5-3

Section 5 Transducer Blocks

Installation and Operation Manual

X-DPT-FF-MT3809G-Alarms-eng
Part Number: 541B218AAG

December, 2017

Model MT3809G F

OUNDATION

TM 

Fieldbus

Index

 

Sub Index

 

Parameter Name 

Description 

Data Type

 

Valid Values 

Initialized 

Value 

Read only or

 

Read/W

rite

 

Table 5-1

 Parameters of the Analog Input Transducer Block (continued)

 29 

 

MODEL_NUMBER 

Model number of the assembled device 

 

ASCII 
Max 20 chars 

Calibrated 
Value

Read/ 
Write

30 

 

RES_TOTALIZER 

A resettable totalizer independent of the function block

30 

RES_TOTALIZER.UOM 

The units of measurement which the totalizer will use  

U16 

Supported UOMs 

Gallon 

Read/ 
Write

30 

RES_TOTALIZER.VALUE 

The value of the resettable totalizer

Float

0.0 Read

31 

 

RESET_RES_TOTALIZER 

Used to reset the resettable totalizer 

U8 

(0) Idle 
(1) Reset

Idle 

Read/ 
Write

32   RES_TOT_DIG_DEC 

Setting of max number of integer digits before automatic 
reset

U8 0 

to 

Read/ 
Write

33   INV_TOTALIZER 

A inventory totalizer which is independent of the function 
block

 

 

 

 

33 

INV_TOTALIZER.UOM 

The units of measurement used for the totalizer 

U16 

Supported UOMs 

Gallon 

Read/ 
Write

33 

INV_TOTALIZER.VALUE 

The value of the inventory totalizer

Float

0.0 Read

34   INV_TOT_DIG_DEC 

Setting of max number of integer digits before automatic 
reset

U8 0 

to 

Read/ 
Write

35   LO_FLOW 

The settings for the low flow alarm with a dedicated 
alarm output on the transmitter

 

 

 

 

35 

LO_FLOW.ALARM_EN 

Enables or disables the low flow alarm 

U8 

(0) Disabled 
(1) Enabled

(1) Enabled 

Read/ 
Write

35 2 LO_FLOW.ALARM_TYPE 

A non latching alarm type will clear the alarm if the flow 
is above the low flow setting

U8 

(0) Non-latched 
(1) Latched

(0) Non-latched 

Read/ 
Write

35 3 LO_FLOW.ALARM_LIMIT 

The value which will cause the alarm if the flow value 
falls below this value

Float  

9.99 

Read/ 
Write

35 4 

LO_FLOW. 
ALARM_LIMIT_DELAY 

The time a flow needs to be below the setting before the 
alarm is triggered 

U8 

0 to 255 Seconds 

Read/ 
Write

36   HIGH_FLOW 

The settings for the high flow alarm with a dedicated 
alarm output on the transmitter

 

 

 

 

36 

HIGH_FLOW.ALARM_EN 

Enables or disables the high flow alarm 

U8 

(0) Disabled 
(1) Enabled

(1) Enabled 

Read/ 
Write

36 2 

HIGH_FLOW. 
ALARM_TYPE 

A non latching alarm type will clear the alarm if the flow 
is below the high flow setting

U8 

(0) Non-latched 
(1) Latched

(0) Non-latched 

Read/ 
Write

36 3 

HIGH_FLOW. 
ALARM_LIMIT 

The value which will cause the alarm if the flow value 
rises above this value

Float  

90.0 

Read/ 
Write

36 4 

HIGH_FLOW. 
ALARM_LIMIT_DELAY 

The time a flow needs to be above the setting before the 
alarm is triggered 

U8 0 

to 

255 

Read/ 
Write

37   PULS_OUT_CFG 

This alarm is used if the configuration for the pulse 
output is wrong. This alarm has no physical output on 
the transmitter

 

 

 

 

37 1 

PULS_OUT_CFG. 
ENABLE 

Enables or disables the pulse output configuration alarm 

U8 

(0) Disabled 
(1) Enabled

(1) Enabled 

Read/ 
Write

37 2 PULS_OUT_CFG.TYPE 

A non latching alarm type will clear the alarm if 
configuration is corrected.

U8 

(0) Non-latched 
(1) Latched

(1)Latched 

Read/ 
Write

38   PULS_OUT_OVERRUN 

This alarm is used if the pulse output cannot keep up 
with the pulse algorithm

 

 

 

 

38 1 

PULS_OUT_ OVERRUN. 
ENABLE 

Enables or disables the pulse output overrun alarm 

U8 

(0) Disabled 
(1) Enabled

(0) Disabled 

Read/ 
Write

38 2 

PULS_OUT_ OVERRUN. 
TYPE 

A non latching alarm type will clear the alarm if overrun 
is solved 

U8 

(0) Non-latched 
(1) Latched

(0) Non-latched 

Read/ 
Write

39   DIAG 

This alarm is used to inform if a software error has 
occurred 

 

 

 

 

39 

DIAG.ENABLE 

Enables or disables the diagnostic alarm 

U8 

(0) Disabled 
(1) Enabled

(1) Enabled 

Read/ 
Write

39 2 DIAG.TYPE 

A non latching alarm type will clear the alarm if the 
problem is solved.

U8 

(0) Non-latched 
(1) Latched

(1)Latched 

Read/ 
Write

40 

 

DB_INIT 

This alarm is reserved for future use

 

40 

DB_INIT.ENABLE 

This alarm is reserved for future use 

U8 

(0) Disabled 
(1) Enabled

(1) Enabled 

Read/ 
Write

40 

DB_INIT.TYPE 

This alarm is reserved for future use 

U8 

(0) Non-latched 
(1) Latched

(1)Latched 

Read/ 
Write

41 

 

POWER 

This alarm is reserved for future use

 

41 

POWER.ENABLE 

This alarm is reserved for future use 

U8 

(0) Disabled 
(1) Enabled

(1) Enabled 

Read/ 
Write

41 

POWER.TYPE 

This alarm is reserved for future use 

U8 

(0) Non-latched 
(1) Latched

(1)Latched 

Read/ 
Write

42 

 

BROOKS_SERIAL_NUMBER 

The serial number assigned to the device 

Visible 
String

ASCII 
Max 32 chars 

Calibrated 
value

Read/ 
Write

43 

 

CURRENT_ALARM_STATUS 

Bitwise representation of the alarms. 

U32 

(0) No Alarm 
(1) Diag_Alarm 
(2) Reserved 
(4) Reserved 
(8) Flow_High_Alarm 
(16) Flow_Low_Alarm 
(32) Pulse_Config_Alarm 
(64)Pulse_Overrun_Alarm 

0 Read 

44   ACTIVE_DIAG_STATUS 

Bitwise representation of the cause of the diagnostic 
alarm 

U32 

(0) Good 
(1) Ram fail 
(2) Flash fail 
(4) Database fail 
(8) Float position fail 
(16) Calibration fail 

0 Read 

45   RESET_ALARM 

Function to reset the alarms which are shown active in 
current alarm status

U8 

(0) Idle 
(1) Reset

(0) Idle 

Read/ 
Write

46   PULSE_OUTPUT 

Settings to set the pulse output on the transmitter

Table continued on next page.

Summary of Contents for MT3809G Metal Tube

Page 1: ...anual X DPT FF MT3809G Alarms eng Part Number 541B218AAG December 2017 Model MT3809G FOUNDATIONTM Fieldbus Supplemental Manual for Brooks Model MT3809G Metal Tube Variable Area Flowmeter with Foundati...

Page 2: ...licable local and national codes Connect all products to the proper electrical and pressure sources Operation 1 Slowly initiate flow into the system Open process valves slowly to avoid flow surges 2 C...

Page 3: ...s fuel cell research and chemicals to medical devices analytical instrumentation semiconductor manufacturing and more The Brooks product you have just received is of the highest quality available offe...

Page 4: ...Installation and Operation Manual X DPT FF MT3809G Alarms eng Part Number 541B218AAG December 2017 Model MT3809G FOUNDATIONTM Fieldbus THIS PAGE WAS INTENTIONALLY LEFT BLANK...

Page 5: ...NDATION Fieldbus Data 3 1 Section 4 Getting Started 4 1 Getting Started 4 1 Section 5 Transducer Blocks 5 Transducer Blocks 5 1 5 1 Overview 5 1 5 2 Analog Input Transducer Block 5 1 Section 6 FOUNDAT...

Page 6: ...ii Contents Installation and Operation Manual X DPT FF MT3809G Alarms eng Part Number 541B218AAG December 2017 Model MT3809G FOUNDATIONTM Fieldbus THIS PAGE WAS INTENTIONALLY LEFT BLANK...

Page 7: ...ovide an overview of FOUNDATION Fieldbus software interface for Brooks Instrument Variable Area Flowmeters model MT3809G with FOUNDATION Fieldbus transmitter This document describes the function and t...

Page 8: ...1 2 Section 1 Introduction Installation and Operation Manual X DPT FF MT3809G Alarms eng Part Number 541B218AAG December 2017 Model MT3809G FOUNDATIONTM Fieldbus THIS PAGE WAS INTENTIONALLY LEFT BLANK...

Page 9: ...arms eng Part Number 541B218AAG December 2017 Model MT3809G FOUNDATIONTM Fieldbus 2 1 Installation Carefully read and follow the instructions for installation and operation given in the Metal Tube Var...

Page 10: ...2 2 Section 2 Installation Installation and Operation Manual X DPT FF MT3809G Alarms eng Part Number 541B218AAG December 2017 Model MT3809G FOUNDATIONTM Fieldbus THIS PAGE WAS INTENTIONALLY LEFT BLANK...

Page 11: ...e Revision 041 Physical layer H1 Quiescent Current Draw mA 12 mA Data Blocks 1x Analog Input Function Block 1 AI 1x Integrator Function Block 1 IT 1x Analog Input Transducer Block 1 AITB 1x Resource B...

Page 12: ...ction 3 FOUNDATION Fieldbus Data Installation and Operation Manual X DPT FF MT3809G Alarms eng Part Number 541B218AAG December 2017 Model MT3809G FOUNDATIONTM Fieldbus THIS PAGE WAS INTENTIONALLY LEFT...

Page 13: ...primary value of the analog transducer block The primary value is the default and used output for the flow value To configure the output of the analog input such that the actual calculated flow is dir...

Page 14: ...2 Section 4 Getting Started Installation and Operation Manual X DPT FF MT3809G Alarms eng Part Number 541B218AAG December 2017 Model MT3809G FOUNDATIONTM Fieldbus THIS PAGE WAS INTENTIONALLY LEFT BLAN...

Page 15: ...sducer block is specifically defined for the Brooks Instrument VA Flowmeter A detailed decription of the block follows in the next section 5 2 Analog Input Transducer Block The following table lists a...

Page 16: ...65535 Other Read 11 XD_ERROR Transducer error code U8 Unspecified error General error 0 No error 0 Read 12 COLLECTION_ DIRECTORY A directory that specifies the number of the data collections in each...

Page 17: ...e the alarm if the flow value rises above this value Float 90 0 Read Write 36 4 HIGH_FLOW ALARM_LIMIT_DELAY The time a flow needs to be above the setting before the alarm is triggered U8 0 to 255 0 Re...

Page 18: ...t Calibrated Value Read Write 49 9 INFO_METER FLANG_MATL U8 Calibrated Value Read Write 49 10 INFO_METER FLANGE_TYPE U8 Calibrated Value Read Write 49 11 INFO_METER FLOAT_MATL U8 Calibrated Value Read...

Page 19: ...TEST_PULSE_FREQUENCY Frequency which is used to test the pulse output Float 0 00 to 100 0 0 Read Write 56 5 TEST TEST_PULSES_COUN T Number of pulses before the test sequence is stopped U32 1 to 100 0...

Page 20: ...Section 5 Transducer Blocks Installation and Operation Manual X DPT FF MT3809G Alarms eng Part Number 541B218AAG December 2017 Model MT3809G FOUNDATIONTM Fieldbus THIS PAGE WAS INTENTIONALLY LEFT BLA...

Page 21: ...6 1 shows how to make a fieldbus network from a wire pair A terminator is added at the FFI end of the wire pair Another terminator is added at the field device end of the wire pair The FFI may have a...

Page 22: ...the FFI is further from the group of field devices in cable length than they are from each other This rull on location of terminators is one that can be bent In Figure 6 2 for example we haven t both...

Page 23: ...in a network beyond the limit of 32 on one segment Using repeaters the maximum number of devices in a network could be increased to 240 Shielding screening A fieldbus network can bu built using only u...

Page 24: ...ng like that of Figure 6 6 Another spur near the FFI has been created to add the power supply Of course we could have put it toward the field end of the trunk We can t use just any off the shelf power...

Page 25: ...onfiguration tool In general other types of FF interfaces will be operated in industrial processes showing a different screen lay out compared to the screens shown in this example Step 2 Load device d...

Page 26: ...Operation Manual X DPT FF MT3809G Alarms eng Part Number 541B218AAG December 2017 Model MT3809G FOUNDATIONTM Fieldbus Step 3 Assign appropriate PD Tag and Node ID as desired Default Assignment Assign...

Page 27: ...UNDATION Fieldbus Guidelines Installation and Operation Manual X DPT FF MT3809G Alarms eng Part Number 541B218AAG December 2017 Model MT3809G FOUNDATIONTM Fieldbus Step 4 Create New Project for Networ...

Page 28: ...art Number 541B218AAG December 2017 Model MT3809G FOUNDATIONTM Fieldbus Step 5 Add FG 110 Linking Device and MT3809G device to Network Configuration Step 6 In Network Configuration configure HSE devic...

Page 29: ...stallation and Operation Manual X DPT FF MT3809G Alarms eng Part Number 541B218AAG December 2017 Model MT3809G FOUNDATIONTM Fieldbus Default settings of MT3809G H1 device Step 7 Configure MT3809G devi...

Page 30: ...Operation Manual X DPT FF MT3809G Alarms eng Part Number 541B218AAG December 2017 Model MT3809G FOUNDATIONTM Fieldbus Step 8 To operate the AI function block a link must be created between AI block an...

Page 31: ...elines Installation and Operation Manual X DPT FF MT3809G Alarms eng Part Number 541B218AAG December 2017 Model MT3809G FOUNDATIONTM Fieldbus Step 9 Add AI block to Source Functionblock s List and add...

Page 32: ...ON Fieldbus Guidelines Installation and Operation Manual X DPT FF MT3809G Alarms eng Part Number 541B218AAG December 2017 Model MT3809G FOUNDATIONTM Fieldbus Step 10 Add AI output to Source pin s and...

Page 33: ...ion and Operation Manual X DPT FF MT3809G Alarms eng Part Number 541B218AAG December 2017 Model MT3809G FOUNDATIONTM Fieldbus Step 11 Click connect icon button choose Project Save choose Download Down...

Page 34: ...es Installation and Operation Manual X DPT FF MT3809G Alarms eng Part Number 541B218AAG December 2017 Model MT3809G FOUNDATIONTM Fieldbus Step 12 To operate AI function block go to AI block in Network...

Page 35: ...and Operation Manual X DPT FF MT3809G Alarms eng Part Number 541B218AAG December 2017 Model MT3809G FOUNDATIONTM Fieldbus Step 13 First set MODE_BLK TARGET to OOS out of service to be able to set desi...

Page 36: ...s Guidelines Installation and Operation Manual X DPT FF MT3809G Alarms eng Part Number 541B218AAG December 2017 Model MT3809G FOUNDATIONTM Fieldbus Step 14 Write desired OUT_SCALE UOM and OUT_SCALE va...

Page 37: ...us Guidelines Installation and Operation Manual X DPT FF MT3809G Alarms eng Part Number 541B218AAG December 2017 Model MT3809G FOUNDATIONTM Fieldbus Step 15 After writing desired OUT_SCALE settings se...

Page 38: ...n and Operation Manual X DPT FF MT3809G Alarms eng Part Number 541B218AAG December 2017 Model MT3809G FOUNDATIONTM Fieldbus Step 16 OUT VALUE and PV VALUE are now indicated as per 200 m3 h FS In the e...

Page 39: ...541B218AAG December 2017 Model MT3809G FOUNDATIONTM Fieldbus Step 17 Alarm settings in AI function block For this example only HI_FLOW and HI_HI_FLOW alarms are set Alarm limit example values 100 and...

Page 40: ...FOUNDATION Fieldbus Guidelines Installation and Operation Manual X DPT FF MT3809G Alarms eng Part Number 541B218AAG December 2017 Model MT3809G FOUNDATIONTM Fieldbus Step 18 When OUT VALUE 100 Hi Alar...

Page 41: ...ON Fieldbus Guidelines Installation and Operation Manual X DPT FF MT3809G Alarms eng Part Number 541B218AAG December 2017 Model MT3809G FOUNDATIONTM Fieldbus Step 19 When OUT VALUE 150 Hi Hi Alarm and...

Page 42: ...ON Fieldbus Guidelines Installation and Operation Manual X DPT FF MT3809G Alarms eng Part Number 541B218AAG December 2017 Model MT3809G FOUNDATIONTM Fieldbus Step 20 When OUT VALUE 100 Current Alarm i...

Page 43: ...eldbus Guidelines Installation and Operation Manual X DPT FF MT3809G Alarms eng Part Number 541B218AAG December 2017 Model MT3809G FOUNDATIONTM Fieldbus Step 21 To reset unacknowledged alarms acknowle...

Page 44: ...6 FOUNDATION Fieldbus Guidelines Installation and Operation Manual X DPT FF MT3809G Alarms eng Part Number 541B218AAG December 2017 Model MT3809G FOUNDATIONTM Fieldbus Step 22 Unacknowledged alarms ha...

Page 45: ...rms eng Part Number 541B218AAG December 2017 Model MT3809G FOUNDATIONTM Fieldbus Step 23 Setting transmitter s physical alarm output contacts Go to AI transducer block and set Hi Flow and Lo Flow limi...

Page 46: ...and Operation Manual X DPT FF MT3809G Alarms eng Part Number 541B218AAG December 2017 Model MT3809G FOUNDATIONTM Fieldbus Step 24 Observing flow alarm conditions PV value 10 Lo Flow Alarm Transmitter...

Page 47: ...elines Installation and Operation Manual X DPT FF MT3809G Alarms eng Part Number 541B218AAG December 2017 Model MT3809G FOUNDATIONTM Fieldbus PV value 90 Hi Flow Alarm Transmitter Contact Output A clo...

Page 48: ...nual X DPT FF MT3809G Alarms eng Part Number 541B218AAG December 2017 Model MT3809G FOUNDATIONTM Fieldbus 90 PV value 10 No Flow Alarm Transmitter Contact Output A and B both open Alarm Status AI tran...

Page 49: ...25 Switch alarm output contacts to latching type Note The latching mode of the flow alarms is only reflecting to the alarm output contacts and NOT to the Alarm Status in the AI transducer block Once P...

Page 50: ...s Installation and Operation Manual X DPT FF MT3809G Alarms eng Part Number 541B218AAG December 2017 Model MT3809G FOUNDATIONTM Fieldbus Step 26 Alarm output contacts reset After Alarm Reset alarm out...

Page 51: ...G Alarms eng Part Number 541B218AAG December 2017 Model MT3809G FOUNDATIONTM Fieldbus Step 27 Alarm output contacts disabling To discontinue alarm output contacts operation set Hi Flow Alarm and Lo Fl...

Page 52: ...ration and is certified by our local Weights and Measures Authorities and traceable to the relevant International Standards Visit www BrooksInstrument com to locate the service location nearest to you...

Reviews: