(FC_5) UNDER FREQUENCY
The troubleshooting steps for under- and over-
frequency faults are identical.
The low frequency shutdown feature is designed to
protect the generator and its loads from an output
frequency that is too low. The control panel senses
frequency at Wires #E1 and #E2. If output frequency
drops below 55 Hz for three seconds, the control panel
will shut down the generator.
The digital display will show
FC_5
and the remote LED
will repeatedly flash five times with a pause.
Under frequency may be caused by:
• A restricted air filter
• A problem in the generator sense wiring
(#E1 or #E2)
• Incorrect engine governor adjustment
• Problems with the fuel delivery system
• Excessive loads
• Engine that is producing insufficient power.
• A problem in the control panel
TEST 1 - Check No-Load & Full-Load
Frequency
For the following procedures, we recommend the use
of Briggs & Stratton Digital Tach and Hour Meter
#19389.
Perform the following test under full electrical loads
with all gaseous fuel appliances turned
ON
and
operating.
No-Load RPM specification is
62.0-62.5 Hz
/ 3750 ± 100 RPM
Full-Load RPM specification is
57.0-62.5 Hz
/ 3420 ± 100 RPM
Check No-Load Frequency
1. Remove the four screws to gain access to the main
circuit breaker.
2. Reset the fault code detection system. See
Resetting
the Fault Code Detection System.
3. Ensure the generator circuit breaker is
ON
.
4. Set control panel system switch to
AUTO
, then push
and hold
MANUAL OVER-RIDE
to start the unit.
5. Measure frequency at the line side of the circuit
breaker (Figure 32).
Figure 32
• If frequency at no-load is correct, proceed to
Check Full-Load Frequency.
6.
If the no-load frequency is not correct,
use
needle nose pliers or Tang Bender #19229 or
#19480, bend spring anchor tang (
A
, Figure 33)
slowly up or down until frequency is 62.0 to 62.5 Hz.
Figure 33
WARNING
Battery posts, terminals, and related
accessories contain lead and lead compounds, chemicals
known to the State of California to cause cancer and
reproductive harm. Wash hands after handling.
Not
for
Reproduction
Summary of Contents for 040298
Page 23: ...19 1 1 N o t f o r R e p r o d u c t i o n...
Page 24: ...20 1 1 N o t f o r R e p r o d u c t i o n...
Page 29: ...25 2 2 N o t f o r R e p r o d u c t i o n...
Page 33: ...29 2 2 N o t f o r R e p r o d u c t i o n...
Page 36: ...32 2 2 N o t f o r R e p r o d u c t i o n...
Page 37: ...33 2 2 N o t f o r R e p r o d u c t i o n...
Page 43: ...39 2 2 N o t f o r R e p r o d u c t i o n...
Page 47: ...43 2 2 N o t f o r R e p r o d u c t i o n...
Page 50: ...46 2 2 N o t f o r R e p r o d u c t i o n...
Page 51: ...47 2 2 N o t f o r R e p r o d u c t i o n...
Page 55: ...51 2 2 N o t f o r R e p r o d u c t i o n...
Page 58: ...54 2 2 N o t f o r R e p r o d u c t i o n...
Page 66: ...4 N o t f o r R e p r o d u c t i o n...