background image

Remove burner by loosening mounting nuts and turn oil burner
slightly counterclockwise to unlock the key hole burner flange.
Prevent putting undue strain on burner wiring. (It may be neces-
sary to disconnect burner wiring in some cases.)
To reinstall burner, insert on the four burner studs on key hole
burner flange and turn it clockwise to lock it and tighten nuts.
IMPORTANT: Burner must always be installed in the upright
position with ignition control on top.

J.

Filters

WARNING:

Never operate unit without a filter or with

filter access door removed. Failure to adhere to this
warning could lead to a hazardous condition which could
lead to equipment damage and bodily harm.

An external filter rack is provided as standard equipment with
furnace. A sufficient clearance should be provided for air filter
access. Refer to Table 8 for filter rack flange dimensions for return
air duct.

START-UP, ADJUSTMENT, AND SAFETY CHECKOUT

I.

OPERATIONAL CHECKOUT

WARNING:

DO NOT TAMPER WITH UNIT OR

CONTROLS—CALL YOUR SERVICE TECHNICIAN.

Installation of furnace is now complete. Run through the following
checkout and ensure each item has been performed.

1. Correct nozzle size has been selected for desired input rate.

2. Blower wheel support is removed.

3. Electrical wiring is completed according to Fig. 3 or Fig. 4.

4. Blower access door is secured in place.

5. Valve on oil supply line is open.

6. RESET BUTTON on primary control is pushed down.

7. Flame observation door and 2 cleanout access doors located

at front of unit are closed.

8. Thermostat is set for heating mode and set above room

temperature.

If all of the above items have been performed, set main electrical
switch to ON position and burner should start. When burner starts,
proceed to Combustion Check section.

II.

COMBUSTION CHECK

In order to obtain optimum performance from oil burner, the
following setup procedures must be followed:

1. A test kit to measure smoke, stack draft, over-fire draft, oil

pump pressure, CO

2

, and stack temperatures MUST be used

in order to obtain proper air band setting. Although all of
the above measurements are required for optimum setup
and efficiency data, the most important readings that must
be taken are smoke number, over-fire draft, stack draft, and
pump pressure.

2. The proper smoke number has been established by engi-

neering tests to be between 0 and 1. This degree of smoke
emission is commonly referred to as a

trace

of smoke. It

is recommended to use a Bacharach true spot smoke test set
or equivalent.

3. In order to ensure proper draft through furnace, a baromet-

ric draft regulator (supplied with furnace) must be installed.

In order for this device to function properly, barometric damper
must be mounted with hinge pins horizontal and face of damper
vertical. (See instructions included with damper.) The draft regu-
lator should be adjusted after furnace has been firing for at least 5
minutes, and set between -0.025 and -0.035 in. wc. (See Table 9.)

4. The over-fire draft, which is taken through observation door

(located in center line above burner in front panel of
furnace), is a measurement necessary to determine if there
is a blockage between oil burner and flue outlet.

There should be a total pressure drop of between 0.020 and 0.05 in.
wc through furnace as shown in Table 9. The over-fire draft must
be set within the range shown in Table 9.

A reading outside the range shown in Table 9 (for e0.1 in.
wc) would indicate that furnace is in an extremely high-pressure
condition in primary section. This condition may be caused by any
of the following problems:

a. Excessive combustion air due to air shutter being too

wide open.

b. A lack of flue draft (chimney effect) or some other

blockage, such as soot, in secondary section of heat
exchanger.

c. Use of an oversized nozzle input.

d. Pump pressure over values listed in Table 10.

5. The CO

2

and stack temperature instruments enable you to

obtain data required to determine thermal efficiency of
furnace.

6. An oil filter should be installed as close to burner as

possible with ALL oil burners and is essential on lower
firing rate burners. We recommend the use of a low
pressure drop oil filter such as the General Filter, Inc. model
#1A-25A or equivalent.

7. The oil pressure regulator is factory set to give oil pressure

of 135 psig for the model having 105,000 BTUH input and
135 psig for the model haveing 119,000 BTUH input. The
firing rate noted on nameplate may be obtained using the
nozzles and pump pressures indicated in table #5. The
proper oil burner turbulator setting for all the firing rates
is 0 (zero)
.

8. On a new installation, air entrapped in oil line leading from

tank to nozzle must be thoroughly purged in order to
prevent excessive after drip. The oil pump is provided with
a special fitting which allows purging of any air between
tank and oil pump. The proper procedure for performing
this operation is as follows:

a. Place a piece of clear plastic 1/4 in. diameter tubing over

purge fitting on oil pump.

b. Start oil burner, then open purge fitting and allow burner

to run until purge tube is completely free of air bubbles.

c. Tighten purge fitting. Allow oil to run to nozzle and fire

burner.

TABLE 8—FILTER AND FLANGE (IN.)

UNIT

SIZE

AIR FILTER

SIZE

FLANGE OPENING

SIZE

036105

16 X 24 X 1

or

16 X 25 X 1

15 X 23

060120

20 X 30 X 1

19 X 29

TABLE 9—FURNACE DRAFT CONDITIONS (IN. WC)

FURNACE

INPUT

(BTUH)

FLUE

DRAFT

MINIMUM

OVER-FIRE

DRAFT

MAXIMUM

TOTAL RESTRICTION

THROUGH

HEAT EXCHANGER

70,000

-0.025

0.010

0.020 to 0.035

91,000

-0.025

0.020

0.030 to 0.045

105,000

-0.025

0.025

0.035 to 0.050

119,000

-0.025

0.025

0.035 to 0.050

140,000

-0.025

0.025

0.035 to 0.050

154,000

-0.025

0.025

0.035 to 0.050

—7—

Summary of Contents for 369RAN

Page 1: ...are intended to be used by qualified personnel who have been trained in installing this type of furnace Installation of this furnace by an unqualified person may lead to equipment damage and or a haz...

Page 2: ...quate duct work and connection to a properly sized vent The air handling capacity of this furnace is designed for cooling airflow Refer to Table 12 for expected airflows at various external duct stati...

Page 3: ...is will cause condensation in heat exchanger and possible failure of heat exchanger which could lead to a fire hazard and or a hazardous condition which may lead to bodily harm Heat exchanger failure...

Page 4: ...ctrical and fuel lines and at other openings If combustion and ventilation air must be supplied to an uncon fined space from outside an opening with a FREE AREA of not less than 1 sq in per 1000 Btuh...

Page 5: ...CONNECTED TO FLUES HAVING SUFFICIENT DRAFT AT ALL TIMES TO ENSURE SAFE AND PROPER OPERATION OF APPLIANCE For additional venting information refer to ANSI NFPA 211 Chimney Fireplaces Vents and Solid Fu...

Page 6: ...have an uninter rupted or unbroken electrical ground to minimize per sonal injury if an electrical fault should occur A green ground screw is provided in control box for this connec tion 115 V WIRING...

Page 7: ...ace of damper vertical See instructions included with damper The draft regu lator should be adjusted after furnace has been firing for at least 5 minutes and set between 0 025 and 0 035 in wc See Tabl...

Page 8: ...Fig 3 Wiring Diagram 036105 A00420 8...

Page 9: ...Fig 4 Wiring Diagram 060120 A00419 9...

Page 10: ...STANT BLOWER SWITCH This furnace is equipped with a constant low speed blower option Whenever room thermostat is not calling for heating or cooling blower runs on low speed in order to provide air cir...

Page 11: ...e flue collar panel located in front part of furnace 4 Remove baffle from secondary heat exchanger 5 Disconnect oil line and remove oil burner from furnace 6 Open two cleanout doors located in upper p...

Page 12: ...video based formats and materials All include video and or slides plus companion book Classroom Service Training plus hands on the products in our labs can mean increased confidence that really pays d...

Reviews: