Page 64
7KHFRQWUROOHULQWKH8QLWHQHUJL]HVWKHDSSURSULDWHSXPS
contacts when it receives a call for heat. Once the call for
KHDWLVVDWLV¿HGWKHSXPSVZLOOUHPDLQRQIRUWKHGH¿QHG
pump overrun time.
The Boiler, System, and DHW pump terminals are
found on the Main control board TB1-15A through 20A.
They are fed 120 Volts internally from the main power
feed. The current rating of the contacts is 7.4 amps, and
an appropriately sized contactor must be supplied and
LQVWDOOHGE\DTXDOL¿HGWHFKQLFLDQWRHQVXUHSURSHUSXPS
operation. Once the system has been installed, the “Pump
&RQ¿JXUDWLRQ´PHQXZLOODOORZWKHLQVWDOOHUWRDGMXVW
Pump control, Overrun time and Demand control for the
various pumps in the system.
6WDWLVWLFV&RQ¿JXUDWLRQ
7KHVWDWLVWLFVFRQ¿JXUDWLRQPHQXDOORZVWKHLQVWDOOHU
to view Burner Cycles, Burner Run Time, DHW Pump
Cycles, Boiler Pump Cycles, and System Pump Cycles.
This menu is ‘Read-Only’
9.7.10 High Limits
The outlet High limit can be adjusted using the installer
password. After a change is made, the control will lockout
DQGUHTXLUHD6DIHW\9HUL¿FDWLRQVHH6HFWLRQIRUPRUH
GHWDLOVRQ6DIHW\9HUL¿FDWLRQ
Installers do not have access to change the Outlet High
Limit Response. That is only accessible to the factory.
9.7.11 Stack Limits
Stack limit delay, response and setpoint can be
changed ONLY BY THE FACTORY.
9.7.12 Delta T Limits-
8QLWLVVKLSSHGZLWKDIDFWRU\VHW'HOWD7WHPSHUDWXUH
rise) limit of 60 degrees F. The installer has the ability
WRDGMXVWWKH'HOWD7LQOHWRXWOHWGHJUHHVHWSRLQW'HOWD
T delay, Delta T response, and the Delta T retry limit
using the installer level password. Only the factory
may disable this function.
9.7.13 Frost Protection
Frost protection will assist in keeping the Unit from
IUHH]LQJZKHQWKHXQLWLVQRWDEOHWR¿UHEXWLVVWLOO
able to run the pumps. The frost overrun time can
be changed.
Summary of Contents for Brute MagnaTech BMGH1600
Page 4: ......
Page 47: ...Page 43 Figure 24 High voltage wiring diagram Model 1600 208V Single Phase ...
Page 54: ...Page 50 8 12 Ladder Diagrams continued Figure 31 Model 1600 208V 1 Phase ladder diagram ...
Page 56: ...Page 52 8 12 Ladder Diagrams continued Figure 33 Model 2000 208V 1 Phase ladder diagram ...
Page 104: ...Page 100 1 13 12 4 3 5 13 2 15 DETAIL A 9 10 8 DETAIL Final Assembly ...