Page 19
SCH 40 METAL PIPE CAPACITY FOR 0.60 SPECIFIC GRAVITY
NATURAL GAS
NOMINAL PIPE SIZE @ 0.30” W.C. PRESSURE DROP
Nominal:
2
2½
3
4
5
Actual ID:
2.067
2.469
3.068
4.026
5.047
Length (ft)
10
4,020
6,400
11,300
23,100
41,800
20
2,760
4,400
7,780
15,900
28,700
30
2,220
3,530
6,250
12,700
23,000
40
1,900
3,020
5,350
10,900
19,700
50
1,680
2,680
4,740
9,660
17,500
60
1,520
2,430
4,290
8,760
15,800
70
1,400
2,230
3,950
8,050
14,600
80
1,300
2,080
3,670
7,490
13,600
90
1,220
1,950
3,450
7,030
12,700
100
1,160
1,840
3,260
6,640
12,000
125
1,020
1,630
2,890
5,890
10,600
150
928
1,480
2,610
5,330
9,650
175
854
1,360
2,410
4,910
8,880
200
794
1,270
2,240
4,560
8,260
150
704
1,120
1,980
4,050
7,320
300
638
1,020
1,800
3,670
6,630
350
587
935
1,650
3,370
6,100
400
546
870
1,540
3,140
5,680
Capacity in Cubic Feet of Gas per Hour
p
(
)
Notes:
1. Inlet pressure - Less than 2 psi
2. Pressure drop - 0.5 in w.c.
3. Specific gravity - 0.60
4. Schedule 40 metallic pipe
Table 12. Pipe Capacity for Natural Gas
Table 13. Pipe Capacity for Propane
SCHED 40 METAL PIPE CAPACITY FOR 1.50 SPECIFIC GRAVITY
UNDILUTED PROPANE
NOMINAL PIPE SIZE @ 11” W.C. INLET AND 0.5” W.C. PRESSURE
DROP
Nominal:
1½
2
2½
3
4
Actual ID:
1.61
2.067
2.469
3.068
4.026
Length (ft)
10
3,520
6,790
10,800
19,100
39,000
20
2,420
4,660
7,430
13,100
26,800
30
1,940
3,750
5,970
10,600
21,500
40
1,660
3,210
5,110
9,030
18,400
50
1,480
2,840
4,530
8,000
16,300
60
1,340
2,570
4,100
7,250
14,800
80
1,230
2,370
3,770
6,670
13,600
100
1,140
2,200
3,510
6,210
124,700
125
1,070
2,070
3,290
5,820
11,900
150
1,010
1,950
3,110
5,500
11,200
175
899
1,730
2,760
4,880
9,950
200
814
1,570
2,500
4,420
9,010
250
749
1,440
2,300
4,060
8,290
300
697
1,340
2,140
3,780
7,710
350
618
1,190
1,900
3,350
6,840
400
560
1,080
1,720
3,040
6,190
p
(
)
Capacity in Cubic Feet of Gas per Hour
Notes:
1. Inlet pressure - 11.0 in w.c.
2. Pressure drop - 0.5 in w.c.
3. Specific gravity - 1.50
4. Schedule 40 metallic pipe
5. Intended use - Pipe sizing between single
or second-stage (low pressure)
regulator and appliance.
The following are gas line sizing examples from the National Fuel Gas Code. Size your gas lines properly,
based on your installation, and all applicable codes.
Summary of Contents for Brute MagnaTech BMGH1600
Page 4: ......
Page 47: ...Page 43 Figure 24 High voltage wiring diagram Model 1600 208V Single Phase ...
Page 54: ...Page 50 8 12 Ladder Diagrams continued Figure 31 Model 1600 208V 1 Phase ladder diagram ...
Page 56: ...Page 52 8 12 Ladder Diagrams continued Figure 33 Model 2000 208V 1 Phase ladder diagram ...
Page 104: ...Page 100 1 13 12 4 3 5 13 2 15 DETAIL A 9 10 8 DETAIL Final Assembly ...