Installation 

S19-280D, -280W, -290D, -290W, 274HDB, 274HWB, 274JDB, 274JWB

Bradley • 

215-1740 Rev. C; ECN 15-05-042 

12/7/2017

WARNING

Flush the water supply lines before beginning installation and after installation is complete. Test 

the unit for leaks and adequate water flow. Main water supply to the eyewash should be “ON” at all 

times. Provisions shall be made to prevent unauthorized shutoff.

CAUTION

Emergency equipment must be supplied with tepid water (60°F to 100°F/15.6°C to 37.8°C). Any 

prolonged exposure to near freezing water affects the body's ability to maintain body temperature, 

increasing the risk of hypothermia.

NOTICE

Before installing this product, ensure that there are adequate clearances around the product and 

activation of the product does not interfere with other products or obstructions.

Avoid cleaners containing organic solvents, alcohols and hydrocarbons. Rinse with water after 

cleaning.

IMPORTANT

The installation and location of all safety drench showers, eye and eye/face washes must comply 

with the requirements of ANSI/ISEA Z358.1.

Read this installation manual completely to ensure proper installation, then file it with the owner or 

maintenance department. Compliance and conformity to drain requirements and other local codes 

and ordinances is the responsibility  of the installer.

Separate parts from packaging and make sure all parts are accounted for before discarding any 

packaging material. If any parts are missing, do not begin installation until you obtain the missing 

parts.

 The ANSI/ISEA Z358.1 standard requires an uninterrupted supply of flushing fluid. Bradley plumbed 

emergency fixtures require a minimum of 30 PSI (0.21MPa) flowing pressure. 

 Self-closing spring-loaded valves are not UL classified to ANSI/ISEA Z358.1.

Weekly activation must be conducted on all plumbed emergency equipment to ensure a suitable 

flushing fluid supply is present and any sediment build-up in the supply line is cleared. Emergency 

equipment should be inspected monthly to address any maintenance issues ensuring the 

equipment is in good operating condition and that there are no signs of wear.

Workers who may come in contact with potentially hazardous materials should be trained regarding 

the placement and proper operation of emergency equipment per ANSI/ISEA Z358.1.

For questions regarding the operation or installation of this product, visit www.bradleycorp.com or 

call 800-BRADLEY (272.3539). 
Product warranties and parts information may also be found under ”Products” on our web site at 

bradleycorp.com.

Supplies Required:

•  Piping to ½" NPT water supply inlet on unit
• Pipe sealant
•  Sign-mounting hardware

 

Local codes may require the installation of a backflow prevention valve 
to complete proper installation. Compliance with local codes is the 
responsibility of the installer. Valve must be tested annually to verify that 
it is functioning properly. Backflow prevention valves are not included 
with the fixture and may be supplied by the contractor or purchased 
from Bradley Corporation.

Summary of Contents for S19-280D

Page 1: ...nted eye face wash S19 290W is similar Une douche oculaire faciale qui est mont e au comptoir S19 290D est montr e Une douche oculaire faciale qui est mont e au mur S19 290W est similaire Se muestra u...

Page 2: ...mensions 14 S19 290D S19 290W S19274JDB S19274JWB Dimensions 15 Installation 16 S19 280D S19 280W Assemblage des composantes 17 S19274HDB S19274HWB Assemblage des composantes 18 S19 280D S19 280W S192...

Page 3: ...ackaging material If any parts are missing do not begin installation until you obtain the missing parts The ANSI ISEA Z358 1 standard requires an uninterrupted supply of flushing fluid Bradley plumbed...

Page 4: ...2 60mm Mounting Pattern Off On 1 35mm Max Deck or Wall 29 41 746mm 1051mm to finished floor 15 384mm 1 32mm 6mm 2 57mm 2 51mm 4 102mm 2 60mm 2 60mm Mounting Pattern Off On 1 35mm Max Dimensions S19274...

Page 5: ...95mm 7 191mm 3 76mm 2 60mm Mounting Pattern Off On 1 35mm Max 15 384mm Deck or Wall Deck or Wall 28 40 711mm 1016mm to finished floor 30 42 762mm 1067mm to finished floor Dimensions S19 290D S19 290W...

Page 6: ...he water supply lines to relieve air and pressurize the valve Test the unit for leaks and adequate flow E Proper faucet shank handle clearance and recommended minimum splash containment dimensions mus...

Page 7: ...trieb pr fen best tigt durch Unterschrift Jegliche St rung sofort melden Date Datum Date Signed Unterschrift Signe Date Date Date Signed Signed Signed DIESES GER T 1ST W CHENTLICH ZU PR FEN ESSAI HEBD...

Page 8: ...operate valve s each week and sign below Report any malfunctions immediately Ventil e w chentlich im Testbetrieb pr fen best tigt durch Unterschrift Jegliche St rung sofort melden Date Datum Date Sig...

Page 9: ...ergency Inspection Tag Item Part No Qty Description Item Part No Qty Description 1 N A 1 Valve not available for service must replace complete fixture 2 160 473 1 Screw Set 13 160 474 2 Screw Set 14 1...

Page 10: ...iately Ventil e w chentlich im Testbetrieb pr fen best tigt durch Unterschrift Jegliche St rung sofort melden Date Datum Date Signed Unterschrift Signe Date Date Date Signed Signed Signed DIESES GER T...

Page 11: ...otated turn Wall 13 P O Box 309 Menomonee Falls WI 53051 R TEST THIS UNIT EACH WEEK Test operate valve s each week and sign below Report any malfunctions immediately Ventil e w chentlich im Testbetrie...

Page 12: ...421 1 Emergency Inspection Tag Item Part No Qty Description Item Part No Qty Description 1 N A 1 Valve not available for service must replace complete fixture 2 160 473 1 Screw Set 13 160 474 2 Screw...

Page 13: ...rme ANSI ISEA Z358 1 pr voit une alimentation ininterrompue du liquide de rin age Les appareils d urgence Bradley raccord s au r seau n cessitent une pression d coulement d au moins 30 PSI 0 21 MPa Le...

Page 14: ...oir ou mur 29 41 746mm 1051mm au plancher fini 15 384mm 1 32mm 6mm 2 57mm 2 51mm 4 102mm 2 60mm 2 60mm Dessin de montage 1 35mm Max Dimensions S19274HDB S19274HWB une unit qui est mont e au comptoir e...

Page 15: ...i dessous 1 32mm 6mm 2 57mm 4 102mm 8 203mm 5 127mm 2 60mm 1 35mm Max Dessin de montage 1 32mm 6mm 2 57mm 3 95mm 7 191mm 3 76mm 2 60mm Dessin de montage 1 35mm Max 15 384mm Comptoir ou mur Comptoir ou...

Page 16: ...il y a des fuites et si le d bit d eau est ad quat E Le d gagement pour les poign es et le tube montant du robinet et les dimensions minimales pour contenir les claboussures doivent tre pris en compt...

Page 17: ...tigt durch Unterschrift Jegliche St rung sofort melden Date Datum Date Signed Unterschrift Signe Date Date Date Signed Signed Signed DIESES GER T 1ST W CHENTLICH ZU PR FEN ESSAI HEBDOMADAIRE Test le...

Page 18: ...WEEK Test operate valve s each week and sign below Report any malfunctions immediately Ventil e w chentlich im Testbetrieb pr fen best tigt durch Unterschrift Jegliche St rung sofort melden Date Datum...

Page 19: ...ion Pi ce R f Qt Description Pi ce R f Qt Description Pi ce R f Qt Description 1 N A 1 Le robinet n est pas disponible en tant que pi ce de rechange l appareil complet doit tre chang 2 160 473 1 Vis d...

Page 20: ...il e w chentlich im Testbetrieb pr fen best tigt durch Unterschrift Jegliche St rung sofort melden Date Datum Date Signed Unterschrift Signe Date Date Date Signed Signed Signed DIESES GER T 1ST W CHEN...

Page 21: ...oculaire est montr e L Assembl e est tourn e tour Mur 13 P O Box 309 Menomonee Falls WI 53051 R TEST THIS UNIT EACH WEEK Test operate valve s each week and sign below Report any malfunctions immediat...

Page 22: ...e R f Qt Description Pi ce R f Qt Description Pi ce R f Qt Description 1 N A 1 Le robinet n est pas disponible en tant que pi ce de rechange l appareil complet doit tre chang 2 160 473 1 Vis de reglag...

Page 23: ...e todas las duchas lavaojos y lavaojos lavacara de seguridad deben cumplir con los requisitos de ANSI ISEA Z358 1 Lea en su totalidad este manual de instalaci n para garantizar una instalaci n adecuad...

Page 24: ...o pared 29 41 746mm 1051mm al suelo terminado 15 384mm 1 32mm 6mm 2 57mm 2 51mm 4 102mm 2 60mm 2 60mm Patr n de montaje 1 35mm Max Dimensiones S19274HDB S19274HWB se muestra una unidad que se monta a...

Page 25: ...ci n 1 32mm 6mm 2 57mm 4 102mm 8 203mm 5 127mm 2 60mm 1 35mm Max Patr n de montaje 1 32mm 6mm 2 57mm 3 95mm 7 191mm 3 76mm 2 60mm Patr n de montaje 1 35mm Max 15 384mm Mostrador o pared Mostrador o pa...

Page 26: ...rifique si el flujo de agua es adecuado E Se debe considerar el espacio adecuado entre la ca a y la manilla de la llave y las dimensiones m nimas para la contenci n de salpicaduras cuando se seleccion...

Page 27: ...Unterschrift Jegliche St rung sofort melden Date Datum Date Signed Unterschrift Signe Date Date Date Signed Signed Signed DIESES GER T 1ST W CHENTLICH ZU PR FEN ESSAI HEBDOMADAIRE Test le fonctionnem...

Page 28: ...e s each week and sign below Report any malfunctions immediately Ventil e w chentlich im Testbetrieb pr fen best tigt durch Unterschrift Jegliche St rung sofort melden Date Datum Date Signed Unterschr...

Page 29: ...rt Pieza N Ctd Descripci n Art Pieza N Ctd Descripci n Art Pieza N Ctd Descripci n 1 N A 1 V lvula no disponible para servicio se debe reemplazar el accesorio por completo 2 160 473 1 Tornillo prision...

Page 30: ...w chentlich im Testbetrieb pr fen best tigt durch Unterschrift Jegliche St rung sofort melden Date Datum Date Signed Unterschrift Signe Date Date Date Signed Signed Signed DIESES GER T 1ST W CHENTLIC...

Page 31: ...ojos Rotan a la asamblea 1 4 vuelta Pared 13 P O Box 309 Menomonee Falls WI 53051 R TEST THIS UNIT EACH WEEK Test operate valve s each week and sign below Report any malfunctions immediately Ventil e...

Page 32: ...ta de inspecci n Art Pieza N Ctd Descripci n Art Pieza N Ctd Descripci n Art Pieza N Ctd Descripci n 1 N A 1 V lvula no disponible para servicio se debe reemplazar el accesorio por completo 2 160 473...

Reviews: