32
Initial Start-up (No Load)
The unit has been set-up for NG operation at the factory.
Fuel conversion, if needed, must be completed prior to
performing these steps. See
Fuel Conversion
.
Before operating the home generator or placing it into service,
inspect the entire installation carefully. Then begin testing the
system without any electrical loads connected, as follows:
1. Remove two screws (
A
) that secure circuit breaker
cover to expose unit’s circuit breaker.
2. Connect an accurate frequency meter to line side of
generator’s main circuit breaker.
3. Set generator’s main circuit breaker to
ON
(closed) position.
4. Install 15 Amp fuse in control board.
5. Press and hold
MANUAL
button on control board
for 3 seconds. Engine will start.
When the generator is started for the very first time, it will
require that air in the gaseous fuel lines be purged. This
may cause the engine to run roughly for a few minutes.
6. Listen for unusual noises, vibration or other
indications of abnormal operation. Check for oil
leaks while engine runs.
7. Let engine warm up for about 5 minutes to allow
internal temperatures to stabilize.
8. Check generator output at load side of circuit
breaker. Voltage should be 239 - 262 Volts,
frequency should be 62.0 - 62.5 Hz.
9. Check generator output between one generator
connection lug and neutral lug, then between
other generator connection lug and neutral lug. In
both cases, voltage reading should be between
112 and 125 Volts.
10. Push and hold
OFF
BUTTON
on control board until
engine stops.
11. Reinstall control box cover.
CAUTION
Installing the 15A fuse could cause the engine
to start at any time without warning resulting in minor or
moderate injury.
• Observe that the 15 Amp fuse has been removed from the
control panel for shipping.
• DO NOT install this fuse until all plumbing and wiring has been
completed and inspected.
MENU
ESC
AUTO
OFF
MANUAL
A
Not for
Reproduction
Summary of Contents for 6404
Page 38: ...38 Schematic Diagram 10kW Schematic Wiring Diagrams N o t f o r R e p r o d u c t i o n ...
Page 39: ...39 N o t f o r R e p r o d u c t i o n ...
Page 52: ...52 This page was intentionally left blank N o t f o r R e p r o d u c t i o n ...
Page 60: ...60 N o t f o r R e p r o d u c t i o n ...
Page 99: ...39 N o t f o r R e p r o d u c t i o n ...
Page 112: ...52 Página dejada en blanco intencionalmente N o t f o r R e p r o d u c t i o n ...
Page 120: ...60 N o t f o r R e p r o d u c t i o n ...
Page 158: ...38 Schéma graphique 10 kW Schémas graphique câblage N o t f o r R e p r o d u c t i o n ...
Page 159: ...39 N o t f o r R e p r o d u c t i o n ...
Page 172: ...52 Cette page a été laissée en blanc intentionnellement N o t f o r R e p r o d u c t i o n ...