background image

CAUTION:

For attic installation, it is important to keep

insulation 12 in. or more away from any furnace open-
ings. Some types of insulating materials may be combus-
tibles.

This furnace is approved for reduced clearances to combustible
construction, therefore, it may be installed in a closet or similar
enclosure. Since this unit may be installed in an upflow, counter-
flow, or horizontal position, it may be located in a basement or on
the same level as area to be heated. In any case, unit should always
be installed level.

In a basement, or when installed on floor (as in a crawlspace), it is
recommended that unit be installed on a concrete pad that is 1 in.
to 2 in. thick.

When installed in counterflow position, furnace must not be
installed on combustible flooring, unless approved subbase is used.
Also, since flue pipe is in a counterflow position, Downflow
Conversion/Vent Guard Kit MUST be used. (Also, read page 9.)

When installed in a horizontal position, furnace may be suspended
by using an angle iron frame, as long as total weight of both
furnace and frame are allowed for in support calculations. (Other
methods of suspending are acceptable.) When installed in the
Horizontal Position, this furnace must not be installed on combus-
tible flooring, unless the approved Horizontal Subbase is used.

The required minimum clearances for furnace are specified in
Table 1.

The furnace should be located as close as possible to chimney or
vent in order to keep vent connections short and direct. The
furnace should also be located as near as possible to center of air
distribution system.

II.

LOCATION RELATIVE TO COOLING EQUIPMENT

When installing furnace with cooling equipment for year-round
operation, the following recommendations must be followed for
series or parallel airflow:

1. In series airflow applications, coil is mounted after furnace

in an enclosure in supply-air stream. The furnace blower is
used for both heating and cooling airflow.

WARNING:

The coil MUST be installed on air dis-

charge side of furnace. Under no circumstances should
airflow be such that cooled, conditioned air can pass over
furnace heat exchanger. This will cause condensation in
heat exchanger and possible failure of heat exchanger
which could lead to a fire hazard and/or a hazardous
condition which may lead to bodily harm. Heat exchanger
failure due to improper installation may not be covered by
warranty.

2. In parallel airflow applications, dampers must be provided

to direct air over furnace heat exchanger when heat is
desired and over cooling coil when cooling is desired.

IMPORTANT:

The dampers should be adequate to prevent

cooled air from entering furnace. If manually operated, dampers
must be equipped with a means to prevent operation of either
cooling unit or furnace unless damper is in full cool or heat
position.

INSTALLATION

I.

AIR FOR COMBUSTION AND VENTILATION

WARNING:

Installation of this furnace in an area where

it will receive contaminated combustion air must be
avoided. Such contamination would include the follow-
ing: ammonia, chlorine, hydrogen sulfide, halogenated
hydrocarbons, carbon tetrachloride, cleaning solvents,
hydrochloric acid, water softening chemicals, and similar
chemicals. Failure to follow this warning will lead to
premature rusting of heat exchanger and possible prema-
ture furnace failure and/or vent failure which could result
in fire hazard and/or bodily harm.

WARNING:

Do not block combustion-air openings in

the furnace. Any blockage will result in improper com-
bustion which may result in a fire hazard and/or cause
bodily harm.

II.

GENERAL

This furnace should be installed in a location in which facilities for
ventilation permit satisfactory combustion of oil, proper venting,
and maintenance of ambient temperature at safe limits under
normal conditions of use. The location should not interfere with
proper circulation of air within the confined space. (See NFPA-31,
Section 1.5.)

TABLE 1—MINIMUM CLEARANCES TO

COMBUSTIBLE MATERIALS (IN.)

UNIT APPLICATION

UPFLOW

DOWNFLOW

HORIZONTAL

Sides

Furnace

0

2

2

Supply Plenum and Warm-Air Duct Within 6 ft
of Furnace

1

2

1

Back

Service Clearance

0

1

0

Top

Furnace Casing or Plenum

2

2

2

Horizontal Warm-Air Duct Within 6 ft of
Furnace

2

2

3

Bottom

0

0*

0*

Flue
Pipe

Horizontally or Below Pipe

4

4

4

Vertically Above Pipe

9

9

9

Front

8

8

24

* Use approved subbase for combustible floor.
NOTE: Adequate service clearances should be provided over and above these dimensions as required.

—3—

Summary of Contents for 369RAN

Page 1: ...are intended to be used by qualified personnel who have been trained in installing this type of furnace Installation of this furnace by an unqualified person may lead to equipment damage and or a haz...

Page 2: ...quate duct work and connection to a properly sized vent The air handling capacity of this furnace is designed for cooling airflow Refer to Table 12 for expected airflows at various external duct stati...

Page 3: ...is will cause condensation in heat exchanger and possible failure of heat exchanger which could lead to a fire hazard and or a hazardous condition which may lead to bodily harm Heat exchanger failure...

Page 4: ...ctrical and fuel lines and at other openings If combustion and ventilation air must be supplied to an uncon fined space from outside an opening with a FREE AREA of not less than 1 sq in per 1000 Btuh...

Page 5: ...CONNECTED TO FLUES HAVING SUFFICIENT DRAFT AT ALL TIMES TO ENSURE SAFE AND PROPER OPERATION OF APPLIANCE For additional venting information refer to ANSI NFPA 211 Chimney Fireplaces Vents and Solid Fu...

Page 6: ...have an uninter rupted or unbroken electrical ground to minimize per sonal injury if an electrical fault should occur A green ground screw is provided in control box for this connec tion 115 V WIRING...

Page 7: ...ace of damper vertical See instructions included with damper The draft regu lator should be adjusted after furnace has been firing for at least 5 minutes and set between 0 025 and 0 035 in wc See Tabl...

Page 8: ...Fig 3 Wiring Diagram 036105 A00420 8...

Page 9: ...Fig 4 Wiring Diagram 060120 A00419 9...

Page 10: ...STANT BLOWER SWITCH This furnace is equipped with a constant low speed blower option Whenever room thermostat is not calling for heating or cooling blower runs on low speed in order to provide air cir...

Page 11: ...e flue collar panel located in front part of furnace 4 Remove baffle from secondary heat exchanger 5 Disconnect oil line and remove oil burner from furnace 6 Open two cleanout doors located in upper p...

Page 12: ...video based formats and materials All include video and or slides plus companion book Classroom Service Training plus hands on the products in our labs can mean increased confidence that really pays d...

Reviews: