10-6
Instruction and Operation Manual
X-CM-QmBS-eng
Part Number: 541B052AHG
June, 2008
Figure 10-7 Frequency Output Wiring – Terminals 31 & 32 (Channel C) – Internal Power
Figure 10-8 Frequency Output Wiring – Terminals 31 & 32 (Channel C) – External Power
000042
Counter
Output voltage level is +15 VDC ±3%
with high resistance load.
Note: Refer to Figure 10-14 for output voltage
versus load resistance.
+
–
3–30 VDC
Pull-up resistor
Counter
Note: Refer to Figure 10-15 for recommended
resistor versus supply voltage.
000042
–
+
+
–
Excessive current will damage the transmitter.
Do not exceed 30 VDC input. Terminal current must be
less than 500 mA.
CAUTION
QmBS Sensor / QTA Transmitters
Section 10 I/O Wiring DIN CIO Transmitter