![BriskHeat SCHCBL Series Installation & Maintenance Instruction Manual Download Page 8](http://html1.mh-extra.com/html/briskheat/schcbl-series/schcbl-series_installation-and-maintenance-instruction-manual_2813313008.webp)
Self Regulating Heating Cable
© BriskHeat
®
Corporation. All rights reserved.
15
FM APPROVED SLCAB connection / termination kit
KITS
USAGE
SLCABUC:
SLCAB Universal Connection Kit. FM approved.
1
2
4
2
2
2
1
1
1
1
1
3/4” (19mm) NPT pipe standoff
Ring terminals
Large, Insulated crimp connectors
Small, Insulated crimp connectors
Pipe straps (for up to 6” (152mm) IPS pipe)
Heat sink end caps
6” (152mm) shrink sleeve
3 oz. (89ml) tube of RTV sealant
Roll of fiberglass tape
Caution label
Ground screw
Ordinary Locations
Hazardous (Classified) Locations
Class I, Division 2, Group B, C, D
Class II, Division 2, Group F, G
Class III, Division 2
Approvals valid only when
used with appropriate heating cable and installation
accessories, and installed in accordance with all applicable instructions, codes, and
regulations.
Enough to complete:
Two end terminations and one input connection, or one input power splice
NOTE: Requires a 3/4” (19mm) NPT junction box
SLCABSK:
SLCABSK Kit. FM approved.
20
20
10
1
Large yellow crimp connectors
Large blue crimp connectors
Heat shrink tubes
3 oz, (89ml) tube of RTV sealant
Enough to complete:
Ten input power connections, or Ten tee splices
10 Heat shrink tube
Enough to complete:
Ten end terminations
SLCABKC:
SLCAB End Seal Kit. FM approved.
KITS
USAGE
SLMCABUC:
SLMCAB Universal Connection Kit. FM approved.
1
2
3
2
2
2
1
1
1
1
3/4” (19mm) NPT pipe standoff
Ring terminals
Large, crimp connectors
Small, crimp connectors
Pipe straps (for up to 6” (152mm) IPS pipe)
End boots
3 oz. (89ml) tube of RTV sealant
Roll of fiberglass tape
Caution label
Ground screw
Ordinary Locations
Hazardous (Classified Locations
Class I, Division 2, Group B, C, D
Class II, Division 2, Group F, G
Class III, Division 2
Approvals valid only when
used wir appropriate heating cable and installation
accessories, and installed in accordance with all applicable instructions, codes, and
regulations.
Enough to complete:
Two end terminations and one input connection, or one input power splice, or one tee
splice
NOTE: Requries a 3/4” (19mm) NPT junctiuon box
10
4
1
End boots
Roll of fiberglass tape
3 oz, (89ml( tube of RTV sealant))
Enough to complete:
Ten end terminations
SLMCABKC:
SLMCAB End Seal Kit. FM approved.
FM APPROVED SLMCAB connection / termination kit
Self Regulating Heating Cable
© BriskHeat
®
Corporation. All rights reserved.
16
CSA APPROVED SLCAB AND SLMCAB connection / termination kit
KITS
USAGE
SLCABUC-CSA-M:
SLCAB and SLMCAB Universal Connection Kit. CSA approved.
1
1
2
1
1
1
1
1
1
1
1
1
1
1
Connector body
Connector cap
Connector gland washers
Grommet
Termination boot
Stain relief grip
Standoff bracket
Locknut
Termination block
Roll of fiberglass tape
Silicone sealant
Pipe strap (for 2” to 6” (51 to 152mm) O.D.pipes)
Ring tongue terminal
End seal kit
Approvals valid only when
used with appropriate heating cable and installation
accessories, and installed in accordance with all applicable instructions, codes, and
regulations.
*2E approved for 3 watts/ft and 5 watts/ft only
Enough to complete:
One input connection and one end termination. Splices and power input splices can be
made using two kits
NOTE: Requires a 3/4” (19mm) NPT junction box
1
1
1
End cap
Clamp
Sealant
Enough to complete:
One end termination
SLCABEND-CSA-2:
SLCAB and SLMCAB End Seal Kit. CSA approved.
Ordinary Locations 130-03 (-G,-W, -S)
Hazardous (Classified) Locations
Class I, Division 1
†
and 2, Groups B, C, D
Class II, Division 1
†
and 2, Groups E, F, G
Class III, Division 1
†
and 2
3, 5, 8 W/ft T6
10 W/ft T5
CSA APPROVED SLHCAB connection / termination kit
KITS
USAGE
SLCABPWP-H :
SLHCAB Power Connection Kit for pipes. CSA approved.
1
1
2
1
1
1
2
1
1
1
1
1
Base
Top
Junction Box
Sealing Grommet (large hole)
Sealing Grommet (small hole)
Sealing Gasket
Shrink Tubes 1/8" x 51/2" (black)
Shrink Tube 1/4" x 51/2" (green/yellow)
Shrink Tube 1/2" x 11/2" (white)
Lock Ring
Adaptor (for installation on pipe smaller than 1")
Stainless Steel Tie Wire
Approvals valid only when
used with appropriate heating cable and installation
accessories, and installed in accordance with all applicable instructions, codes, and
regulations.
Enough to complete:
One input connection and one end termination. Splices and power input splices can be
made using two kits
NOTE: Requires a 3/4” (19mm) NPT junction box
1
1
1
End cap
Clamp
Sealant
Enough to complete:
One end termination
SLCABKC-H:
SLHAB End Seal Kit. CSA approved.
Ordinary Locations 130-03 (-G,-W, -S)
Hazardous (Classified) Locations
Class I, Division 1
†
and 2, Groups B, C, D
Class II, Division 1
†
and 2, Groups E, F, G
Class III, Division 1
†
and 2
3, 5, 8 W/ft T6
10 W/ft T5
†
CI/D1 approval for BF only. Contact a BriskHeat representative for information on Division I hazardous location systems.