Not for
Reproduction
19
INSTALLATION
cont.
NOTICE
Concrete slab is not required unless mandated
by national rules and regulations of the
respective country
C
C
C
C
Figure 10
Anchor Holes
Figure 9
Lifting Generator
A
B
Lifting the Generator
The generator weighs more than 227kg. Use proper tools
and equipment in all phases of handling and moving the
generator.
Two 1.5 m lengths of steel pipe (
A
), supplied by the
installer, are required to lift the generator. Steel pipe to
be 25 mm outer diameter and a minimum of 2.5 mm wall
thickness. Insert pipes through the lifting holes (
B
) located
in the generator’s base.
If using hoisting equipment to lift the generator, attach the
chains or cables to the lifting pipes with a spreader bar. The
proper use of a spreader bar will prevent damage to the
generator enclosure.
DO NOT
touch the roof when lifting the generator.
Concrete Anchoring
In areas prone to high winds or storms, it is recommended
to anchor the generator to concrete.
The concrete anchors
must be rated to hold 363 kg. There are four 11 mm hole
locations
(C)
around the base of the generator in which to
anchor the unit. See figure below.
WARNING
Lift Hazard - Heavy object could result
in serious injury.
DO
• Do
use lifting pipes as described in
Lifting
the Generator
.
DO NOT
• Do not
lift or move generator without
assistance.
NOTICE
Do not
lift unit by roof as this will damage the
generator and void warranty
WARNING
Electrical Shock - Contact with power
lines could cause electric shock or burns,
resulting in death or serious injury.
DO NOT
• Do not
contact any power lines if using
lifting or hoisting equipment.