Page 21
5.2
Water Heater Flow and Head Requirements
Headloss is for boiler only (no piping)
Headloss is for boiler only (no piping)
Headloss is for boiler only (no piping)
Allowable pH: 6.5 to 9.5
**
*
Model
Flow Rate
Temp Rise
Headloss
Flow Rate
Temp Rise
Headloss
GPM
°F
Ft
LPM
°C
m
1600
152
20
31.0
525
11.1
10.1
2000
152
25
33.0
575
14
10.1
2500
190
25
33.7
719
13.9
10.0
3000
190
30
36.0
719
17
11.0
3500
222
30
30.6
839
17
9.0
4000
224
34
30.0
848
19
9.1
Water Hardness
1-10 grains per gallon
Flow Rate
Temp Rise
Headloss
Flow Rate
Temp Rise
Headloss
GPM
°F
Ft
LPM
°C
m
177
17
41.0
670
9.4
12.5
177
21
43.9
670
12
13.4
220
21
46.0
833
11.7
14
220
26
46.0
833
14
14
266
25
40.6
1007
14
12
266
29
41.2
1007
16
12.6
Water Hardness
11-15 grains per gallon
Model
1600
2000
2500
3000
3500
4000
*
*
*
*
Table 16. Normal Water
Table 17. Hard Water
Summary of Contents for Brute MagnaTech BMGH1600
Page 4: ......
Page 47: ...Page 43 Figure 24 High voltage wiring diagram Model 1600 208V Single Phase ...
Page 54: ...Page 50 8 12 Ladder Diagrams continued Figure 31 Model 1600 208V 1 Phase ladder diagram ...
Page 56: ...Page 52 8 12 Ladder Diagrams continued Figure 33 Model 2000 208V 1 Phase ladder diagram ...
Page 104: ...Page 100 1 13 12 4 3 5 13 2 15 DETAIL A 9 10 8 DETAIL Final Assembly ...