. Switches are all fixed, non-adjustable type.

High--Pressure Switch —

The high--pressure switch is stem mounted on

the

discharge line. The switch is a fixed, non-adjustable type.

Outdoor Fans —

Each fan is supported by a formed-wire mount bolted to

the fan deck and covered with a wire guard. Fan motors

have permanently lubricated bearings.

1. Shut off unit power supply. Install lockout tag.
2. Remove outdoor fan assembly (grille, motor, and fan).
3. Loosen fan hub setscrews.
4. Adjust fan height as shown in Fig. 36.
5. Tighten setscrews to 84 in--lbs (949 N--cm).
6. Replace outdoor fan assembly.

3.6 mm +0/0/-0.8

C10103

Fig. 36 -- Outdoor Fan Blade Position

Lubrication —

Fan Motors:

The fan motors have sealed bearings. No

provisions are made for lubrication.

Compressor:

The compressor has its own oil supply. Loss

of oil due to a leak in the system should be the only

reason for adding oil after the system has been in

operation.

569J

Summary of Contents for 569J Series

Page 1: ...ary Checks 26 Start Unit 27 OPERATING SEQUENCE 37 Base Unit Controls 37 Indoor Supply Fan 37 Cooling Unit Without Economizer 37 569J 12F Unit with Hot Gas Bypass HGBP 37 Cooling Unit with Economizer 39 Heating 39 ROUTINE SYSTEM MAINTENANCE 39 Quarterly Inspection and 30 days after initial start 39 Seasonal Maintenance 39 SERVICE 39 47 Refrigeration System 39 Compressor Oil 39 Servicing Systems on ...

Page 2: ...e R 22 service equipment or components on Puron refrigerant equipment WARNING PERSONAL INJURY AND ENVIRONMENTAL HAZARD Failure to follow this warning could cause in personal injury or death Relieve pressure and recover all refrigerant before system repair or final unit disposal Wear safety glasses and gloves when handling refrigerants Keep torches and other ignition sources away from refrigerants ...

Page 3: ... new field supplied liquid line filter drier at the indoor coil just upstream of the TXV or fix orifice metering device 6 If a suction line filter drier is also to be installed in stall suction line drier downstream of suction line ser vice valve at condensing unit UNIT DAMAGE HAZARD Failure to follow this caution may result in equipment damage or improper operation Never install suction line filt...

Page 4: ...ot Gas Bypass 569J size 12 only G Single Circuit Two Stage H Single Circuit Two Stage with Low Ambient Controller Electrical Options A None C Non Fused Disconnect Service Options 0 None 1 Unpowered Convenience Outlet 2 Powered Convenience Outlet Base Unit Controls 0 Electro Mechanical Controls Not Used 0 Not Used Not Used 0 Not Used Not Used 0 Not Used Not Used 0 Not Used Voltage E 460 3 60 P 208 ...

Page 5: ...8 457 2 24 609 6 21 533 4 42 3 8 1076 0 569J 12A B RTPF 490 222 177 80 120 54 78 35 114 52 18 457 2 24 609 6 24 609 6 50 3 8 1279 2 569J 14A B RTPF 598 271 195 88 142 64 110 50 151 68 20 508 0 25 635 0 24 609 6 50 3 8 1279 2 569J 12D E F RTPF 516 234 185 84 117 53 83 38 131 59 19 482 6 23 584 2 24 609 6 50 3 8 1279 2 569J 14D E RTPF 654 297 214 97 155 70 120 54 165 75 20 508 0 25 635 0 24 609 6 50...

Page 6: ...al Airflow Cfm Total 6000 6000 6000 6000 6000 Watts Total 610 610 610 610 610 RTPF CONDENSER COIL Material Tube Fin Cu Al Cu Al Cu Al Cu Al Cu Al Coil Type 3 8 in RTPF 3 8 in RTPF 3 8 in RTPF 3 8 in RTPF 3 8 in RTPF Rows Fins per inch FPI 2 17 2 17 2 17 2 17 3 17 Face Area sq ft total 17 5 17 5 17 5 25 1 31 8 CONTROLS Pressurestat Settings psig High Cutout 630 10 630 10 630 10 630 10 630 10 Cut in...

Page 7: ...2 Watts Total 610 610 610 610 610 RTPF CONDENSER COIL Material Tube Fin Cu Al Cu Al Cu Al Cu Al Cu Al Coil Type 3 8 in RTPF 3 8 in RTPF 3 8 in RTPF 3 8 in RTPF 3 8 in RTPF Rows Fins per Meter Fins m 2 670 2 670 2 670 2 670 3 670 Face Area sq m total 1 6 1 6 1 6 2 3 3 0 CONTROLS Pressurestat Settings kPa High Cutout 4347 70 4347 70 4347 70 4347 70 4347 70 Cut in 3482 138 3482 138 3482 138 3482 138 ...

Page 8: ...eter 22 22 Nominal Airflow Cfm Total 6000 6000 Watts Total 610 610 RTPF CONDENSER COIL Material Tube Fin Cu Al Cu Al Coil Type 3 8 in RTPF 3 8 in RTPF Rows Fins per inch FPI 2 17 3 17 Face Area sq ft total 25 1 31 8 CONTROLS Pressurestat Settings psig High Cutout 630 10 630 10 Cut in 505 20 505 20 Low Cutout 54 3 54 3 Cut in 117 5 117 5 PIPING CONNECTIONS in ODS Qty Suction 1 2 1 1 1 8 1 1 1 8 1 1...

Page 9: ...otal 6000 6000 Watts Total 610 610 RTPF CONDENSER COIL Material Tube Fin Cu Al Cu Al Coil Type 3 8 in RTPF 3 8 in RTPF Rows Fins per Meter Fins m 2 670 3 670 Face Area sq m total 2 3 3 0 CONTROLS Pressurestat Settings kPa High Cutout 4347 70 4347 70 Cut in 3482 138 3482 138 Low Cutout 372 21 372 21 Cut in 807 34 807 34 PIPING CONNECTIONS in ODS Qty Suction 1 2 1 1 1 8 1 1 1 8 1 1 3 8 1 1 3 8 Qty L...

Page 10: ...he recommended clearances to satisfy local codes NOTE Consider also the effect of adjacent units on airflow performance and control box safety clearance REAR Min 18 457 mm requried for service Note Observe requirements for 39 914 mm operating clearance on either Left or Rear coil opening RIGHT Min 18 457 mm requried for service LEFT Min 18 457 mm requried for service FRONT 42 1067 mm requried for ...

Page 11: ... Refer to the indoor unit installation instructions for additional details on refrigeration specialties devices Determine equivalent line length adjustments for path and components and add to linear line lengths See Table 4 Equivalent Lengths for Common Fittings for usual fitting types Also identify adjustments for refrigeration specialties Contact Bryant Applications Engineering for additional da...

Page 12: ...t PD _F 2 9 5 0 4 5 5 0 5 0 6 5 6 4 6 5 6 4 Suction Line size 7 8 7 8 1 1 8 1 1 8 1 3 8 1 1 8 1 3 8 1 1 8 1 3 8 Suction Ln PD _F 2 4 4 8 1 2 1 8 0 6 2 4 0 9 3 1 1 1 Charge 15 7 17 5 19 7 19 8 23 1 21 6 26 1 23 6 29 2 TR 1 67 1 86 2 09 2 10 2 45 2 29 2 77 2 50 3 10 569J 14A B Liquid Line size 5 8 5 8 3 4 5 8 3 4 5 8 3 4 5 8 3 4 Liquid PD _F 0 4 0 8 0 4 1 2 0 6 1 6 0 8 2 0 1 1 Max Lift 23 16 23 10 1...

Page 13: ... 42 125 Max Lift PD _F 4 0 8 1 12 1 13 6 9 4 13 6 11 7 Suction Line size 7 8 7 8 7 8 1 1 8 1 1 8 1 1 8 Suction Ln PD _F Cap Red 1 0 1 9 2 9 1 5 0 8 1 1 1 4 Charge 17 0 18 0 19 0 19 5 20 6 23 7 21 8 25 7 TR 1 36 1 44 1 52 1 56 1 65 1 90 1 74 2 05 Legend TC Total Capacity MBH at 45 F Saturated suction 95 F outdoor air temp SC Sub cooling degrees F at liquid line valve Liquid PD _F Liquid line pressu...

Page 14: ...Circuit 1 NO VAPOR RISER REQUIRED 7 8 7 8 1 1 8 1 1 8 1 1 8 Circuit 2 7 8 7 8 1 1 8 1 1 8 1 1 8 Pressure Drop 1 1 2 1 0 9 1 2 1 5 Charge lbs 1 2 13 3 14 3 15 8 16 9 20 0 18 1 22 0 Legend Equivalent Length Equivalent tubing length including effects of refrigeration specialties devices Linear Length Typical linear tubing length 50 added to linear to define Equivalent Length for this table Liquid Lin...

Page 15: ...7 includes three different suction line size selections for Circuit 1 based on the elevation difference conditions between the 569J unit and the evaporator coil location Outdoor unit ABOVE evaporator coil This installation will have at least one suction riser segment If the vertical elevation difference is less than 20 ft 6 1 m linear feet and requires only one or two segments consider a speed ris...

Page 16: ...D E F the lower coil circuit should be connected to the 569J D E F s Circuit 1 so that the evaporator s lower coil segment is first on last off to avoid re evaporation of condensate on dry lower coil segments Circuit 1 Connections Circuit 2 Connections CKT 2 CKT 1 C10912 Fig 7 569J D E F Service Valve Locations Plan the Circuit 1 and Circuit 2 tubing segments carefully mark each segment and check ...

Page 17: ...ing unit and the evaporator coil Locate the solenoid valve at the outlet end of the liquid line near the evaporator coil connections with flow direction arrow pointed at the evaporator coil Refer to Table 10 A liquid line solenoid valve is required when the liquid line length exceeds 75 ft 23 m This valve prevents refrigerant migration which causes oil dilution to the compressor during the off cyc...

Page 18: ...compressors an accumulator is not required If an accumulator is to be added check the accumulator manufacturer s literature carefully for indication of its suitability for use with R 410A look for minimum working pressure of 200 psig 1380 kPa Select the accumulator first on the basis of its cataloged minimum capacity tons to ensure oil return from the accumulator then on tube size or holding capac...

Page 19: ...fications to unit wiring should be completed now These accessories may include Winter Start controls and Low Ambient controls Refer to the instructions shipped with the accessory Step 8 Complete Electrical Connections ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or death Do not use gas piping as an electrical ground Unit cabinet must have an uninterrupted ...

Page 20: ... v power supply the control transformer must be rewired by moving the black wire with the in female spade connector from the 230 v connection and moving it to the 208 v in male terminal on the primary side of the transformer Refer to unit label diagram for line side information Affix the crankcase heater warning sticker to the unit disconnect switch 11 13 L1 L2 L3 C TB1 208 230 3 60 460 3 60 575 3...

Page 21: ...ceptacle does not trip as required Press the RESET button to clear the tripped condition Fuse on power type The factory fuse is a Bussman Fusetron T 15 non renewable screw in Edison base type plug fuse ELECTRICAL OPERATION HAZARD Failure to follow this warning could result in personal injury or death Using unit mounted convenience outlets Units with unit mounded convenience outlet circuits will of...

Page 22: ...tal transformer accessory may be required The 569J unit requires an external temperature control device This device can be a thermostat field supplied or a thermostat emulation device provided as part of a third party Building Management System Thermostat Install a Bryant approved accessory thermostat according to installation instructions included with the accessory Locate the thermostat accessor...

Page 23: ... Transformer Wiring External Devices The 569J control transformers provide 24 v NEC Class 2 power sources to energize external control devices These devices will include the indoor fan motor contactor or control relay These devices may also include liquid line solenoid valve two on 56 J D E F models economizer control relay supplemental electric heater contactors or control relays and other device...

Page 24: ... 251 251 460 3 60 414 506 18 6 125 2 0 8 25 30 23 129 575 3 60 518 633 14 7 100 2 0 7 20 30 19 104 WITH POWERED CONVENIENCE OUTLET UNIT V Ph Hz VOLTAGE RANGE COMPRESSOR 1 OFM ea POWER SUPPLY DISCONNECT SIZE MIN MAX RLA LRA QTY FLA MCA Fuse or HACR Brkr FLA LRA 569J 07A B Units produced on or after 02 09 2015 208 230 3 60 187 253 19 6 136 2 1 5 33 33 50 50 32 32 147 147 460 3 60 414 506 8 2 66 2 0 ...

Page 25: ...ee Legend and Notes for Tables 11 and 12 below Legend and Notes for Tables 11 and 12 LEGEND FLA Full Load Amps LRA Locked Rotor Amps MOCP Maximum Over Current Protection NEC National Electrical Code RLA Rated Load Amps Units are suitable for use on electrical systems where voltage supplied to the unit terminals is not below or above the listed limits NOTES 1 The MCA and Fuse values are calculated ...

Page 26: ...ase heater proceed as follows 1 Set the space thermostat set point above the space temperature so there is no demand for cooling 2 Close the field disconnect Preliminary Charge Before starting the unit charge liquid refrigerant into the high side of the system through the liquid service valve The amount of refrigerant added must be at least 80 of the operating charge listed in the Physical Data ta...

Page 27: ...roll Temperature Protection Label 0 10 20 30 40 50 60 70 80 90 100 110 120 0 10 20 30 40 60 70 80 90 50 Compressor Unloaded Run Time Minutes Times are approximate NOTE Various factors including high humidity high ambient temperature and the presence of a sound blanket will increase cool down times Recommended Cooling Time Minutes C10081 Fig 21 Recommended Minimum Cool Down Time After Compressor is...

Page 28: ...on and the service panels are in place 350 700 1050 1400 1750 2100 2450 2800 3150 3500 3850 6 0 6 12 18 24 30 36 42 48 54 60 20 40 60 80 100 120 140 50 100 150 200 250 300 350 400 450 500 550 600 Temperature at Liquid Valve C F Pressure at Liquid Valve PSIG Kpa 6 Ton Charging Chart R410a Refrigerant Add Charge if Above the Curve Remove Charge if Below the Curve C 38AU501045 C150414 Fig 22 569J 07A...

Page 29: ... 250 300 350 400 450 500 550 600 Temperature at Liquid Valve C F Pressure at Liquid Valve PSIG Kpa 7 5 Ton Charging Chart R410a Refrigerant Add Charge if Above the Curve Remove Charge if Below the Curve Add Charge if Above the Curve Remove Charge if Below the Curve 38AU501046 C C150415 Fig 23 569J 08A B Charging Chart RTPF 569J ...

Page 30: ...60 80 100 120 140 50 100 150 200 250 300 350 400 450 500 550 600 Temperature at Liquid Valve C F Pressure at Liquid Valve PSIG Kpa 10 Ton Charging Chart R410a Refrigerant Add Charge if Above the Curve Remove Charge if Below the Curve 38AU501047 C C150416 Fig 24 569J 12A B Charging Chart RTPF 569J ...

Page 31: ...0 80 100 120 140 50 100 150 200 250 300 350 400 450 500 550 600 Temperature at Liquid Valve C F Pressure at Liquid Valve PSIG Kpa 12 5 Ton Charging Chart R410a Refrigerant Add Charge if Above the Curve Remove Charge if Below the Curve C 38AU501048 C150417 Fig 25 569J 14A B Charging Chart RTPF 569J ...

Page 32: ...AD ALL CONDENSER FANS OPERATING 60 54 48 42 36 30 24 18 12 6 0 6 140 120 100 80 60 40 20 50 350 100 700 150 1050 200 1400 250 1750 300 2100 350 2450 400 2800 450 3150 500 3500 3850 550 600 Pressure at Liquid Valve PSIG Kpa Temperature at Liquid Valve C F PN 38AU000484 REV C150338 Fig 26 569J 07G H Charging Chart RTPF 569J ...

Page 33: ...harge if Below the Curve 38AU501102 C C 38AU501102 C150418 Fig 27 569J 12D E F Charging Chart RTPF 350 700 1050 1400 1750 2100 2450 2800 3150 3500 3850 6 0 6 12 18 24 30 36 42 48 54 60 20 40 60 80 100 120 140 50 100 150 200 250 300 350 400 450 500 550 600 Temperature at Liquid Valve C F Pressure at Liquid Valve PSIG Kpa 12 5 Ton Circuit A Charging Chart R410a Refrigerant Add Charge if Above the Cu...

Page 34: ...34 C10925 Fig 29 Typical Single Circuit Single Stage 569J A B Wiring Diagram 569J ...

Page 35: ...35 C150339 Fig 30 Typical Single Circuit Two Stage 569J 07G H Wiring Diagram 569J ...

Page 36: ...36 C12547 Fig 31 Typical Dual Circuit Two Stage 569J D E F Wiring Diagram 569J ...

Page 37: ... be energized and indoor supply fan motor runs Thermostat output Y1 is energized terminal Y1 at 569J D E F unit receives 24 v 24 v received at CADM1 terminal Y If anti recycle time delay period has not expired CADM1 relay will remain open de energizing Solenoid Valve Relay 1 SVR1 and preventing compressor start When safety pressure switches are closed and CADM1 time delay expires CADM1 relay close...

Page 38: ...first stage cooling LVTB terminal Y1 is powered when CADM1 is satisfied compressor contactor C1 and Solenoid Valve Relay SVR1 are energized SVR1 contacts close providing 24 v to LVTB terminal A1 then through HGBP RELAY NC contacts to HGBP SOLENOID HGBP solenoid valve opens allowing bypass vapor from the desuperheating tank to enter the compressor suction port If thermostat calls for second stage c...

Page 39: ...earing locking collar tightness checked S Condensate drain checked Seasonal Maintenance These items should be checked at the beginning of each season or more often if local conditions and usage patterns dictate Air Conditioning S Condenser fan motor mounting bolts tightness S Compressor mounting bolts S Condenser fan blade positioning S Control box cleanliness and wiring condition S Wire terminal ...

Page 40: ... cm Factory High Flow Access Ports There are two additional access ports in the system on the suction tube between the compressor and the suction service valve and on the liquid tube near the liquid service valve see Figs 38 and 40 These are brass fittings with black plastic caps The hose connection fittings are standard in SAE Male Flare couplings The brass fittings are two piece High Flow valves...

Page 41: ...ugh a flash code The ALERT LED will blink a number of times consecutively pause and the repeat the process The number of blinks defined in Table 13 correlates to a particular abnormal condition troubleshooting tips are provided for each Alert code Reset of the ALERT may be automatic or manual If the fault condition causing the Alert is self corrected the Alert code will be removed and the CADM wil...

Page 42: ...unning c Evaporator coil is frozen d Faulty metering device e Condenser coil is dirty f Liquid line restriction filter drier blocked if present Yellow ALERT Flash Code 3 Short Cycling Compressor is running only briefly four consecutive cycles of less than three minutes each LOCKOUT 1 Loose connection between thermostat Y1 and CADM Y terminal 2 Unit short cycling on thermostat 3 System or control b...

Page 43: ... present If not R and C are reverse wired Verify voltage at contactor coil falls below 0 5VAC when off Compressor Protection Compressor Overtemperature Protection IP A thermostat installed on the compressor motor winding reacts to excessively high winding temperatures and shuts off the compressor Crankcase Heater The heater minimizes absorption of liquid refrigerant by oil in the crankcase during ...

Page 44: ...nser Fans Service Valves C10927 Fig 37 Typical Exterior Single Circuit Unit 569J 08A B shown Outdoor Coil HPS LPS High Flow Access Port C150029 Fig 38 Typical Interior Single Circuit Unit 569J 08A B shown 569J ...

Page 45: ...ns Service Valves C10929 Fig 39 Typical Exterior Two Circuit Unit 569J 14D E shown HPS LPS Outdoor Coil CKT 2 CKT 1 1 1 2 2 High Flow Access Ports C150030 Fig 40 Typical Interior Two Circuit Unit 569J 14D E shown 569J ...

Page 46: ...t performance High velocity water from a pressure washer garden hose or compressed air should never be used to clean a coil The force of the water or air jet will bend the fin edges and increase airside pressure drop CAUTION Totaline Environmentally Sound Coil Cleaner Application Instructions NOTE Proper eye protection such as safety glasses is recommended during mixing and application 1 Turn off ...

Page 47: ...tive 5 Reset lockout circuit 6 Low pressure switch open 6 Check for refrigerant undercharge obstruction of indoor airflow Make sure liquid line solenoid valve s is open 7 High pressure switch open 7 Check for refrigerant overcharge obstruction of outdoor airflow air in system Be sure outdoor fans are operating correctly 8 Compressor overtemperature switch open 8 Check for open condition Allow for ...

Page 48: ...place filters 4 Expansion valve power head defective 4 Replace power head 5 Indoor coil partially iced 5 Check low pressure setting 6 Indoor airflow restricted 6 Remove obstruction Suction Pressure High 1 Heat load excessive 1 Check for open doors or windows in vicinity of fan coil UNIT OPERATES TOO LONG OR CONTINUOUSLY 1 Low refrigerant charge 1 Add refrigerant 2 Control contacts fused 2 Replace ...

Page 49: ...plastics and roofing materials S Wrap all filter driers and service valves with wet cloth when brazing S A factory approved liquid line filter drier is required on every unit S Do not use an R 22 TXV S If indoor unit is equipped with a TXV it must be changed to a Puron TXV S Never open system to atmosphere while it is under a vacuum S When system must be opened for service recover refrigerant brea...

Page 50: ...e open 42_F 5_F close 57_F 5_F open 5 5_C 2 8_C close 13 9_C 2 8_C To override the speed control for full fan speed operation during service or maintenance either a remove sensor and place in hot water 120_F 49_C or b rewire to bypass control by connecting speed control input and output power wires Troubleshooting OBSERVATION POSSIBLE REMEDY Fans won t start All fans Check power wiring Check outdo...

Page 51: ...51 569J 07 08A B 569J 12A B 569J 14A B C11098 Fig 42 569J 07 14A B Motormaster Sensor Locations RTPF 569J ...

Page 52: ...52 569J 12D E F 569J 14D E C12551 Fig 43 569J 12 14D E F Motormaster Sensor Locations RTPF 569J ...

Page 53: ...53 D K J H G F E C B A C10800 Fig 44 Wind Baffles 569J ...

Page 54: ...4 RIGHT SIDE 25 25 1 2 26 1 4 43 1 8 4 1 4 11 1 4 18 1 4 25 1 4 32 1 4 39 1 4 DIMENSIONS MM UNIT BAFFLE A B C D E F G H J K 569J 07A B G H RTPF LEFT SIDE 718 737 756 895 33 236 439 643 846 BACK 1016 1035 1054 895 107 284 462 640 818 569J 08A B RTPF LEFT SIDE 718 737 756 895 33 236 439 643 846 BACK 1016 1035 1054 895 107 284 462 640 818 569J 12A B D E F RTPF LEFT SIDE 1022 1041 1060 1095 33 236 439...

Page 55: ...E ALL WIRING TERMINALS including main power supply TIGHT Y N HAS CRANKCASE HEATER BEEN ENERGIZED FOR 24 HOURS Y N INDOOR UNIT HAS WATER BEEN PLACED IN DRAIN PAN TO CONFIRM PROPER DRAINAGE Y N ARE PROPER AIR FILTERS IN PLACE Y N HAVE FAN AND MOTOR PULLEYS BEEN CHECKED FOR PROPER ALIGNMENT Y N DO THE FAN BELTS HAVE PROPER TENSION Y N HAS CORRECT FAN ROTATION BEEN CONFIRMED Y N PIPING ARE LIQUID LINE...

Page 56: ...ESSURE CIR 1 CIR 2 SUCTION LINE TEMP CIR 1 CIR 2 LIQUID PRESSURE CIR 1 CIR 2 LIQUID LINE TEMP CIR 1 CIR 2 ENTERING OUTDOOR UNIT AIR TEMP LEAVING OUTDOOR UNIT AIR TEMP INDOOR UNIT ENTERING AIR DB dry bulb TEMP INDOOR UNIT ENTERING AIR WB wet bulb TEMP INDOOR UNIT LEAVING AIR DB TEMP INDOOR UNIT LEAVING AIR WB TEMP COMPRESSOR 1 AMPS L1 L2 L3 COMPRESSOR 2 AMPS L1 L2 L3 NOTES 2015 Bryant Heating Cooli...

Reviews: