background image

control and all time delays have expired. Short the
TWIN/TEST terminal to ground or C

OM

for 1 to 4 sec. (See

Fig. 11.)

NOTE:

The component test feature will not operate if the control

is receiving any thermostat signals or until all time delays have
expired.

The component test sequence is as follows:

a. The furnace control checks itself, operates the inducer

motor on low speed for 7 sec and on high speed for 7 sec,
then stops.

b. The hot surface ignitor is energized for 15 sec, then

de-energized.

c. The blower motor operates on low-gas-heat/heat pump

low-heat/low-cool/continuous fan speed for 7 sec, then
stops.

d. The blower motor operates on high-gas heat for 7 sec,

then stops.

e. The blower motor operates on heat pump high-heat/high-

cool speed for 7 sec, then stops.

The gas valve and humidifier terminal HUM are not
energized for safety reasons.

NOTE:

The EAC terminals are energized when the blower is

energized.

2. After all connections have been made, purge gas lines and

check for leaks.

WARNING:

Never purge a line into a combustion

chamber. Never use matches, candles, flame, or other
sources of ignition for the purpose of checking leakage.
Use a soap-and-water solution to check for leakage. A
failure to follow this warning can cause a fire, explosion,
personal injury, or death.

3. To operate furnace, follow procedures on operating instruc-

tions label attached to furnace.

4. With furnace operating, set thermostat below room tem-

perature and observe that furnace goes off. Set thermostat
above room temperature and observe that furnace restarts.

D.

Adjustments

1. Set gas input rate.

Furnace gas input rate on rating plate is for installations at
altitudes up to 2000 ft.

In the U.S.A., input rating for altitudes above 2000 ft must
be reduced by 4 percent for each 1000 ft above sea level.

In Canada, input rating must be derated by 10 percent for
altitudes of 2000 ft to 4500 ft above sea level.

Furnace input rate must be within

±

2 percent of input on

furnace rating plate.

2. Determine natural gas orifice size and manifold pressure for

correct input.

a. Obtain yearly heat value average (at installed altitude)

from local gas supplier.

b. Obtain yearly specific gravity average from local gas

supplier.

c. Verify furnace model. Table 9 can only be used for

model 330AAV Furnaces.

d. Find installation altitude in Table 9.

NOTE:

For Canada altitudes of 2000 to 4500 ft, use U.S.A.

altitudes of 2001 to 3000 ft in Table 9.

e. Find closest natural gas heat value and specific gravity in

Table 9.

f. Follow heat value and specific gravity lines to point of

intersection to find orifice size and low- and high-heat
manifold pressure settings for proper operation.

EXAMPLE: (0—2000 ft altitude)
Heating value = 1075 Btu/cu ft
Specific gravity = 0.62
Therefore: Orifice No. 45

Manifold pressure: 3.4-in. wc for high heat

1.4-in. wc for low heat

* Furnace is shipped with No. 45 orifices. In this example,
all main burner orifices are the correct size and do not need
to be changed to obtain proper input rate.

g. Check and verify burner orifice size in furnace. NEVER

ASSUME ORIFICE SIZE; ALWAYS CHECK AND
VERIFY.

3. Adjust manifold pressure to obtain input rate.

a. Remove caps that conceal adjustment screws for low-

and high-heat gas valve regulators. (See Fig. 14.)

b. Move setup switch SW-2 on control center to ON

position. (See Fig. 12.) This keeps furnace locked in
low-heat operation.

c. Jumper R and W/W1 thermostat connections on control

center to start furnace.

d. Turn low-heat adjusting screw (5/64 hex Allen wrench)

counterclockwise (out) to decrease input rate or clock-
wise (in) to increase input rate.

NOTE:

DO NOT set low-heat manifold pressure less than 1.3-in.

wc or more than 1.7-in. wc for natural gas. If manifold pressure is
outside this range, change main burner orifices.

CAUTION:

DO NOT bottom out gas valve regulator

adjusting screw. This can result in unregulated manifold
pressure and result in excess overfire and heat exchanger
failures.

NOTE:

If orifice hole appears damaged or it is suspected to have

been redrilled, check orifice hole with a numbered drill bit of
correct size. Never redrill an orifice. A burr-free and squarely
aligned orifice hole is essential for proper flame characteristics.

CAUTION:

DO NOT redrill orifices. Improper drilling

(burrs, out-of-round holes, etc.) can cause excessive
burner noise and misdirection of burner flames. This can
result in flame impingement of burners and heat exchang-
ers, causing failures.

A93059

BURNER 

ORIFICE

—15—

Summary of Contents for 330AAV

Page 1: ...labels attached to or shipped with the unit and other safety precautions that may apply Follow all safety codes In the United States refer to the National Fuel Gas Code NFGC NFPA No 54 1999 ANSI Z223...

Page 2: ...6 12 11 16 4 134 042080 17 1 2 15 7 8 16 4 150 048080 21 19 3 8 19 1 2 4 154 036100 17 1 2 15 7 8 16 4 160 048100 21 19 3 8 19 1 2 4 166 060100 24 1 2 22 7 8 23 4 184 048120 21 19 3 8 19 1 2 5 178 060...

Page 3: ...require these instructions as a minimum for a safe installation CAUTION Application of this furnace should be in doors with special attention given to vent sizing and material gas input rate air tempe...

Page 4: ...on and ventilation air must be provided in accordance with Section 5 3 Air for Combustion and Ventilation of the NFGC or applicable provisions of the local building codes Canadian installations must b...

Page 5: ...with the outdoors shall be provided See item 2 below c If furnace is installed on a raised platform to provide a return air plenum and return air is taken directly from hallway or space adjacent to fu...

Page 6: ...sories All accesso ries MUST be connected external to furnace main casing IV RETURN AIR CONNECTIONS CAUTION For airflow requirements above 1800 CFM see Air Delivery table in Product Data literature fo...

Page 7: ...le in each bottom corner of furnace as shown in Fig 7 2 Install nut on bolt and install bolt and nut in hole Install flat washer if desired 3 Install another nut on other side of furnace base Install...

Page 8: ...een gas control manifold and manual shutoff valve WARNING Use the proper length of pipes and ad equate piping support to avoid stress on the gas control manifold A failure to follow this warning can c...

Page 9: ...24 v humidifier connection The terminals are energized with 24v 0 5 amp maximum when the gas valve is energized Fig 9 Heating and Cooling Application Wiring Diagram 1 Stage Thermostat and Condensing U...

Page 10: ...and high gas heat for optimum comfort Setup switch 2 SW 2 must be in the factory shipped OFF position See Fig 12 and Tables 6 and 7 for setup switch information If a 2 stage heating thermostat is to b...

Page 11: ...ec tion is based on stored history of thermostat cycle times When wall thermostat calls for heat R W W1 circuit closes The furnace control performs a self check verifies the low heat and high heat pre...

Page 12: ...high gas heat and vice versa a Switching from low to high gas heat If thermostat R W W1 circuit for low gas heat is closed and R W2 circuit for high gas heat closes the control CPU switches the induc...

Page 13: ...et thermal overload switches 4 Blower motor speed selections are for average conditions See Installation Instructions for details on optimumspeed selection 5 Replace only with a 3 AMP fuse 6 Auxiliary...

Page 14: ...r motor BLWM speed by sensing only G for low cool speed and Y2 for high cool speed 2 The EAC terminals EAC 1 and EAC 2 are ener gized with 115v when the blower motor BLWM is operating on either coolin...

Page 15: ...al gas supplier b Obtain yearly specific gravity average from local gas supplier c Verify furnace model Table 9 can only be used for model 330AAV Furnaces d Find installation altitude in Table 9 NOTE...

Page 16: ...t connections See Fig 12 This keeps furnace locked in high heat operation Repeat items h through k for high heat operation EXAMPLE High heat operation at 0 2000 ft altitude Furnace input from rating p...

Page 17: ...3 6 1 5 44 3 8 1 6 43 3 4 1 4 43 3 5 1 5 43 3 6 1 5 2001 825 44 3 4 1 4 44 3 5 1 5 44 3 7 1 5 44 3 8 1 6 43 3 4 1 4 to 850 44 3 2 1 4 44 3 3 1 4 44 3 4 1 5 44 3 6 1 5 44 3 7 1 5 3000 875 45 3 7 1 6 4...

Page 18: ...4 750 45 3 4 1 4 45 3 5 1 5 45 3 6 1 5 45 3 7 1 6 45 3 8 1 6 775 45 3 2 1 3 45 3 3 1 4 45 3 4 1 4 45 3 5 1 5 45 3 6 1 5 5001 800 47 3 5 1 5 47 3 6 1 5 45 3 2 1 3 45 3 3 1 4 45 3 4 1 4 825 48 3 8 1 6...

Page 19: ...Pressure High Low U S A Only 600 45 3 4 1 4 45 3 5 1 5 45 3 6 1 5 45 3 7 1 6 45 3 8 1 6 625 47 3 7 1 6 45 3 2 1 4 45 3 3 1 4 45 3 4 1 4 45 3 5 1 5 8001 650 47 3 4 1 4 47 3 5 1 5 47 3 6 1 5 45 3 2 1 3...

Page 20: ...TE CU FT HR SECONDS FOR 1 REVOLUTION SIZE OF TEST DIAL SECONDS FOR 1 REVOLUTION SIZE OF TEST DIAL 1 cu ft 2 cu ft 5 cu ft 1 cu ft 2 cu ft 5 cu ft 10 11 12 13 14 360 327 300 277 257 720 655 600 555 514...

Page 21: ...normal start up allow furnace to operate for 2 minutes then block flue outlet 100 percent Furnace should cycle off within 2 minutes d Remove blockage and reconnect vent connector to furnace flue coll...

Page 22: ...22...

Page 23: ...23...

Page 24: ...video based formats and materials All include video and or slides plus companion book Classroom Service Training plus hands on the products in our labs can mean increased confidence that really pays d...

Reviews: