5-4
Section 5 Transducer Blocks
Installation and Operation Manual
X-DPT-FF-MT3809G-Alarms-eng
Part Number: 541B218AAG
December, 2017
Model MT3809G F
OUNDATION
TM
Fieldbus
Index
Sub Index
Parameter Name
Description
Data Type
Valid Values
Initialized
Value
Read only or
Read/W
rite
Table 5-1
Parameters of the Analog Input Transducer Block (continued)
Table continued on next page.
46
1
PULSE_OUTPUT.UOM
Unit of measurement used to generate the pulses
U16
Supported UOMS
Gallon
Read/
Write
46 2 PULSE_OUTPUT.SCALER
The scale value scales the number of pulses according
to het flow
Float
0.1 to 10.0
1.0
Read/
Write
46 3
PULSE_OUTPUT.
PULSE_WIDTH
The pulse width of each pulse on the pulse output
Float
0.00 to 50.0
50.0
Read/
Write
47
WEIGHTS_MEASURES_CALI
B
Information about the calibration
U32
0
Read
48
WEIGHTS_MEASURES_CON
FIG
Information about the calibration
U32
0
Read
49 INFO_METER
The info meter contains information about the meter.
The values which are a member of info_meter are not
used in the process
49 1
INFO_METER.
FLOW_HI_LIMIT
The maximum limit of flow for this meter
Float
Calibrated
Value
Read/
Write
49 2
INFO_METER.
FLOW_LO_LIMIT
The minimum of flow for this meter
Float
Calibrated
Value
Read/
Write
49 3
INFO_METER.
TEMP_HI_LIMIT
The maximum temperature for this meter
Float
Calibrated
Value
Read/
Write
49 4
INFO_METER.
TEMP_LO_LIMIT
The minimum temperature for this meter
Float
Calibrated
Value
Read/
Write
49 5
INFO_METER.
MATL
The material of this meter
U8
Calibrated
Value
Read/
Write
49 6
INFO_METER.
PRESSURE_HI_LIMIT
The maximum pressure for this meter
Float
Calibrated
Value
Read/
Write
49 7
INFO_METER.
PRESSURE_LO_LIMIT
The minimum pressure for this meter
Float
Calibrated
Value
Read/
Write
49 8
INFO_METER.
PRESSURE_DROP_LIMIT
Float
Calibrated
Value
Read/
Write
49 9
INFO_METER.
FLANG_MATL
U8
Calibrated
Value
Read
/Write
49 10
INFO_METER.
FLANGE_TYPE
U8
Calibrated
Value
Read/
Write
49 11
INFO_METER.
FLOAT_MATL
U8
Calibrated
Value
Read/
Write
49 12
INFO_METER.
FLOAT_TYPE
Visible
String
ASCII
Max 8 chars
Calibrated
Value
Read/
Write
49 13
INFO_METER.
ORING_MATL
U8
Calibrated
Value
Read/
Write
49 14
INFO_METER.
SIZE
U8
Calibrated
Value
Read/
Write
50
INFO_ACCESSORIES
Accessories attached to the meter
U8
Calibrated
Value
Read/
Write
51
MAGNET_ANGLE_ADJUSTE
D
The magnet angle of the measuring device after a zero
adjust
Float
0.0
Read
52
MAGNET_ANGLE_ABSOLUT
E
The magnet angle of the measuring device
Float
0.0
Read
53 MAGNET_ANGLE_OFFSET
The offset which is used to calculate the magnet
adjusted angle from the absolute angle
Float
0.0
Read
54 VISCOSITY
54
1
VISCOSITY.UOM
Units of measurements for the viscosity
U16
Supported UOMs
cP
Read/
Write
54 2 VISCOSITY.VALUE
Float
1
Read/
Write
55
Calibration
This group contains information about the calibration
55 1
CALIB.
FLUID
Visible
String
Reserved, do not use
Read/
Write
55 2
CALIB.
TOOL
Visible
String
Reserved, do not use
Read/
Write
55 3
CALIB.
ACC_CLASS
Visible
String
Reserved, do not use
Read/
Write
55 4
CALIB.
NAME
Visible
String
Reserved, do not use
Read/
Write
55 5
CALIB.
CALIB_DATA
Visible
String
Reserved, do not use
Read/
Write
55 6
CALIB.
CALIB_FLOW_RATE_UOM
U16
Supported
UOMs
Calibrated
Value
Read/
Write
55 7
CALIB.
CALIB_TEMPERATURE_UOM
U16
Reserved, do not use
Read/
Write
55 8
CALIB.
CALIB_TEMPERATURE
Float
Reserved, do not use
Read/
Write
55 9
CALIB.
CALIB_PRESSURE_UOM
U16
Reserved, do not use
Read/
Write
55 10
CALIB.
CALIB_PRESSURE
Float
Reserved, do not use
Read/
Write
55 11
CALIB.
CALIB_DENS_UOM
U16
Reserved, do not use
Read/
Write
55 12
CALILB.
CALIB_DENSITY
Float
Reserved, do not use
Read/
Write
55 13
CALIB.
CALIB_VISCOSITY_UOM
U16
Reserved, do not use
Read/
Write
55 14
CALIB.
CALIB_VISCOSITY
Float
Reserved, do not use
Read/
Write