background image

ACS5000 Installation Manual 

Page 6  

 

 

 
© 2017 Brivo Systems LLC. All rights reserved. 

Rev 1 

Pre-Installation Procedures 

 

Before you begin installing the Brivo control panel, perform the following tasks to ensure a safe, speedy, and 
successful installation. 

Understand the function of the Brivo ACS5000 control panel (A/E/S). 

The ACS5000-E, ACS5000-A, and ACS5000-S are four (4) reader control panels with multiple access 
points (up to four readers per chassis). This control panel is considered a standalone system. The 
main board has two (2) readers on-board, and one additional expansion board can be integrated with 
the main board which will form the four (4) reader panel. Additional expansion panels (ACS5000-EXP) 
can connect to the main control panel with two expansion boards in each. Each expansion board can 
be a door board (two (2) readers on board) or an input-output board.  

The Brivo ACS5000-E uses an on-board Ethernet interface to communicate via any TCP/IP networking 
technology that can be connected through a hub, router or switch, including Wi-Fi and satellite 
communications. It is an IP-enabled Access Control System that interacts with the Brivo OnAir cloud 
server via the Brivo OnAir application. 

The Brivo ACS5000-A is identical to the ACS5000-E except that the ACS5000-A communicates to a 
Brivo OnSite Server instead of the Brivo OnAir cloud server. 

The Brivo ACS5000-S is identical to the ACS5000-E except that the ACS5000-S cannot communicate 
through the web. Instead, it is programmed through an on-board interface for data management. 

The ACS5008-E, ACS5008-A, and ACS5008-S are identical to their respective ACS5000 models except 
for a larger enclosure which allows for two additional expansion boards (for a total of up to four door 
boards and/or input-output boards). Also, the ACS5008 series are connected to two (2) 12V, 7Ah 
batteries for standby power (Batteries should be connected in parallel). 

For communications to remote sites or other locations not served by wired bandwidth technologies, 
the Brivo ACS5000-E can be linked to a Brivo Cellular Network Router (CNR). 

Because the ACS5000-E downloads all credential information and operating parameters from the 
Brivo OnAir cloud server, it must be properly installed and configured through the Brivo OnAir cloud 
server before it is fully functional. 

 

WARNING: 

 CHECK YOUR FIRMWARE  

Please contact Brivo Technical Support at 866-274-8648, option 3 or email 

[email protected]

 to confirm that your ACS5000 panel is loaded with 

the latest firmware. If it is not, please follow the instructions provided by Brivo 
Technical Support to upgrade your firmware to the latest version before 
proceeding with the installation. 

 
Understand Brivo ACS5000 product compatibility. 

The ACS5000 control panel is compatible with a large number of standard reader models including 
the following (UL tested for compatibility) reader models: Essex KTP162, Essex KTP163, HID 5355, 
HID 5365, HID 6005, HID 310, AWID KP-6840, and BIOSCRYPT VSmart. Brivo products are designed 
to accommodate the latest updates in Wiegand formats. The ACS5000 control board is compatible 
with Wiegand devices that transmit up to 255-bit data. 

A current list of compatible readers and keypads is maintained on Brivo’s website at 
http://www.brivo.com. If you have a specific model of reader or keypad that is not listed on the Brivo 
website, please contact Technical Support at 1-866-BRIVO-4-U to determine compatibility. 

Summary of Contents for ACS5000

Page 1: ...ACS5000 Panel A E S Installation Manual Rev 1 ENG DOC 003 ...

Page 2: ... The unit will continue to operate standalone if the network connection is interrupted The monitoring software is not UL evaluated Canada Underwriters Laboratories C UL Compliancy For C UL Listed applications the unit shall be installed in accordance with Part 1 of the Canadian Electrical Code Parts and Service The ACS5000 control panel contains no user serviceable parts The lithium battery is not...

Page 3: ...ms LLC All rights reserved Rev 1 Table of Contents INTRODUCTION 4 PRE INSTALLATION PROCEDURES 6 FOR ACS5000 E PANELS USING THE BRIVO CELLULAR NETWORK ROUTER 12 GENERAL ASSEMBLY PROCEDURES 13 POWERING AND TESTING PROCEDURES 18 INSTALLATION PROCEDURES 20 ...

Page 4: ...o contain one expansion board either a DOOR BOARD or an INPUT OUTPUT BOARD if using a standard chassis or three expansion boards in any combination of DOOR BOARDs or INPUT OUTPUT BOARDs if using a large chassis Expansion chassis Additional chassis containing one or two expansion boards either DOOR BOARDs and or INPUT OUTPUT BOARDs Large expansion chassis Additional chassis containing up to four ex...

Page 5: ... Yes 1500 ft Molex Connector N A 22 Yes No 1 ft Earth ground N A 6 Yes Yes 20 to 40 ft Reader Data 1 5504FE 22 Yes Yes 250 ft Reader Data 2 5400FE 20 Yes Yes 300 ft Reader Data 3 6300FE 18 Yes Yes 500 ft Additional Resources The following additional resources are available for the installer as well as the client Networking Admin Interface Guide Reader Keypad Wiring Guide Installation Worksheet Net...

Page 6: ...ve ACS5000 models except for a larger enclosure which allows for two additional expansion boards for a total of up to four door boards and or input output boards Also the ACS5008 series are connected to two 2 12V 7Ah batteries for standby power Batteries should be connected in parallel For communications to remote sites or other locations not served by wired bandwidth technologies the Brivo ACS500...

Page 7: ...ounts make sure the account has been created and the control panel is registered through Brivo OnAir If the control panel has not been registered by the dealer the installer may either contact Brivo Technical Support for assistance or simply register the panel directly 4 Verify that the Master Administrator and any other employee who will be accessing the system have Internet access on a computer ...

Page 8: ...mbly ELC PWR A001 7 If additional expansion chassis have been ordered with the control panel locate and check the contents of each Expansion Chassis Kit B ACS5000 EXP or Large Expansion Chassis Kit B ACS5008 EXP Each standard expansion chassis can hold up to two boards including any combination of door and or Input Output boards Each large expansion chassis can hold up to four boards including any...

Page 9: ...node is to be used for a door do not connect any other device to the following terminal blocks REX DOOR DOOR LOCK RELAY and READER An INPUT OUTPUT BOARD cannot be used to control a door however it can be used in any circumstance that uses contact closure to track change of status 8 You may download and complete the appropriate Installation Worksheets from Brivo s website 9 For ACS5000 E control pa...

Page 10: ...Maximum Distance Calculations c Calculate the distance between each chassis and its associated keypad or reader The ACS5000 does not specify a maximum distance between the chassis and a keypad or reader but the keypad reader manufacturer does Follow manufacturer guidelines for each keypad and reader d Place each chassis within 500 feet of its associated electronic strike or latch ...

Page 11: ...hardware WARNING Heat and Noise DO NOT INSTALL THE CONTROL PANEL IN AN AREA THAT COULD DROP BELOW 32 DEGRESS FAHRENHEIT OR EXCEED 120 DEGREES Doing so can cause damage to components within the control panel DO NOT INSTALL THE CONTROL PANEL NEAR OR ON THE SAME CIRCUIT WITH DEVICES THAT PRODUCE LARGE AMOUNTS OF ELECTRICAL NOISE This includes grinders electric motors and blowers electrical switch gea...

Page 12: ...ructions on the configuration of the Brivo CNR with the ACS5000 E panel WARNING Cable Connectors THE CONNECTORS ON THE INTERNAL ANTENNA CABLE ARE VERY FRAGILE Be very careful when plugging in the equipment WARNING Attach antenna before powering the Brivo CNR NEVER POWER UP A BRIVO CNR BEFORE CONNECTING THE ANTENNA WARNING FCC RF Exposure NO ONE SHOULD BE WITHIN 20cm 8 inches OF THE ANTENNA WHEN IT...

Page 13: ...em out using a screwdriver 5 Assemble the chassis a Install the power supply board in each chassis first If you install the MAIN BOARD or a Door or INPUT OUTPUT BOARD first you may find it difficult to position your screwdriver in a way that will allow you to install the power supply board later b Install the MAIN BOARD in the control chassis Install each board by aligning it with the previously i...

Page 14: ...ol chassis connect that to the power supply board Figure 2 Connect Expansion Board to Power Supply 3 If there are expansion chassis connect each DOOR BOARD and INPUT OUTPUT BOARD to the power supply board in each chassis a Use the power cable that came with each circuit board kit b The Power connector uses a PC style 4 wire molded Molex connector to deliver 12V Ground AC Power Detection and Earth ...

Page 15: ... using the bolt and washer included with your packaging 2 Connect the white and green wires from the AC power indicated LED to the 16 5 VAC terminals of the power supply board Connect the tamper switch to the MAIN BOARD and to one board in each expansion chassis 1 Connect the tamper switch to the MAIN BOARD in the control chassis Figure 3 Connect Tamper Switch to MAIN BOARD a The tamper header con...

Page 16: ...terminals may cause damage to the control panel 1 Connect the battery wires ELC BAT W001 that come with each circuit board kit to the power supply BATTERY INPUT terminal block a Connect the black wire to the ground GND terminal b Connect the red wire to the 12V terminal Figure 5 Connect Battery Leads to Power Supply Wire the AC transformer to the power supply WARNING Transform Connection DO NOT CO...

Page 17: ...LLC All rights reserved Rev 1 1 Use 18 AWG wire minimum grade to connect the screw terminals on the transformer to the 16 5 VAC POWER INPUT terminal block on the power supply board using terminals AC1 and AC2 Figure 6 Connect AC Transformer to Power Supply ...

Page 18: ...ors a Check the power supply board to confirm that the green LED is on and blinking indicating that AC power is being supplied to the board and that the board is producing 12 VDC power b Check the MAIN BOARD to confirm that the LOCAL HRTBT local heartbeat and MAIN HRTBT main heartbeat have come on and are blinking The local heartbeat should begin blinking immediately The main heartbeat can take 30...

Page 19: ...f If any of these power indicators is not correct i e the LED light does not come on or does not begin blinking check the connections from the power supply to each of the circuit boards If all connections are good but there is a still a problem with the power indicator contact Technical Support NOTE A steady light is an indication of a problem just as much as no light is 3 If ALL power indicators ...

Page 20: ...llation Procedures Establish CAN BUS Wiring 1 If there is an expansion board in the control chassis connect it to the MAIN BOARD Figure 9 Connect Expansion Board to MAIN BOARD 2 When dealing with expansion chassis connect the second expansion board to the first one in each expansion chassis ...

Page 21: ...control panel there would be a MAIN BOARD and five expansion boards E1 E2 E3 E4 and E5 Each expansion board could be either a DOOR BOARD or an INPUT OUTPUT BOARD b To daisy chain the boards together See Figure 11 below Wire E5 to E4 in Expansion Chassis 2 Wire E4 in Expansion Chassis 2 to E3 in Expansion Chassis 1 Wire E3 to E2 in Expansion Chassis 1 Wire E2 in Expansion Chassis 1 to E1 in the Con...

Page 22: ...last board s in the daisy chain i e It must be removed from all boards except the endpoint of the daisy chain NOTE The MAIN BOARD does not have to be an endpoint in the control panel the control panel may be in the middle of the chain with expansion boards branching out in either direction 7 On the first board connect the wires of the CAT5 CAT6 cable to the CAN BUS terminal block as follows a Conn...

Page 23: ...p to board numbers when the control panel is configures in the application Ignore the AEN Port WARNING AEN Port DO NOT CONNECT THE AEN PORT FOR ANY REASON This will significantly interfere with the function of the external network If instructed by Technical Support connect a laptop to the MAIN BOARD Figure 13 Connect Laptop to MAIN BOARD 1 Connect a laptop to the ADMIN port on the MAIN BOARD accor...

Page 24: ...e non crossover cable to connect this port to a local hub switch or router that has connectivity to the Internet Connect the Brivo CNR to the MAIN BOARD only if using a cellular connection Figure 15 Connect Brivo CNR to MAIN BOARD 1 Connect the Brivo CNR to the MAIN BOARD via the LAN port and follow the instructions in the Brivo CNR Configuration Guide a The LAN port is a 10 100 Ethernet interface...

Page 25: ...ation including the option to activate the door or other relays fire the door strike and suppress any Door Forced messages b Connect the Normally Closed NC contacts of the Door Sensor to the COM and CONTACT terminals In this context an NC switch is considered closed when the door is closed magnet is present and open when the door is open no magnet is present When the switch is open the control pan...

Page 26: ...O Normally Open and NC Normally Closed contacts WARNING Relay Amp Limit THERE IS A 3 AMP 24 VOLT DC LIMIT ON THROUGH CURRENT FOR ALL RELAYS 5 If used wire the AUX INPUTS terminal block a The IN1 and IN2 terminals are contact closure type inputs that share a COM terminal b The terminals can be used for a variety of purposes and are programmed through the application 6 Wire the Reader switches to th...

Page 27: ...rown reader wire to the RED LED terminal This is the red LED circuit 7 Install MOVs WARNING Noise Suppression INSTALL THE TRANSIENT NOISE SUPPRESSION DEVICE MOV SUPPLIED WITH THE CONTROL PANEL a Install the MOV across the conductors as close as possible to the electric strike or latch This will normally be at the connection from the field installed wiring to the pig tail or screw terminals of the ...

Page 28: ...s placed in series with the switch so that one end of the resistor is connected to wire 1 from the switch while the other end is connected to the wire leading to the ACS5000 control board e The other wire from the ACS5000 is connected to wire 2 from the switch as shown in Figure 18 Figure 18 EOL Resistor Wiring WARNING Powering Electronic Strikes and Latches DO NOT POWER ELECTRONIC STRIKES AND LAT...

Page 29: ...Merged separate ACS5000 A E F S manuals into a single installation manual 1 1 11 30 2016 LMW Added clarification for FIPS 201 compliance 1 2 01 06 2017 LMW Added ANSI NFPA70 compliance language 1 3 02 15 2017 LMW Added parts and service clarification 1 4 02 21 2017 LMW Added UL compliance language per UL request 1 5 04 26 2017 LMW Removed reference to the F panel and Brivo OnAir for Government P M...

Reviews: