Bryant 330AAV Installation, Start-Up, And Operating Instructions Manual Download Page 5

For Example:

330AAV FURNACE HIGH-FIRE

INPUT BTUH

MINIMUM SQ FT WITH

7-1/2 FT CEILING

40,000

267

60,000

400

80,000

534

100,000

667

120,000

800

133,000

887

If the unconfined space is of unusually tight construction, air for
combustion and ventilation MUST come from either the outdoors
or spaces freely communicating with the outdoors. Combustion
and ventilation openings must be sized the same as for a confined
space as defined below. Return air must not be taken from the
room unless an equal or greater amount of air is supplied to the
room.

B.

Confined Space

A confined space is defined as a space whose volume is less than
50 cu ft per 1000 Btuh of total input ratings of all appliances
installed in that space. A confined space MUST have provisions
for supplying air for combustion, ventilation, and dilution of flue
gases using 1 of the following methods. (See Fig. 3 and Table 2.)

NOTE:

In determining free area of an opening, the blocking

effect of louvers, grilles, and screens must be considered. If free
area of louver or grille design is unknown, assume that wood
louvers have a 20 percent free area and metal louvers or grilles
have a 60 percent free area. Screens, when used, must not be
smaller than 1/4-in. mesh. Louvers and grilles must be constructed
so they cannot be closed.
The size of the openings depends upon whether air comes from
outside of the structure or an unconfined space inside the structure.

1. All air from inside the structure requires 2 openings (for

structures not usually tight):

a. Each opening MUST have at least 1 sq in. of free area

per 1000 Btuh of total input for all equipment within the
confined space, but not less than 100 sq in. per opening.
(See Fig. 3 and Table 2.) The minimum dimension of air
openings shall not be less than 3 in.

b. If building is constructed unusually tight, a permanent

opening directly communicating with the outdoors shall
be provided. See item 2 below.

c. If furnace is installed on a raised platform to provide a

return-air plenum, and return air is taken directly from
hallway or space adjacent to furnace, all air for combus-
tion must come from outdoors.

2. Air from outside the structure requires 1 of the following

methods:

a. If combustion air is taken from outdoors through 2

vertical ducts, the openings and ducts MUST have at
least 1 sq in. of free area per 4000 Btuh of total input for
all equipment within the confined space. (See Fig. 4 and
Table 2.)

b. If combustion air is taken from outdoors through 2

horizontal ducts, the openings and ducts MUST have at
least 1 sq in. of free area per 2000 Btuh of total input for
all equipment within the confined space. (See Fig. 4 and
Table 2.)

c. If combustion air is taken from outdoors through a single

opening or duct (horizontal or vertical) commencing
within 12 in. of the top of the confined space, opening
and duct MUST have at least 1 sq in. of free area per
3000 Btuh of the total input for all equipment within the
confined space and not less than the sum of the areas of
all vent connectors in the confined space. (See Fig. 4 and

Fig. 3—Confined Space: Air for Combustion and Ventilation

from an Unconfined Space

A89012

SUPPLY

AIR

6

 MIN

(FRONT) 

RETURN AIR

VENT THROUGH ROOF 

1 SQ IN.
PER 1000
BTUH* IN DOOR

OR WALL

12

 MAX 

1 SQ IN.
PER 1000
BTUH* IN DOOR

OR WALL

12

 MAX 

INTERIOR

HEATED

SPACE 

* Minimum opening size is 100 sq in. with
  minimum dimensions of 3 in. 

† 

Minimum of 3 in. when type-B1 vent is used.

UNCONFINED
SPACE 

CONFINED

SPACE 

Fig. 4—Confined Space: Air for Combustion and Ventilation

from Outdoors

A89013

1 SQ IN.

PER

4000

BTUH*

DUCTS

TO

OUTDOORS

1 SQ IN.
PER 4000
BTUH*

SUPPLY

AIR

VENT
THROUGH
ROOF

D

B

A

C

E  

1 SQ IN.
PER 4000
BTUH*

DUCT

TO

OUTDOORS

RETURN AIR

1 SQ IN.
PER 2000
BTUH*

1 SQ IN.
PER 2000
BTUH*

DUCTS

TO

OUTDOORS

12

 MAX

12

 MAX

12

 MAX

Use any of the following
combinations of openings:
A & B     C & D    D & E     F & G

NOTE:

*

Minimum dimensions of 3 in.

CONFINED

SPACE

12

MAX

12

MAX

OUTDOORS

1 SQ IN.

PER

4000

BTUH*

F

G

—5—

Summary of Contents for 330AAV

Page 1: ...labels attached to or shipped with the unit and other safety precautions that may apply Follow all safety codes In the United States refer to the National Fuel Gas Code NFGC NFPA No 54 1999 ANSI Z223...

Page 2: ...6 12 11 16 4 134 042080 17 1 2 15 7 8 16 4 150 048080 21 19 3 8 19 1 2 4 154 036100 17 1 2 15 7 8 16 4 160 048100 21 19 3 8 19 1 2 4 166 060100 24 1 2 22 7 8 23 4 184 048120 21 19 3 8 19 1 2 5 178 060...

Page 3: ...require these instructions as a minimum for a safe installation CAUTION Application of this furnace should be in doors with special attention given to vent sizing and material gas input rate air tempe...

Page 4: ...on and ventilation air must be provided in accordance with Section 5 3 Air for Combustion and Ventilation of the NFGC or applicable provisions of the local building codes Canadian installations must b...

Page 5: ...with the outdoors shall be provided See item 2 below c If furnace is installed on a raised platform to provide a return air plenum and return air is taken directly from hallway or space adjacent to fu...

Page 6: ...sories All accesso ries MUST be connected external to furnace main casing IV RETURN AIR CONNECTIONS CAUTION For airflow requirements above 1800 CFM see Air Delivery table in Product Data literature fo...

Page 7: ...le in each bottom corner of furnace as shown in Fig 7 2 Install nut on bolt and install bolt and nut in hole Install flat washer if desired 3 Install another nut on other side of furnace base Install...

Page 8: ...een gas control manifold and manual shutoff valve WARNING Use the proper length of pipes and ad equate piping support to avoid stress on the gas control manifold A failure to follow this warning can c...

Page 9: ...24 v humidifier connection The terminals are energized with 24v 0 5 amp maximum when the gas valve is energized Fig 9 Heating and Cooling Application Wiring Diagram 1 Stage Thermostat and Condensing U...

Page 10: ...and high gas heat for optimum comfort Setup switch 2 SW 2 must be in the factory shipped OFF position See Fig 12 and Tables 6 and 7 for setup switch information If a 2 stage heating thermostat is to b...

Page 11: ...ec tion is based on stored history of thermostat cycle times When wall thermostat calls for heat R W W1 circuit closes The furnace control performs a self check verifies the low heat and high heat pre...

Page 12: ...high gas heat and vice versa a Switching from low to high gas heat If thermostat R W W1 circuit for low gas heat is closed and R W2 circuit for high gas heat closes the control CPU switches the induc...

Page 13: ...et thermal overload switches 4 Blower motor speed selections are for average conditions See Installation Instructions for details on optimumspeed selection 5 Replace only with a 3 AMP fuse 6 Auxiliary...

Page 14: ...r motor BLWM speed by sensing only G for low cool speed and Y2 for high cool speed 2 The EAC terminals EAC 1 and EAC 2 are ener gized with 115v when the blower motor BLWM is operating on either coolin...

Page 15: ...al gas supplier b Obtain yearly specific gravity average from local gas supplier c Verify furnace model Table 9 can only be used for model 330AAV Furnaces d Find installation altitude in Table 9 NOTE...

Page 16: ...t connections See Fig 12 This keeps furnace locked in high heat operation Repeat items h through k for high heat operation EXAMPLE High heat operation at 0 2000 ft altitude Furnace input from rating p...

Page 17: ...3 6 1 5 44 3 8 1 6 43 3 4 1 4 43 3 5 1 5 43 3 6 1 5 2001 825 44 3 4 1 4 44 3 5 1 5 44 3 7 1 5 44 3 8 1 6 43 3 4 1 4 to 850 44 3 2 1 4 44 3 3 1 4 44 3 4 1 5 44 3 6 1 5 44 3 7 1 5 3000 875 45 3 7 1 6 4...

Page 18: ...4 750 45 3 4 1 4 45 3 5 1 5 45 3 6 1 5 45 3 7 1 6 45 3 8 1 6 775 45 3 2 1 3 45 3 3 1 4 45 3 4 1 4 45 3 5 1 5 45 3 6 1 5 5001 800 47 3 5 1 5 47 3 6 1 5 45 3 2 1 3 45 3 3 1 4 45 3 4 1 4 825 48 3 8 1 6...

Page 19: ...Pressure High Low U S A Only 600 45 3 4 1 4 45 3 5 1 5 45 3 6 1 5 45 3 7 1 6 45 3 8 1 6 625 47 3 7 1 6 45 3 2 1 4 45 3 3 1 4 45 3 4 1 4 45 3 5 1 5 8001 650 47 3 4 1 4 47 3 5 1 5 47 3 6 1 5 45 3 2 1 3...

Page 20: ...TE CU FT HR SECONDS FOR 1 REVOLUTION SIZE OF TEST DIAL SECONDS FOR 1 REVOLUTION SIZE OF TEST DIAL 1 cu ft 2 cu ft 5 cu ft 1 cu ft 2 cu ft 5 cu ft 10 11 12 13 14 360 327 300 277 257 720 655 600 555 514...

Page 21: ...normal start up allow furnace to operate for 2 minutes then block flue outlet 100 percent Furnace should cycle off within 2 minutes d Remove blockage and reconnect vent connector to furnace flue coll...

Page 22: ...22...

Page 23: ...23...

Page 24: ...video based formats and materials All include video and or slides plus companion book Classroom Service Training plus hands on the products in our labs can mean increased confidence that really pays d...

Reviews: