6720892984 (2019/02) US
SSB
80 | Service reminder
HR #
Access
Description
Range
R
W
33019
X
Overdue counter 14
0…65534 hours.
Service Settings
33042
X
Service Interval.
0…255 x 100 hours
NOTE: A Overdue counter value of 0xFFFF means that the counter is not available/empty.
M .4
Burner/Module info
Each module/burner present in the boiler has its own set of status information holding registers. Each set has the holding register offset of ((‘Unit/burner
Number’ - 1) x 100) + 40000. So Burner 1 starts at holding register 40000, Burner 2 starts at 40100, etc.
M .4 .1 Burner/Module 1 Status and Control Registers
HR #
Access
Description
Range
R
W
Module/Burner 1 status info
40000
X
Current state of the unit/burner.
State(*)
40001
X
Error of the unit/burner.
See manual
40002
X
Module supply setpoint (calculated)
0-100°C (32-212°F)
40003
X
Power level.
0.0 - 100.0%
40006
X
General pump status.
0=Off, 1=On
40009
X
CH Flow rate.
0-255 l/min
40011
X
Actual fan speed.
RPM
40030
X
Supply sensor temperature.
-50...150°C
(-58...302°F)
40032
X
Return sensor temperature.
-50...150°C
(-58...302°F)
40035
X
Flue sensor temperature.
-50...150°C
(-58...302°F)
40052
X
Total burn hours.
0-65536Hours
The State(*) can be divided in the following steps:
Standby: 0 : Initialization
1 : Reset
2 : Standby
Active:
3/4 : Pre Purge
5/6 : (Pre) Ignition 7 : Flame Proving 8/9 : Burn 10/11 : Post Purge
Error:
12 : Error
13 : Alarm
14 : Warning
15 : Burner Boot