5-2

Section 5 Transducer Blocks

Installation and Operation Manual

X-DPT-FF-MT3809G-Alarms-eng

Part Number: 541B218AAG

December, 2017

Model MT3809G F

OUNDATION

TM 

Fieldbus

Index

 

Sub Index

 

Parameter Name 

Description 

Data Type

 

Valid Values 

Initialized 

Value 

Read only or

 

Read/W

rite

 

Table 5-1

 Parameters of the Analog Input Transducer Block (continued)

5 4 

MODE_BLK.NORMAL 

Setting for which mode should be used when operated 
with normal conditions 

Bit String 

x

 None 

x

 OOS 

x

Auto

Auto 

Read/ 
Write 

 

BLOCK_ERR 

Error status of this block 

Bit String 

x

 None 

x

Out of Service  

None Read 

 

UPDATE_EVT 

On a change in the static data this alert is generated 

 

 

 

 

7 1 

UPDATE_EVT. 
UNACKNOWLEDGED 

Interface to acknowledge this update alert 

U8 

(0) Uninitialized 
(1) Acknowledged 
(2) Unacknowledged 

(0) Uninitialized 

Read/ 
Write 

7 2 

UPDATE_EVT. 
UPDATE_STATE 

Indication if the alert has been reported 

U8 

(0) Uninitialized 
(1) Reported 
(2) Not Reported 

(0)  Uninitialized 

Read 

7 3 

UPDATE_EVT. 
TIMESTAMP 

The time stamp when the alert is generated 

TM 

MM/DD/YY HH:MM:SS 

Read 

7 4 

UPDATE_EVT. 
STATIC_REVISION 

The static revision when the alert was generated.  

U16 

0 to 65535 

Read 

7 5 

UPDATE_EVT. 
RELATIVE_INDEX

The index of the static parameter whose causes this 
alert to be generated

U16 0 

to 

65535 

Read 

8  BLOCK_ALARM 

The block alarm can generate an alarm if a block error 
occurs

 

 

 

 

8 1 

BLOCK_ALARM. 
UNACKNOWLEDGED 

Interface to acknowledge this block alarm 

U8 

(0) Uninitialized 
(1) Acknowledged 
(2) Unacknowledged 

(0) Uninitialized 

Read/ 
Write 

8 2 

BLOCK_ALARM. 
ALARM_STATE 

Indication if alarm is active or cleared and reported 

U8 

Uninitialized  
Clear-Reported 
Clear-Not Reported 
Active-Reported 
Active-Not Reported 

Uninitialized Read 

8 3 

BLOCK_ALARM. 
TIMESTAMP 

The time stamp when the alarm is generated 

TM 

MM/DD/YY HH:MM:SS 

Read 

8 4 

BLOCK_ALARM. 
SUBCODE 

The sub code which causes the block alarm 

U8 

Other 
OutOfService 

Other Read 

BLOCK_ALARM.VALUE 

The value of the parameter associated with this alarm

U8

0 to 255

Read

9

TRANSDUCER_ 
DIRECTORY 

A directory that specifies the number of the data 
collections in the transducer block

U16 0 

Read 

10  

TRANSDUCER_ 
TYPE 

Identifies the transducer error that follows 

U16 

Other (65535) 

Other 

Read 

11 

 

XD_ERROR 

Transducer error code 

U8 

Unspecified error 
General error 
(0) No error

0 Read 

12  

COLLECTION_ 
DIRECTORY 

A directory that specifies the number of the data 
collections in each transducer within a transducer block

U8 0 

Read 

13 

 

PRIMARY_VALUE 

The measure flow value and status.

 

13 1 

PRIMARY_VALUE. 
STATUS 

The status of the primary value 

U8 

Bad 
Good_NonCascade 

Good Non 
Cascade

Read 

13 2 

PRIMARY_VALUE. 
VALUE 

The value of the primary value 

Float 

 

0.0 

Read 

14   FLOW_RATE_UOM 

Units of measurement of the flow rate given in the 
primary value 

U16 Supported 

UOMs 

Calibrated 
value

Read/ 
Write

15   SW_REV 

Software 

version of the application 

Visible 
String 

x.x.x where the x 
represents  the version 

 Read 

16 

 

HW_REV 

Hardware revision of the transmitter 

Visible 
String

x.x.x where the x 
represents  the version 

 Read 

17 

 

BROOKS_PASSWORD 

Password protection for manufacture settings 

Visible 
string

Brooks password 

*************** 

Read/ 
Write 

18   MESSAGE 

Extra message field for indicating the transmitter. This 
value is not processed

Visible 
String

ASCII 
Max 24 chars 

Blank 

Read/ 
Write

19   TAG_NAME 

Extra tag name for the device. This value is not 
processed 

Visible 
String

ASCII 
Max 16 chars 

Calibrated 
value

Read/ 
Write

20   DESCRIPTOR 

Extra descriptor field for the device. This value is not 
processed 

Visible 
String 

ASCII 
Max 17 chars 

Blank 

Read/ 
Write 

21 

 

DEV_DATE 

Date of calibration 

Visible 
String

DD/MM/YY 

Calibrated 
value

Read/ 
Write

22 

 

AO_FILTER 

The analog filter values used for the flow calculation 

Float 

0.00 to 10.00 

Calibrated 
value

Read/ 
Write

23 

 

FIN_ASSY_NUM 

Final assembly number 

U32 

0 to 4294967296 

Calibrated 
value

Read/ 
Write

24 

0..
9

CALIB_POSITION 

10 position array with calibrated float positions.  

Float 

 

Calibrated 
values

Read/ 
Write

25 

0..
9

CALIB_FLOW_RATE 

10 position array with calibrated flow rates according to 
the scale 

Float  

Calibrated 
values

Read/ 
Write

26   LFCUTOFF 

Low flow cut off value. Every value below this flow will be 
cut off to zero 

Float 0.00 

to 

99999.9 

Read/ 
Write

27   DENSITY 

Density uom and value used for the calculation

 

27 

DENSITY.UOM 

 

U16 

Reserved, do not use 

Read/ 
Write

27 

DENSITY.VALUE 

 

Float 

Reserved, do not use 

1.0 

Read/ 
Write

28 

 

PRESSURE 

Pressure uom and value used for the calculation

 

28 

PRESSURE.UOM 

 

U16 

Reserved, do not use 

Read/ 
Write

28 

PRESSURE.VALUE 

 

Float 

Reserved. Do not use 

0.0 

Read/ 
Write

Table continued on next page.

Summary of Contents for MT3809G Metal Tube

Page 1: ...anual X DPT FF MT3809G Alarms eng Part Number 541B218AAG December 2017 Model MT3809G FOUNDATIONTM Fieldbus Supplemental Manual for Brooks Model MT3809G Metal Tube Variable Area Flowmeter with Foundati...

Page 2: ...licable local and national codes Connect all products to the proper electrical and pressure sources Operation 1 Slowly initiate flow into the system Open process valves slowly to avoid flow surges 2 C...

Page 3: ...s fuel cell research and chemicals to medical devices analytical instrumentation semiconductor manufacturing and more The Brooks product you have just received is of the highest quality available offe...

Page 4: ...Installation and Operation Manual X DPT FF MT3809G Alarms eng Part Number 541B218AAG December 2017 Model MT3809G FOUNDATIONTM Fieldbus THIS PAGE WAS INTENTIONALLY LEFT BLANK...

Page 5: ...NDATION Fieldbus Data 3 1 Section 4 Getting Started 4 1 Getting Started 4 1 Section 5 Transducer Blocks 5 Transducer Blocks 5 1 5 1 Overview 5 1 5 2 Analog Input Transducer Block 5 1 Section 6 FOUNDAT...

Page 6: ...ii Contents Installation and Operation Manual X DPT FF MT3809G Alarms eng Part Number 541B218AAG December 2017 Model MT3809G FOUNDATIONTM Fieldbus THIS PAGE WAS INTENTIONALLY LEFT BLANK...

Page 7: ...ovide an overview of FOUNDATION Fieldbus software interface for Brooks Instrument Variable Area Flowmeters model MT3809G with FOUNDATION Fieldbus transmitter This document describes the function and t...

Page 8: ...1 2 Section 1 Introduction Installation and Operation Manual X DPT FF MT3809G Alarms eng Part Number 541B218AAG December 2017 Model MT3809G FOUNDATIONTM Fieldbus THIS PAGE WAS INTENTIONALLY LEFT BLANK...

Page 9: ...arms eng Part Number 541B218AAG December 2017 Model MT3809G FOUNDATIONTM Fieldbus 2 1 Installation Carefully read and follow the instructions for installation and operation given in the Metal Tube Var...

Page 10: ...2 2 Section 2 Installation Installation and Operation Manual X DPT FF MT3809G Alarms eng Part Number 541B218AAG December 2017 Model MT3809G FOUNDATIONTM Fieldbus THIS PAGE WAS INTENTIONALLY LEFT BLANK...

Page 11: ...e Revision 041 Physical layer H1 Quiescent Current Draw mA 12 mA Data Blocks 1x Analog Input Function Block 1 AI 1x Integrator Function Block 1 IT 1x Analog Input Transducer Block 1 AITB 1x Resource B...

Page 12: ...ction 3 FOUNDATION Fieldbus Data Installation and Operation Manual X DPT FF MT3809G Alarms eng Part Number 541B218AAG December 2017 Model MT3809G FOUNDATIONTM Fieldbus THIS PAGE WAS INTENTIONALLY LEFT...

Page 13: ...primary value of the analog transducer block The primary value is the default and used output for the flow value To configure the output of the analog input such that the actual calculated flow is dir...

Page 14: ...2 Section 4 Getting Started Installation and Operation Manual X DPT FF MT3809G Alarms eng Part Number 541B218AAG December 2017 Model MT3809G FOUNDATIONTM Fieldbus THIS PAGE WAS INTENTIONALLY LEFT BLAN...

Page 15: ...sducer block is specifically defined for the Brooks Instrument VA Flowmeter A detailed decription of the block follows in the next section 5 2 Analog Input Transducer Block The following table lists a...

Page 16: ...65535 Other Read 11 XD_ERROR Transducer error code U8 Unspecified error General error 0 No error 0 Read 12 COLLECTION_ DIRECTORY A directory that specifies the number of the data collections in each...

Page 17: ...e the alarm if the flow value rises above this value Float 90 0 Read Write 36 4 HIGH_FLOW ALARM_LIMIT_DELAY The time a flow needs to be above the setting before the alarm is triggered U8 0 to 255 0 Re...

Page 18: ...t Calibrated Value Read Write 49 9 INFO_METER FLANG_MATL U8 Calibrated Value Read Write 49 10 INFO_METER FLANGE_TYPE U8 Calibrated Value Read Write 49 11 INFO_METER FLOAT_MATL U8 Calibrated Value Read...

Page 19: ...TEST_PULSE_FREQUENCY Frequency which is used to test the pulse output Float 0 00 to 100 0 0 Read Write 56 5 TEST TEST_PULSES_COUN T Number of pulses before the test sequence is stopped U32 1 to 100 0...

Page 20: ...Section 5 Transducer Blocks Installation and Operation Manual X DPT FF MT3809G Alarms eng Part Number 541B218AAG December 2017 Model MT3809G FOUNDATIONTM Fieldbus THIS PAGE WAS INTENTIONALLY LEFT BLA...

Page 21: ...6 1 shows how to make a fieldbus network from a wire pair A terminator is added at the FFI end of the wire pair Another terminator is added at the field device end of the wire pair The FFI may have a...

Page 22: ...the FFI is further from the group of field devices in cable length than they are from each other This rull on location of terminators is one that can be bent In Figure 6 2 for example we haven t both...

Page 23: ...in a network beyond the limit of 32 on one segment Using repeaters the maximum number of devices in a network could be increased to 240 Shielding screening A fieldbus network can bu built using only u...

Page 24: ...ng like that of Figure 6 6 Another spur near the FFI has been created to add the power supply Of course we could have put it toward the field end of the trunk We can t use just any off the shelf power...

Page 25: ...onfiguration tool In general other types of FF interfaces will be operated in industrial processes showing a different screen lay out compared to the screens shown in this example Step 2 Load device d...

Page 26: ...Operation Manual X DPT FF MT3809G Alarms eng Part Number 541B218AAG December 2017 Model MT3809G FOUNDATIONTM Fieldbus Step 3 Assign appropriate PD Tag and Node ID as desired Default Assignment Assign...

Page 27: ...UNDATION Fieldbus Guidelines Installation and Operation Manual X DPT FF MT3809G Alarms eng Part Number 541B218AAG December 2017 Model MT3809G FOUNDATIONTM Fieldbus Step 4 Create New Project for Networ...

Page 28: ...art Number 541B218AAG December 2017 Model MT3809G FOUNDATIONTM Fieldbus Step 5 Add FG 110 Linking Device and MT3809G device to Network Configuration Step 6 In Network Configuration configure HSE devic...

Page 29: ...stallation and Operation Manual X DPT FF MT3809G Alarms eng Part Number 541B218AAG December 2017 Model MT3809G FOUNDATIONTM Fieldbus Default settings of MT3809G H1 device Step 7 Configure MT3809G devi...

Page 30: ...Operation Manual X DPT FF MT3809G Alarms eng Part Number 541B218AAG December 2017 Model MT3809G FOUNDATIONTM Fieldbus Step 8 To operate the AI function block a link must be created between AI block an...

Page 31: ...elines Installation and Operation Manual X DPT FF MT3809G Alarms eng Part Number 541B218AAG December 2017 Model MT3809G FOUNDATIONTM Fieldbus Step 9 Add AI block to Source Functionblock s List and add...

Page 32: ...ON Fieldbus Guidelines Installation and Operation Manual X DPT FF MT3809G Alarms eng Part Number 541B218AAG December 2017 Model MT3809G FOUNDATIONTM Fieldbus Step 10 Add AI output to Source pin s and...

Page 33: ...ion and Operation Manual X DPT FF MT3809G Alarms eng Part Number 541B218AAG December 2017 Model MT3809G FOUNDATIONTM Fieldbus Step 11 Click connect icon button choose Project Save choose Download Down...

Page 34: ...es Installation and Operation Manual X DPT FF MT3809G Alarms eng Part Number 541B218AAG December 2017 Model MT3809G FOUNDATIONTM Fieldbus Step 12 To operate AI function block go to AI block in Network...

Page 35: ...and Operation Manual X DPT FF MT3809G Alarms eng Part Number 541B218AAG December 2017 Model MT3809G FOUNDATIONTM Fieldbus Step 13 First set MODE_BLK TARGET to OOS out of service to be able to set desi...

Page 36: ...s Guidelines Installation and Operation Manual X DPT FF MT3809G Alarms eng Part Number 541B218AAG December 2017 Model MT3809G FOUNDATIONTM Fieldbus Step 14 Write desired OUT_SCALE UOM and OUT_SCALE va...

Page 37: ...us Guidelines Installation and Operation Manual X DPT FF MT3809G Alarms eng Part Number 541B218AAG December 2017 Model MT3809G FOUNDATIONTM Fieldbus Step 15 After writing desired OUT_SCALE settings se...

Page 38: ...n and Operation Manual X DPT FF MT3809G Alarms eng Part Number 541B218AAG December 2017 Model MT3809G FOUNDATIONTM Fieldbus Step 16 OUT VALUE and PV VALUE are now indicated as per 200 m3 h FS In the e...

Page 39: ...541B218AAG December 2017 Model MT3809G FOUNDATIONTM Fieldbus Step 17 Alarm settings in AI function block For this example only HI_FLOW and HI_HI_FLOW alarms are set Alarm limit example values 100 and...

Page 40: ...FOUNDATION Fieldbus Guidelines Installation and Operation Manual X DPT FF MT3809G Alarms eng Part Number 541B218AAG December 2017 Model MT3809G FOUNDATIONTM Fieldbus Step 18 When OUT VALUE 100 Hi Alar...

Page 41: ...ON Fieldbus Guidelines Installation and Operation Manual X DPT FF MT3809G Alarms eng Part Number 541B218AAG December 2017 Model MT3809G FOUNDATIONTM Fieldbus Step 19 When OUT VALUE 150 Hi Hi Alarm and...

Page 42: ...ON Fieldbus Guidelines Installation and Operation Manual X DPT FF MT3809G Alarms eng Part Number 541B218AAG December 2017 Model MT3809G FOUNDATIONTM Fieldbus Step 20 When OUT VALUE 100 Current Alarm i...

Page 43: ...eldbus Guidelines Installation and Operation Manual X DPT FF MT3809G Alarms eng Part Number 541B218AAG December 2017 Model MT3809G FOUNDATIONTM Fieldbus Step 21 To reset unacknowledged alarms acknowle...

Page 44: ...6 FOUNDATION Fieldbus Guidelines Installation and Operation Manual X DPT FF MT3809G Alarms eng Part Number 541B218AAG December 2017 Model MT3809G FOUNDATIONTM Fieldbus Step 22 Unacknowledged alarms ha...

Page 45: ...rms eng Part Number 541B218AAG December 2017 Model MT3809G FOUNDATIONTM Fieldbus Step 23 Setting transmitter s physical alarm output contacts Go to AI transducer block and set Hi Flow and Lo Flow limi...

Page 46: ...and Operation Manual X DPT FF MT3809G Alarms eng Part Number 541B218AAG December 2017 Model MT3809G FOUNDATIONTM Fieldbus Step 24 Observing flow alarm conditions PV value 10 Lo Flow Alarm Transmitter...

Page 47: ...elines Installation and Operation Manual X DPT FF MT3809G Alarms eng Part Number 541B218AAG December 2017 Model MT3809G FOUNDATIONTM Fieldbus PV value 90 Hi Flow Alarm Transmitter Contact Output A clo...

Page 48: ...nual X DPT FF MT3809G Alarms eng Part Number 541B218AAG December 2017 Model MT3809G FOUNDATIONTM Fieldbus 90 PV value 10 No Flow Alarm Transmitter Contact Output A and B both open Alarm Status AI tran...

Page 49: ...25 Switch alarm output contacts to latching type Note The latching mode of the flow alarms is only reflecting to the alarm output contacts and NOT to the Alarm Status in the AI transducer block Once P...

Page 50: ...s Installation and Operation Manual X DPT FF MT3809G Alarms eng Part Number 541B218AAG December 2017 Model MT3809G FOUNDATIONTM Fieldbus Step 26 Alarm output contacts reset After Alarm Reset alarm out...