Scaling the 4-20 mA Analog Output (
Aout
)
The
Analog Output
menu is used to program the 4-20 mA output based on display values.
The 4-20 mA analog output (if equipped) can be scaled to provide a 4-20 mA signal for any display range
selected for either the rate, total, or grand total. The output may be disabled (
DSABL
), and will only
output the minimum signal.
No equipment is needed to scale the analog output; simply program two display values and
corresponding mA output signals.
!
CAUTION
Please note that when power is removed
from the meter, the analog output will drop
below 1 mA.
Take this effect into consideration when
designing any system using the 4-20 mA
output.