Section 1 Introduction
Installation and Operation Manual
X-TMF-5965-5851EM-MFC-eng
Part Number: 541B122AAG
September, 2009
PERFORMANCE CHARACTERISTICS (continued):
Pressure Equipment Directive (PED) 97/23/EC
Working Pressure
1000 psi (70 bar) max.
Mounting Sensitivity
+0.5% maximum full scale deviation after re-zeroing.
ELECTRICAL CHARACTERISTICS:
Power Requirements
Voltage Option: + 15 Vdc +5% Watts power consumption
Current Option: +22.5 to +28 Vdc, 370 mA @ +28 Vdc
Class III Equipment: The dc main input shall be supplied from a SELV
(Separate Extra-Low Voltage) source.
Electrical Connections
Card Edge: 30 micorinch gold over low stress nickel-plated copper
D-Connector: DA-15P
Electrical Pinouts
Card Edge: Compatible with Brooks Model 5965/5851EM as well as most
competitve models
D-Connector: Compatible with Brooks Models 5850C, D and E.
Environmental Conditions
Installation category: "I"
Pollution degree: 2
Humidity: 50 - 80% Relative Humidity
Meter Altitude:2,000 meters (6562 feet)
For Indoor Use ONLY
Mains supply voltage fluctuations not to 10% of nominal voltage
Command Input
Voltage Option: 0-5 Vdc. Input resistance 200 k ohm
Current Option: Input Resistance 75 ohm
Output Signal
Voltage I/O Option: 0-5 Vdc into 2,000 ohms or greater. Max. ripple 3 mV.
Current I/O Option: 0-5 Vdc into 2,000 ohms or greater. Maximum ripple 3
mVP-P jumper selectable 4-20 mAdc or 0-20 mAdc. Refer to Fiugre 2-5 for
maximum loop resistance.
5 Volt Reference Output
5 Volts, ±0.2 (±0.01 Vdc). Maximum load 1 k ohms.