Fuel Consumption
Estimated fuel supply requirements at half and full load
for natural gas and LP vapor fuels are shown below.
LP Vapor (Propane)
20kW
17kW
Full Load
Cu Ft/Hr
135
118
Gal/Hr
(liquid)
3.75
3.28
BTU/Hr
337500
295000
3/4 Load
Cu Ft/Hr
109
99
Gal/Hr
(liquid)
3.03
2.75
BTU/Hr
272500
247500
1/2 Load
Cu Ft/Hr
83
74
Gal/Hr
(liquid)
2.31
2.06
BTU/Hr
207500
185000
1/4 Load
Cu Ft/Hr
56
54
Gal/Hr
(liquid)
1.56
1.5
BTU/Hr
140000
135000
Exercise
Cu Ft/Hr
40
40
Gal/Hr
(liquid)
1.11
1.11
BTU/Hr
100000
100000
Natural Gas
20 kW
(18 kW)
17 kW
(15.3 kW)
Full Load
Cu Ft/ Hr
260
248
BTU / Hr
260000
248000
3/4 Load
Cu Ft/ Hr
240
218
BTU / Hr
240000
218000
1/2 Load
Cu Ft/ Hr
187
170
BTU / Hr
187000
170000
1/4 Load
Cu Ft/ Hr
135
128
BTU / Hr
135000
128000
Exercise
Cu Ft/ Hr
99
99
BTU / Hr
99000
99000
Recommended
Energy Content of
Fuel
LP Vapor Natural
Gas
Heating Value:
BTU per gallon (gross**)
Cubic feet (gas)
91,547
2,500
1,000
Fuel Pressure
Both LP vapor and natural gas fuel supply pressure
at the generator’s fuel inlet port should be between
the following levels at full load with all gas appliances
turned on and operating.
• NG is 3.5-7”
• LP is 11-14” W.C.
Ensure that all gas line shutoff valves are OPEN and
that adequate fuel pressure is available whenever
automatic operation is desired.
For natural gas fuel pressure levels of 3.5-5” W.C.,
replace regulator assembly with service kit 6331-00.
Power Loss
Air density is less at high altitudes, resulting in less
available engine power. Specifically, engine power
will decrease 3.5% for each 1,000 feet (300 meters)
above sea level and 1% for each 10° F (5.6°C) above
77°F (25°C). Make sure you and your installer consider
these factors when determining total generator load.
Fuel Pipe Sizing
There are numerous on-line or otherwise-published
references for fuel pip sizing. For example, NFPA
54-Natural Fuel Gas Code, 2006 (Item #: 320-6031-06)
is a common resource.
The installer should consider the specific gravity of gas
and compensate for a nominal amount of restriction
from bends, fittings, etc. If an unusual number of
fittings, bends, or other restrictions are used, refer to
federal and local codes for guidance.
Summary of Contents for Fortress
Page 45: ...N o t f o r R e p r o d u c t i o n 45 This page was intentionally left blank...
Page 52: ...N o t f o r R e p r o d u c t i o n 52 This page was intentionally left blank...
Page 97: ...N o t f o r R e p r o d u c t i o n 45 Esta p gina se dej intencionalmente en blanco...
Page 104: ...N o t f o r R e p r o d u c t i o n 52 Esta p gina se dej intencionalmente en blanco...
Page 149: ...N o t f o r R e p r o d u c t i o n 45 Cette page a t laiss e en blanc intentionnellement...
Page 156: ...N o t f o r R e p r o d u c t i o n 52 Cette page a t laiss e en blanc intentionnellement...