7.6
Brüel & Kjær Vibro AS-247 dual axis accelerometers
on channel 1-10
AS-247 sensor mounting.
AS 247 is a bi-axial sensor, that is, it produces two output signals
one for each axis. In the figure these two axes are denoted XSIG
and ZSIG.
If the AS 247 sensor shall be connected to other AC/DC channels
than channel 11 or channel 12 the +24 signal must be looped to
the SP terminal. The +24 V supply may also be connected to the
sensor power input besides the power connector on the top of the
VCM-3
. Refer to the section “Power Connection – External
Sensor Power” in the “Power Connections” section of this manual.
The sensor power terminal “SP” is internally connected to the
individual “SP” terminals for each sensor.
The color of the connection wires corresponds to sensor
connection cable AC-1401.
NOTE!
Maximum current output in this configuration
is 55 mA in total