background image

2.3 Overview operational controls

The Air Control - Allure clock thermostat has a number of buttons with which the device can be operated:

1 = Setting knob

2 = 

Return key

3 =

Setting & activating timer programme

4 = 

Key manual control

5 = 

Setting key operation mode

1. This setting knob (menu) has various functions depending on the selected menu.

Turn - Change temperature / time setting or select menu.

Press - Open selected menu or confirm selection.

2. The “Return” key always takes you one step back in the menu or cancels a temporary or manual setting.
3. Key for setting the time programme
4. Pressing the key manual control allows putting the Air Control - Allure clock thermostat at a constant

temperature for an indefinite period (see section 5.2).

5. This key allows you to choose from four different operating modes (refer to the table below).

Four different operating modes can be selected with the key nr. 5; on the display the selected operating

mode is shown in red (1, 2, 3 or 

T

):

1 Ventilation mode off

The system fan is controlled by the temperature sensor; if there is no heat demand, the system fan is

stopped.

Burner modulating in accordance with heat demand room thermostat.

2 Comfort mode

The system fan is controlled by the temperature sensor; if there is no heat demand, the system fan

runs continuously at minimum air flow rate.

Burner modulating in accordance with heat demand room thermostat.

3 Increased ventilation mode

The system fan runs continuously at maximum preset air flow rate.

Burner modulating in accordance with heat demand room thermostat.

T

Cooling on

If there is cooling demand, the system fan runs continuously in cooling mode; if there is no cooling

demand, the system fan runs at minimum air flow rate.

The burner can never be activated when the left-hand setting knob is set at cooling mode.

Air Control - Allure clock thermostat 616720-A

Brink / 5

Summary of Contents for Air Control Allure

Page 1: ...aphorst T 31 0 522 46 99 44 F 31 0 522 46 94 00 info brinkclimatesystems nl www brinkclimatesystems nl Modifications reserved Art nr 614884 C 1 Brink Air Control Ventilation 2 Brink Air Control Allure The Allure manual starts after page 32 of the Ventilation manual STORE NEAR THE APPLIANCE ...

Page 2: ......

Page 3: ...Brink Air Control Ventilation English Installation regulations ...

Page 4: ...e Brink Air Control Ventilation 14 5 Description of operation manner of use 15 5 1 Navigation general description 15 5 2 Selecting a device connected to the Brink Air Control Ventilation 16 5 3 Weekly programmes P1 P2 and P3 16 5 3 1 Standard settings P1 P2 and P3 16 5 3 2 Creating a P1 program 17 5 3 3 Creating a P2 program 18 5 3 4 Creating a P3 program 19 5 4 Activating program type P1 P2 or P3...

Page 5: ...tilation should be used in combination with products that have been approved by Brink Climate Systems B V Brink Climate Systems B V cannot be held responsible for possible damage caused by improper incorrect or unwise use It is important that one understands this user s manual completely Working with other devices The Brink Air Control Ventilation is connected to other devices The HRU Heat Recover...

Page 6: ...se 2 2 Environment influences The Brink Air Control Ventilation should be placed and used in a space with the correct ambient conditions for proper operation The Brink Air Control Ventilation may only be mounted on the indoors but not on the vicinity of a heat source a radiator in a draft or in a humid environment The Brink Air Control Ventilation may also not be exposed to direct radiation heat s...

Page 7: ...nob Return key Setting activating timer programme Manual control key Bypassing the timer programme 2 4 Overview display version main screen 1 2 3 4 5 6 7 8 Flow rate indicator eBus connection indicator Fan indicator Fault symbol Filter message Current time block Current time Current date day month year Brink Air Control Ventilation 614884 B Brink 5 ...

Page 8: ...e Description of operation manner of use page 15 You can adjust every ventilation mode yourself for more information Setting ventilation mode values page 21 You can retrieve the set values at the Device information menu see below Ventilation modes 1 2 3 Device information HRU appliance Information HRU ventilation Brink Air Control Ventilation 614884 B ...

Page 9: ... relative humidity between 0 and 90 All settings excluding the filter message will be lost if the Brink Air Control Ventilation breaks down or if the factory settings are reset There is no backup available 3 2 During placement Take note Assembly and installation should be performed by an installer approved by Brink Climate Systems B V The following requirements should be taken into account during ...

Page 10: ...tion may not be removed as unsorted urban waste but should be treated separately Make enquiries within your own region where the Brink Air Control Ventilation can be handed in when use has been terminated Do not throw away electrical devices or parts but check if parts of the Brink Air Control Ventilation cannot be handed in recycled or re used Brink Air Control Ventilation 614884 B ...

Page 11: ...ional module from the wall bracket Disconnect the operational module from the wall bracket Perform the following actions Slide the control unit upward over the two guide profiles of the wall bracket until the control unit can be taken off 4 1 2 Mounting the wall bracket The wall bracket can be attached to a wall box Ø 55 mm or can be directly mounted on the wall with screws and plugs Screw the wal...

Page 12: ...on 4 1 4 Replacing the operational module in the wall bracket Place the operational in the wall bracket mounted on the wall Perform the following actions for this Slide the control unit downward over the two guide profiles Make sure the guide profiles of the wall bracket fit snugly in the cutouts of the control unit provided for that purpose 1 25 seconds 2 HRU ventilation Take note The operational...

Page 13: ...Settings opens Select Language by turning setting knob 1 Press setting knob 1 Language opens Select the desired language by turning setting knob 1 Press setting knob 1 to set the selected language Press return key 2 as many times as necessary to get to the main screen 1 2 3 Basic settings Language Englisch Take note The names of the described menu items will not correspond with this user manual s ...

Page 14: ...reen Press setting knob 1 Main Menu opens Select Basic Settings by turning setting knob 1 Press setting knob 1 Basic Settings opens Select Clock by turning setting knob 1 Press setting knob 1 Clock opens Change the time by turning setting knob 1 Press setting knob 1 to confirm the time Repeat the previous two steps for both the minutes and seconds Press returnkey 2 as many times as necessary to ge...

Page 15: ...Press setting knob 1 Basic Settings opens Select Date by turning setting knob 1 Press setting knob 1 Date opens Change the day by turning setting knob 1 Repeat the previous two steps for both the months and the year Press returnkey 2 as many times as necessary to get to the main screen 1 Flow rate indicator 2 eBus connection indicator 3 Fan indicator 4 Fault symbol 5 Filter message 6 Current time ...

Page 16: ...n Press setting knob 1 Main Menu opens Select Installer by turning setting knob 1 Press setting knob 1 Installer opens Select Device by turning setting knob 1 Press setting knob 1 to confirm selected device If only one appliance is connected no choice is offered and only Heat Recovery Unit appliance is displayed 1 Installer 2 HRU appliance 3 Device settings 4 Please wait Loading data 5 Airflow mod...

Page 17: ...use setting knob 1 You scroll through the menus by turning the setting knob 1 You can open a selected menu item by pressing the setting knob 1 1 Main menu 2 Device information 3 Basic settings 4 Installer Return to the main screen The main screen is the Brink Air Control Ventilation start screen You can always return to the main screen by pressing on the return key 2 a few times The number of time...

Page 18: ...kly program You can choose from programs P1 P2 and P3 Program P1 With this you create a day program for every day of the week Program P2 With this you create two day programs One day program for weekdays mo fri and one day program for the weekend sa su Program P3 With this you create seven day programs Separately for every day of the week 5 3 1 Standard settings P1 P2 and P3 The Brink Air Control ...

Page 19: ...Time by turning setting knob 1 Press setting knob 1 Start Time opens Change the start time by turning setting knob 1 You have a range of between 3 00u and 2 59u If in a period the time is turned back so far that lines appear that period and the one above it will be deleted Press setting knob 1 to confirm the start time Now set the ventilation mode for period 1 Perform the following actions for thi...

Page 20: ...etting knob 1 Press setting knob 1 Period 1 opens Select start time by turning setting knob 1 Press setting knob 1 start time opens Change start time by turning setting knob 1 You have a range of between 3 00 hrs and 2 59 hrs Press setting knob 1 to confirm start time Now set the ventilation mode for period 1 Perform the following actions for this Select Ventilatiestand by turning setting knob 1 P...

Page 21: ... opens Select Start time by turning setting knob 1 Press setting knob 1 Start time opens Change Start time by turning setting knob 1 You have a range of between 3 00u and 2 59u Press setting knob 1 to confirm Start time Now set the ventilation mode for period 1 Perform the following actions for this Select Ventilation mode by turning setting knob 1 Press setting knob 1 Ventilatiestand opens Set th...

Page 22: ...een Press knob 5 Bypassing the timer programme opens Turn setting knob 1 to temporarily set the ventilation mode Take note It is stated at the top of your screen how long the newly set ventilation mode applies The program will be enabled again after this period of time The override period will be 30 minutes if you overruled the device in the maximum position You can also undo this by pressing retu...

Page 23: ... knob 1 Press setting knob 1 Device settings opens Select Airflow 0 Holiday by turning setting knob 1 Take note Airflow 0 Holiday refers to ventilation mode Airflow 1 Reduced refers to ventilation mode Airflow 2 Normal refers to ventilation mode Airflow 3 High refers to ventilation mode Set Airflow 0 Holiday by turning setting knob 1 Press setting knob 1 to confirm the set value for Airflow 0 Holi...

Page 24: ...ntilation It is possible to set back all this device s settings to the factory settings Perform the following actions for this Press returnkey 2 as many times as necessary to get to the main screen Pressetting knob 1 Main Menu opens Select Installation Settings by turning setting knob 1 Press setting knob 1 Installation Settings opens Select Installer by turning setting knob 1 Press setting knob 1...

Page 25: ...ation The filters in the device connected to the Brink Air Control Ventilation should be cleaned or replaced when the text FILTER appears on the Brink Air Control Ventilation display 6 2 2 Removing cleaning or replacing Consult the manual of the device connected to the Brink Air Control Ventilation for removing cleaning and replacing filters Brink Air Control Ventilation 614884 B Brink 23 ...

Page 26: ...aned or replaced the filter or the filters For this you press the setting knob 1 for at least five seconds Press returnkey 2 to get to the main screen The text filter on the Brink Air Control Ventilation display disappears 1 2 Filter notification 5 seconds Brink Air Control Ventilation 614884 B ...

Page 27: ...ted to dismantle the Brink Air Control Ventilation or parts of the Brink Air Control Ventilation by yourself This may only be done by a maintenance mechanic approved by Brink Climate Systems B V Brink Air Control Ventilation 614884 B Brink 25 ...

Page 28: ...ed to open or repair the Brink Air Control Ventilation or parts of the Brink Air Control Ventilation by yourself This may only be done by a maintenance mechanic approved by Brink Climate Systems B V Brink Air Control Ventilation 614884 B ...

Page 29: ...moting re use recycling and other forms of recovering such waste in order to limit the amount of waste The WEEE logo on a product or on the packaging indicates that this product may not be disposed of or thrown away with domestic waste You should dispose of all your old electronic or electrical equipment via special collection points for such dangerous waste Separate collection and correct treatme...

Page 30: ...ditions These can be found on www brinkclimatesystems com Do you want to claim under the guarantee You then have to make that known in writing via Brink Climate Systems B V Mailbox 11 NL 7950 AA Staphorst The Netherlands The right to guarantee lapses in case of incorrect or improper use of the Brink Air Control Ventilation and failure to follow the user indications in this user s manual Warning Ma...

Page 31: ...ndard settings weekly programs 11 1 Standard program P1 Week Monday through Sunday Period Start time Ventilation mode 1 07 00 2 08 00 3 17 00 4 22 00 5 Not set 6 Not set Brink Air Control Ventilation 614884 B Brink 29 ...

Page 32: ...iday Weekend Saturday and Sunday Period Start time Ventilation mode Period Start time Ventilation mode 1 07 00 1 08 00 2 08 00 2 23 00 3 17 00 3 Not set 4 22 00 4 Not set 5 Not set 5 Not set 6 Not set 6 Not set Brink Air Control Ventilation 614884 B ...

Page 33: ...de 1 07 00 2 08 00 3 17 00 4 22 00 5 Not set 6 Not set Tuesday the same as Monday Wednesday the same as Monday Thursday the same as Monday Friday the same as Monday Saturday the same as Monday Sunday the same as Monday Brink Air Control Ventilation 614884 B Brink 31 ...

Page 34: ...Air Control Allure clock thermostat English Installation regulations ...

Page 35: ...e setting on or off 14 4 2 5 Change factory program setting 15 5 Description of operation manner of use 17 5 1 Navigation general description 17 5 2 Weekly programmes P1 P2 and P3 18 5 2 1 Activating program type P1 P2 or P3 18 5 2 2 Activating cooling program type P1 P2 or P3 19 5 2 3 Temperarily overriding program 20 5 2 4 Overriding program for a longer period of time 21 5 2 5 Retrieving settin...

Page 36: ...l The Brink Air Control Allure clock thermostat automatically recognizes the correc Brink appliance to which it is connected Use in accordance with the instruction also means observance of the manual as well as all other additional applicable Brink Climate Systems B V documents Any other or more far reaching use is considered not in accordance with the instructions Brink Climate Systems B V cannot...

Page 37: ...onment influences The Air Control Allure clock thermostat should be placed and used in a space with the correct ambient conditions for proper operation The Air Control Allure clock thermostat may only be mounted on the indoors but not on the vicinity of a heat source a radiator in a draft or in a humid environment The Air Control Allure clock thermostat may also not be exposed to direct radiation ...

Page 38: ...Four different operating modes can be selected with the key nr 5 on the display the selected operating mode is shown in red 1 2 3 or T 1 Ventilation mode off The system fan is controlled by the temperature sensor if there is no heat demand the system fan is stopped Burner modulating in accordance with heat demand room thermostat 2 Comfort mode The system fan is controlled by the temperature sensor...

Page 39: ...lure clock thermostat display shows the desired room temperature set temperature to be set with the rotary knob 8 Fault code In the event of a malfunction in the air heater the Brink Air Control Allure clock thermostat display shows an error message It is composed of an E Error with an error number an error message is also shown on the air heater display Refer to the installation instructions supp...

Page 40: ... relative humidity between 0 and 90 All settings excluding the filter message will be lost if the Air Control Allure clock thermostat breaks down or if the factory settings are reset There is no backup available 3 2 During placement Take note Assembly and installation should be performed by an installer approved by Brink Climate Systems B V The following requirements should be taken into account d...

Page 41: ...ay not be removed as unsorted urban waste but should be treated separately Make enquiries within your own region where the Air Control Allure clock thermostat can be handed in when use has been terminated Do not throw away electrical devices or parts but check if parts of the Air Control Allure clock thermostat cannot be handed in recycled or re used Air Control Allure clock thermostat 616720 A ...

Page 42: ...al module from the wall bracket Disconnect the operational module from the wall bracket Perform the following actions Slide the control unit upward over the two guide profiles of the wall bracket until the control unit can be taken off 4 1 2 Mounting the wall bracket The wall bracket can be attached to a wall box Ø 55 mm or can be directly mounted on the wall with screws and plugs Screw the wall b...

Page 43: ...1 4 Replacing the operational module in the wall bracket Place the operational in the wall bracket mounted on the wall Perform the following actions for this Slide the control unit downward over the two guide profiles Make sure the guide profiles of the wall bracket fit snugly in the cutouts of the control unit provided for that purpose 1 25 seconds 2 Brink Air heating system Take note The operati...

Page 44: ...s opens Select Language by turning setting knob 1 Press setting knob 1 Language opens Select the desired language by turning setting knob 1 Press setting knob 1 to set the selected language Press return key 2 as many times as necessary to get to the main screen 1 Basic settings 2 Language 3 English Take note The names of the described menu items will not correspond with this user manual s menu ite...

Page 45: ...1 Main Menu opens Select Basic Settings by turning setting knob 1 Press setting knob 1 Basic Settings opens Select Clock by turning setting knob 1 Press setting knob 1 Clock opens Change the time by turning setting knob 1 Press setting knob 1 to confirm the time Repeat the previous two steps for both the minutes and seconds Press return key 2 as many times as necessary to get to the main screen 1 ...

Page 46: ...Select Basic Settings by turning setting knob 1 Press setting knob 1 Basic Settings opens Select Date by turning setting knob 1 Press setting knob 1 Date opens Change the day by turning setting knob 1 Repeat the previous two steps for both the months and the year Press return key 2 as many times as necessary to get to the main screen 1 Basic settings 2 Date menu 3 Adjustable date Air Control Allur...

Page 47: ...aptive temperature control Press return key 2 as many times as necessary to get to the main screen Press setting knob 1 Main Menu opens Select Basic Settings by turning setting knob 1 Press setting knob 1 Basic Settings opens Select Adaptive by turning setting knob 1 Press setting knob 1 Adaptive opens Select the desired adjustment by turning setting knob 1 Press setting knob 1 to set the selected...

Page 48: ...nob 1 Basic Settings opens Select clock program or clock program cooling by turning setting knob 1 Press setting knob 1 selected program opens Select program you wanted to adjust by turning and pressing setting knob 1 Select period you wanted to adjust by turning and pressing setting knob 1 Select Start time and or Temp selection depending which setting you wanted to adjust by turning and pressing...

Page 49: ...1 Clock program 2 Selected program P1 3 Selected period 2 4 Adjustable time 5 Adjustable temperature Air Control Allure clock thermostat 616720 A ...

Page 50: ... scroll through the menus by turning the setting knob 1 You can open a selected menu item by pressing the setting knob 1 1 Main menu 2 Menu device information 3 Menu basic settings 4 Menu clock program 5 Menu clock program cooling Return to the main screen The main screen is the Air Control Allure clock thermostat start screen You can always return to the main screen by pressing on the return key ...

Page 51: ...e week 5 2 1 Activating program type P1 P2 or P3 The Air Control Allure clock thermostat has three types of weekly heating programs P1 P2 and P3 You can program the weekly heating programs by yourself for more information see paragraph Weekly programmes P1 P2 and P3 page 18 Perform the following actions if you wish to program one of the weekly programs Press return key 2 as many times as necessary...

Page 52: ... key 2 as many times as necessary to get to the main screen Press setting knob 4 unil cooling symbol appears on display The thermostat runs automatically than a cooling timer programme Changing the cooling timer program by pressing knob 3 clock program cooling opens Turn and press knob 1 to open Activate program Select cooling program P1 P2 or P3 by turning setting knob 1 Press setting knob 1 to a...

Page 53: ...as this modified temperature is active the text TEMPORARILY is visible on the display This temporary temperature adjustment remains active until the next clock program set point is reached Note At least 2 periods must be programmed otherwise the temporary temperature setting will not be canceled Period 1 may not have a start time of 3 00 this is not seen as a switch on point by the thermostat If y...

Page 54: ...et to the main screen Press knob 3 and Manual appears in the display Turn setting knob 1 to set the desired temperature The manual position now overrules the programme Press return key 2 if you wish to undo the manual position Return key 2 can not be operated until some 10 seconds after the latest setting 1 Notification manual temperature set 2 Desired manual temperature Air Control Allure clock t...

Page 55: ...nu opens Select Device information by turning setting knob 1 Press setting knob 1 Device information opens Turn setting knob 1 to display the desired information Press return key 2 if you wish to exit the device information 1 Device information menu 2 Displayed device information Take note You can look at but not change the settings via the device information menu Air Control Allure clock thermost...

Page 56: ...setting knob 1 Press setting knob 1 Installation Settings opens Select Installer by turning setting knob 1 Press setting knob 1 Installer opens Select Factory Setting by turning setting knob 1 Press setting knob 1 Factory Setting opens Turn setting knob 1 to select the option yes Press setting knob 1 to confirm the desired Factory Setting The settings are put back to the factory settings Selecting...

Page 57: ...e filters in the device connected to the Air Control Allure clock thermostat should be cleaned or replaced when the text FILTER appears on the Air Control Allure clock thermostat display 6 2 2 Removing cleaning or replacing Consult the manual of the device connected to the Air Control Allure clock thermostat for removing cleaning and replacing filters Air Control Allure clock thermostat 616720 A ...

Page 58: ...laced the filter or the filters For this you press the setting knob 1 for at least five seconds Press returnkey 2 to get to the main screen The text filter on the Air Control Allure clock thermostat display disappears 1 2 Filter notification 5 seconds Air Control Allure clock thermostat 616720 A Brink 25 ...

Page 59: ...to dismantle the Air Control Allure clock thermostat or parts of the Air Control Allure clock thermostat by yourself This may only be done by a maintenance mechanic approved by Brink Climate Systems B V Air Control Allure clock thermostat 616720 A ...

Page 60: ... repair the Air Control Allure clock thermostat or parts of the Air Control Allure clock thermostat by yourself This may only be done by a maintenance mechanic approved by Brink Climate Systems B V Air Control Allure clock thermostat 616720 A Brink 27 ...

Page 61: ...r promoting re use recycling and other forms of recovering such waste in order to limit the amount of waste The WEEE logo on a product or on the packaging indicates that this product may not be disposed of or thrown away with domestic waste You should dispose of all your old electronic or electrical equipment via special collection points for such dangerous waste Separate collection and correct tr...

Page 62: ...se can be found on www brinkclimatesystems com Do you want to claim under the guarantee You then have to make that known in writing via Brink Climate Systems B V Mailbox 11 NL 7950 AA Staphorst The Netherlands The right to guarantee lapses in case of incorrect or improper use of the Air Control Allure clock thermostat and failure to follow the user indications in this user s manual Warning Making ...

Page 63: ...21 0 C 5 22 00 16 0 C 6 00 00 16 0 C 11 2 Standard program P2 Week Monday through Friday Weekend Saturday and Sunday Period Start time Set temperature Period Start time Set temperature 1 07 00 20 0 C 1 08 00 20 0 C 2 08 00 16 0 C 2 17 00 21 0 C 3 17 00 20 0 C 3 23 00 16 0 C 4 20 00 21 0 C 4 00 00 16 0 C 5 22 00 16 0 C 5 C 6 00 00 16 0 C 6 C Air Control Allure clock thermostat 616720 A ...

Page 64: ...rature 1 07 00 20 0 C 2 08 00 16 0 C 3 17 00 20 0 C 4 20 00 21 0 C 5 22 00 16 0 C 6 00 00 16 0 C Saterday Sunday Period Start time Set temperature 1 08 00 20 0 C 2 17 00 21 0 C 3 23 00 16 0 C 4 00 00 16 0 C 5 C 6 C Air Control Allure clock thermostat 616720 A Brink 31 ...

Page 65: ...0 28 0 C 3 C 4 C 5 C 6 C 11 5 Standard cooling program P2 Week Monday through Friday Weekend Saturday and Sunday Period Start time Set temperature Period Start time Set temperature 1 07 00 24 0C 1 08 00 24 0 C 2 22 00 28 0 C 2 23 00 28 0 C 3 C 3 C 4 C 4 C 5 C 5 C 6 C 6 C Air Control Allure clock thermostat 616720 A ...

Page 66: ...ay Friday Period Start time Set temperature 1 07 00 24 0 C 2 22 00 28 0 C 3 C 4 C 5 C 6 C Saterday Sunday Period Start time Set temperature 1 08 00 24 0 C 2 23 00 28 0 C 3 C 4 C 5 C 6 C Air Control Allure clock thermostat 616720 A Brink 33 ...

Page 67: ......

Page 68: ...inkClimateSystemsB V WethouderWassebaliestraat8 7951SN Staphorst P O Box11 NL 7950AAStaphorst T 31 0 522 46 99 44 F 31 0 522 46 94 00 info brinkclimatesystems nl www brinkclimatesystems nl Art nr 614884 C ...