Communication Connections
Connect the applicable communication leads to the
automatic transfer switch as shown in the table below.
* Metric system rounded for simplicity
Pin
Number
Description
Wire Type
Connect To
Notes
1
Normally Open
18 AWG [1 mm²] twisted pair conductors no longer
than 61 m, 300V, 90°C copper wire
For Optional Alarm
2
Common
18 AWG [1 mm²] twisted pair conductors no longer
than 61 m, 300V, 90°C copper wire
For Optional Alarm
3
Normally Closed
18 AWG [1 mm²] twisted pair conductors no longer
than 61 m, 300V, 90°C copper wire
For Optional Alarm
4
Transfer Switch
Communication
18 AWG [1 mm²] twisted pair conductors no longer
than 61 m, 300V, 90°C copper wire
4 (T/R) on transfer switch
board
Must Connect
5
Transfer Switch
Communication Ground
18 AWG [1 mm²] twisted pair conductors no longer
than 61 m, 300V, 90°C copper wire
5 (GND) Ground on transfer
switch board
Must Connect
6
+LED
18 AWG [1 mm²] twisted pair conductors no longer
than 61 m, 300V, 90°C copper wire
Red wire on fault indicator
plate
For Optional Fault
Indication
7
Ground
18 AWG [1 mm²] twisted pair conductors no longer
than 61 m, 300V, 90°C copper wire
Black wire on fault indicator
plate
For Optional Fault
Indication Ground
8
Not Used
N/A
N/A
N/A
25
Utility
14 AWG [2.5 mm²] minimum 300v wire
Transfer Switch Utility
Must Connect
26
Utility
14 AWG [2.5 mm²] minimum 300v wire
Transfer Switch Utility
Must Connect
Generator AC Connection System
A single-phase, three-wire AC connection system is used
in the home generator. The stator assembly consists of
a pair of stationary windings with two leads brought out
of each winding. The junction of leads 22 and 33 forms
the neutral lead, as shown schematically and as a wiring
diagram. A complete schematic and wiring diagram can be
found later in this manual.
NOTICE
Neutral is not bonded to ground at generator.
NOTICE
Generator must be used with only an UL listed
transfer switch that is compatible with the generator.
240V
120V
120V
Po
wer Winding
11
44
Neutral
Circuit
Breaker
33
22
Circuit
Breaker
33
22
11
0
44
N
L1
L2
Not for
Reproduction
Summary of Contents for 6404
Page 38: ...38 Schematic Diagram 10kW Schematic Wiring Diagrams N o t f o r R e p r o d u c t i o n ...
Page 39: ...39 N o t f o r R e p r o d u c t i o n ...
Page 52: ...52 This page was intentionally left blank N o t f o r R e p r o d u c t i o n ...
Page 60: ...60 N o t f o r R e p r o d u c t i o n ...
Page 99: ...39 N o t f o r R e p r o d u c t i o n ...
Page 112: ...52 Página dejada en blanco intencionalmente N o t f o r R e p r o d u c t i o n ...
Page 120: ...60 N o t f o r R e p r o d u c t i o n ...
Page 158: ...38 Schéma graphique 10 kW Schémas graphique câblage N o t f o r R e p r o d u c t i o n ...
Page 159: ...39 N o t f o r R e p r o d u c t i o n ...
Page 172: ...52 Cette page a été laissée en blanc intentionnellement N o t f o r R e p r o d u c t i o n ...