5-2
Section 5 Transducer Blocks
Installation and Operation Manual
X-DPT-FF-MT3809G-Alarms-eng
Part Number: 541B218AAG
December, 2017
Model MT3809G F
OUNDATION
TM
Fieldbus
Index
Sub Index
Parameter Name
Description
Data Type
Valid Values
Initialized
Value
Read only or
Read/W
rite
Table 5-1
Parameters of the Analog Input Transducer Block (continued)
5 4
MODE_BLK.NORMAL
Setting for which mode should be used when operated
with normal conditions
Bit String
x
None
x
OOS
x
Auto
Auto
Read/
Write
6
BLOCK_ERR
Error status of this block
Bit String
x
None
x
Out of Service
None Read
7
UPDATE_EVT
On a change in the static data this alert is generated
7 1
UPDATE_EVT.
UNACKNOWLEDGED
Interface to acknowledge this update alert
U8
(0) Uninitialized
(1) Acknowledged
(2) Unacknowledged
(0) Uninitialized
Read/
Write
7 2
UPDATE_EVT.
UPDATE_STATE
Indication if the alert has been reported
U8
(0) Uninitialized
(1) Reported
(2) Not Reported
(0) Uninitialized
Read
7 3
UPDATE_EVT.
TIMESTAMP
The time stamp when the alert is generated
TM
MM/DD/YY HH:MM:SS
0
Read
7 4
UPDATE_EVT.
STATIC_REVISION
The static revision when the alert was generated.
U16
0 to 65535
0
Read
7 5
UPDATE_EVT.
RELATIVE_INDEX
The index of the static parameter whose causes this
alert to be generated
U16 0
to
65535
0
Read
8 BLOCK_ALARM
The block alarm can generate an alarm if a block error
occurs
8 1
BLOCK_ALARM.
UNACKNOWLEDGED
Interface to acknowledge this block alarm
U8
(0) Uninitialized
(1) Acknowledged
(2) Unacknowledged
(0) Uninitialized
Read/
Write
8 2
BLOCK_ALARM.
ALARM_STATE
Indication if alarm is active or cleared and reported
U8
Uninitialized
Clear-Reported
Clear-Not Reported
Active-Reported
Active-Not Reported
Uninitialized Read
8 3
BLOCK_ALARM.
TIMESTAMP
The time stamp when the alarm is generated
TM
MM/DD/YY HH:MM:SS
0
Read
8 4
BLOCK_ALARM.
SUBCODE
The sub code which causes the block alarm
U8
Other
OutOfService
Other Read
8
5
BLOCK_ALARM.VALUE
The value of the parameter associated with this alarm
U8
0 to 255
0
Read
9
TRANSDUCER_
DIRECTORY
A directory that specifies the number of the data
collections in the transducer block
U16 0
0
Read
10
TRANSDUCER_
TYPE
Identifies the transducer error that follows
U16
Other (65535)
Other
Read
11
XD_ERROR
Transducer error code
U8
Unspecified error
General error
(0) No error
0 Read
12
COLLECTION_
DIRECTORY
A directory that specifies the number of the data
collections in each transducer within a transducer block
U8 0
0
Read
13
PRIMARY_VALUE
The measure flow value and status.
13 1
PRIMARY_VALUE.
STATUS
The status of the primary value
U8
Bad
Good_NonCascade
Good Non
Cascade
Read
13 2
PRIMARY_VALUE.
VALUE
The value of the primary value
Float
0.0
Read
14 FLOW_RATE_UOM
Units of measurement of the flow rate given in the
primary value
U16 Supported
UOMs
Calibrated
value
Read/
Write
15 SW_REV
Software
version of the application
Visible
String
x.x.x where the x
represents the version
Read
16
HW_REV
Hardware revision of the transmitter
Visible
String
x.x.x where the x
represents the version
Read
17
BROOKS_PASSWORD
Password protection for manufacture settings
Visible
string
Brooks password
***************
Read/
Write
18 MESSAGE
Extra message field for indicating the transmitter. This
value is not processed
Visible
String
ASCII
Max 24 chars
Blank
Read/
Write
19 TAG_NAME
Extra tag name for the device. This value is not
processed
Visible
String
ASCII
Max 16 chars
Calibrated
value
Read/
Write
20 DESCRIPTOR
Extra descriptor field for the device. This value is not
processed
Visible
String
ASCII
Max 17 chars
Blank
Read/
Write
21
DEV_DATE
Date of calibration
Visible
String
DD/MM/YY
Calibrated
value
Read/
Write
22
AO_FILTER
The analog filter values used for the flow calculation
Float
0.00 to 10.00
Calibrated
value
Read/
Write
23
FIN_ASSY_NUM
Final assembly number
U32
0 to 4294967296
Calibrated
value
Read/
Write
24
0..
9
CALIB_POSITION
10 position array with calibrated float positions.
Float
Calibrated
values
Read/
Write
25
0..
9
CALIB_FLOW_RATE
10 position array with calibrated flow rates according to
the scale
Float
Calibrated
values
Read/
Write
26 LFCUTOFF
Low flow cut off value. Every value below this flow will be
cut off to zero
Float 0.00
to
99999.9
0
Read/
Write
27 DENSITY
Density uom and value used for the calculation
27
1
DENSITY.UOM
U16
Reserved, do not use
0
Read/
Write
27
2
DENSITY.VALUE
Float
Reserved, do not use
1.0
Read/
Write
28
PRESSURE
Pressure uom and value used for the calculation
28
1
PRESSURE.UOM
U16
Reserved, do not use
0
Read/
Write
28
2
PRESSURE.VALUE
Float
Reserved. Do not use
0.0
Read/
Write
Table continued on next page.