background image

WARNING:

Failure to replace any heat exchanger gas-

kets with new gaskets when any heat exchanger plates or
covers are removed could lead to heat exchanger leakage,
sooting, and/or a hazardous condition capable of causing
bodily harm.

This furnace should never be operated without an air filter.
Disposable filters should be replaced at least once a year. If
equipped to provide cooling, filters should be replaced a minimum
of twice a year. Permanent filters should be cleaned at least twice
a year.

ALWAYS KEEP MAIN OIL VALVE TURNED OFF IF
BURNER IS SHUT DOWN FOR AN EXTENDED PERIOD OF
TIME.

II.

OIL BURNER

For optimum performance, oil burner nozzle should be replaced
once a year. Contact your service technician if you are unsure of
this procedure.

The procedure for nozzle installation and/or replacement is out-
lined in oil burner instruction manual which came with furnace.

After replacement of nozzle, burner should be adjusted in accor-
dance with Combustion Check section of this instruction.

III.

HEAT EXCHANGER AND FLUE PIPE

Ordinarily, it is not necessary to clean heat exchanger or flue pipe
every year, but it is necessary to have your service technician
check unit before each heating season to determine whether
cleaning or replacement of parts is required.

If cleaning is necessary, the following steps should be performed:

1. Turn off all oil and electrical supplies upstream of furnace.

CAUTION:

If furnace has been in operation, some

surfaces may be hot. Allow time for unit to cool down.

2. Disconnect flue pipe.

3. Remove flue collar panel located in front part of furnace.

4. Remove baffle from secondary heat exchanger.

5. Disconnect oil line and remove oil burner from furnace.

6. Open two cleanout doors located in upper part of front panel

of furnace.

7. Clean secondary tubes, and primary cylinder with stiff

brush and vacuum cleaner.

8. Before re-assembly, the heat exchanger and combustion

chamber should be inspected to determine if replacement is
required.

9. After cleaning, replace baffle, flue collar plate, oil burner,

and close the two cleanout access doors. Reconnect flue
pipe and oil line.

10. Re-adjust burner for proper operation.

IV.

BLOWER REMOVAL

To remove blower from furnace:

1. Turn off all oil and electrical supplies upstream of furnace.

2. Remove burner access and blower door.

3. Remove blower retaining screw (on blower shelf).

4. Remove cover from control box and disconnect thermostat

and power wires from the board.

5. Slide blower forward on rails toward front of unit.

6. Reverse items 1 through 5 to re-install blower. Refer to

wiring diagram (Fig. 3 or Fig. 4) of these instructions or
diagram located on inside of blower door to properly rewire
unit.

TABLE 12—AIRFLOW DATA (CFM)

UNIT

SIZE

BLOWER

SPEED

EXTERNAL STATIC PRESSURE IN. WC

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

036105

High

1425

1350

1305

1250

1170

1030

925

805

Med-High

1130

1045

1000

950

885

820

745

670

Med-Low

840

810

770

740

685

635

580

500

Low

725

730

740

745

730

715

690

665

060120

High

2080

2041

1965

1864

1702

1576

1474

1336

Med-High

1892

1859

1770

1675

1550

1449

1330

1217

Med-Low

1556

1475

1394

1318

1211

1134

1051

938

Low

1221

1164

1081

998

926

855

782

653

NOTES:
1. Airflow values in cubic ft per minute (CFM) rounded to nearest 5 CFM.
2. Data taken with filters in place.

—11—

Summary of Contents for 369RAN

Page 1: ...are intended to be used by qualified personnel who have been trained in installing this type of furnace Installation of this furnace by an unqualified person may lead to equipment damage and or a haz...

Page 2: ...quate duct work and connection to a properly sized vent The air handling capacity of this furnace is designed for cooling airflow Refer to Table 12 for expected airflows at various external duct stati...

Page 3: ...is will cause condensation in heat exchanger and possible failure of heat exchanger which could lead to a fire hazard and or a hazardous condition which may lead to bodily harm Heat exchanger failure...

Page 4: ...ctrical and fuel lines and at other openings If combustion and ventilation air must be supplied to an uncon fined space from outside an opening with a FREE AREA of not less than 1 sq in per 1000 Btuh...

Page 5: ...CONNECTED TO FLUES HAVING SUFFICIENT DRAFT AT ALL TIMES TO ENSURE SAFE AND PROPER OPERATION OF APPLIANCE For additional venting information refer to ANSI NFPA 211 Chimney Fireplaces Vents and Solid Fu...

Page 6: ...have an uninter rupted or unbroken electrical ground to minimize per sonal injury if an electrical fault should occur A green ground screw is provided in control box for this connec tion 115 V WIRING...

Page 7: ...ace of damper vertical See instructions included with damper The draft regu lator should be adjusted after furnace has been firing for at least 5 minutes and set between 0 025 and 0 035 in wc See Tabl...

Page 8: ...Fig 3 Wiring Diagram 036105 A00420 8...

Page 9: ...Fig 4 Wiring Diagram 060120 A00419 9...

Page 10: ...STANT BLOWER SWITCH This furnace is equipped with a constant low speed blower option Whenever room thermostat is not calling for heating or cooling blower runs on low speed in order to provide air cir...

Page 11: ...e flue collar panel located in front part of furnace 4 Remove baffle from secondary heat exchanger 5 Disconnect oil line and remove oil burner from furnace 6 Open two cleanout doors located in upper p...

Page 12: ...video based formats and materials All include video and or slides plus companion book Classroom Service Training plus hands on the products in our labs can mean increased confidence that really pays d...

Reviews: