Page 23
Different glycol products may provide varying
degrees of protection. Glycol products must be
maintained properly in a heating system, or they may
EHFRPHLQHIIHFWLYH&RQVXOWWKHJO\FROVSHFL¿FDWLRQV
or the glycol manufacturer, for information about
VSHFL¿FSURGXFWVPDLQWHQDQFHRIVROXWLRQVDQGVHW
up according to your particular conditions.
The following manufacturers offer glycols, inhibitors,
and anti foamants that are suitable for use in the
Unit. Please refer to the manufacturers instructions
for proper selection and application.
•
Sentinel Performance Solutions Group
•
Hercules Chemical Company
•
Dow Chemical Company
The boiler control offers some assistance with freeze
protection, as long as the boiler is energized, and
DEOHWR¿UH
1. If the outlet sensor detects less than 45°F, the
control energizes the boiler pump.
2. If the outlet sensor detects less than 35°F, the
FRQWUROZLOO¿UHDWORZUDWH
3. Once in freeze protect mode, the boiler will
remain in that state until the outlet sensor detects
greater than 50°F.
6.4
Condensate Drain Trap
A condensate drain trap is included with the unit
and is designed to drain the unit of condensate.
See Figure 2 on page 7. The vent condensate
should be drained through a drain tee located in
the vent line. This will help prevent excessive
condensate from entering the unit at the vent.
Figure 8. Raised concrete platform
Neutralizer kit is
not included.
6.5 Suggested Piping Schematics
Figure 9 on page 24 through Figure 12 on page
VKRZVXJJHVWHGSLSLQJFRQ¿JXUDWLRQVIRU
boilers. These diagrams are only meant as guides.
All components or piping required by local code
must be installed.
The condensate drain must be installed to
prevent the accumulation of condensate. When
a condensate pump is not used, the tubing must
continuously slope downward toward the drain with
no spiraling.
Connect a 3/4” PVC pipe between the drain
FRQQHFWLRQDQGDÀRRUGUDLQRUFRQGHQVDWHSXPSLI
DÀRRUGUDLQLVQRWDFFHVVLEOH
Consult local codes for the disposal method.
A condensate neutralizer is not included with the unit
and yet is almost always used. It is advised that the
unit be installed on a raised 4” concrete platform so
WKDWWKHUHLVVXI¿FLHQWHOHYDWLRQIRUWKHFRQGHQVDWH
neutralizer below the included condensate trap.
See Figure 8
Caution
Condensate is mildly acidic (pH
=
5), and
PD\KDUPVRPHÀRRUGUDLQVDQGRUSLSHV
particularly those that are metal. Ensure
that the drain, drainpipe, and anything that
will come in contact with the condensate
can withstand the acidity, or neutralize
the condensate before disposal.
Damage
caused by failure to install a neutralizer
kit or to adequately treat condensate will
not be the manufacturer’s responsibility.
Summary of Contents for Brute MagnaTech BMGH1600
Page 4: ......
Page 47: ...Page 43 Figure 24 High voltage wiring diagram Model 1600 208V Single Phase ...
Page 54: ...Page 50 8 12 Ladder Diagrams continued Figure 31 Model 1600 208V 1 Phase ladder diagram ...
Page 56: ...Page 52 8 12 Ladder Diagrams continued Figure 33 Model 2000 208V 1 Phase ladder diagram ...
Page 104: ...Page 100 1 13 12 4 3 5 13 2 15 DETAIL A 9 10 8 DETAIL Final Assembly ...