Fig. 19 Plume distance to opening
4.1.4
EXTENDED FLUE INSTALLATION
Fig. 20 Slope for condensate disposal
NOTE:
OUTLET POSITIONS
B
The flue terminal outlet position must
follow those stated in figure 3.
When redirecting the flue discharge the
terminal end must be at least 1500mm
from any opening in the direction of the
discharge to prevent combustion
products from entering the building as
shown
1
Opening in building
2
Flue discharge
3
Terminal end
4
Minimum 1500mm from an opening in the
building
Table 11 Key to figure 19
6720643895-119.1Wo
1
3
4
2
NOTE:
CONDENSATE DISPOSAL
B
All horizontal flue sections must rise by at
least 52mm per metre away from the
boiler to ensure that the condensate
flows back into the boiler for safe
disposal via the condensate waste pipe.
To ease assembly of the flue components,
lightly grease the seals with the solvent-free
grease supplied.
Check all the seals are properly seated in
the grooves provided and are in good
condition.
All flue joints must be sealed to prevent
leakage of condensate and flue products.
6720644842-10.1Wo
2m
1m
52mm
104mm