SSB
6720892984 (2019/02) US
Service reminder | 53
Menu item
Sub item / Parameter
Range
Default Value
Units
User Level
(136) Mod. Pump Mode
On/Off
Modulating
Fixed 20..100%
On/Off
2: Installer
(137) Mod. Pump Min Power
0..100
40
%
2: Installer
(138) Appliance Type
50..55
50
2: Installer
(139) Dair active
Yes, No
No
2: Installer
(140) Minimal Flow
0,0..100
50
l/min
2: Installer
(107) Antilegionella Day
Sun..Sat
Sun
Day
2: Installer
(108) Antilegionella Hour
0..23
0
Hour
2: Installer
(183) Hight Limit Test
Simulated / Physical
Simulated
3: Factory
Module
Cascade
Settings
(72) Permit EmergencyMode
Yes/No
Yes
1: User
(74) Emergency Setpoint
20...90 (68...194)
70 (158)
°C (°F)
2: Installer
(75) Delay Per Start Next Dep
5..255
200
Sec.
2: Installer
(76) Delay Per Stop Next Dep
5..255
180
Sec.
2: Installer
(142) Delay Quick Start Next
5..255
50
Sec.
2: Installer
(143) Delay Per Quick Stop Next
5..255
30
Sec.
2: Installer
(77) Hyst Down Start Module
0...40 (0...72)
5 (9)
°C (°F)
2: Installer
(78) Hyst Up Stop Module
0...40 (0...72)
4 (7)
°C (°F)
2: Installer
(144) Hyst Down Quick Start
0...40 (0...72)
10 (18)
°C (°F)
2: Installer
(145) Hyst Up Quick Stop
0...40 (0...72)
6 (11)
°C (°F)
2: Installer
(146) Hyst Up Stop All
0...40 (0...72)
8 (14)
°C (°F)
2: Installer
(147) Number of Units
1..8
8
2: Installer
(148) Power Mode
0) Disabled
1) Min burners
2) Max burners
3) Balanced burners
2
2: Installer
(79) Max. Setp. Offset Down
0...40 (0...72)
20 (36)
°C (°F)
2: Installer
(80) Max Setp Offset Up
0...40 (0...72)
20 (36)
°C (°F)
2: Installer
(81) Start Mod Delay Fact
0..60
60
Min.
2: Installer
(82) Next Module Start Rate
10..100
80
%
2: Installer
(83) Next Module Stop Rate
10..100
25
%
2: Installer
(84) Module Rotation Interval
0..30
5
Days
2: Installer
(149) First Module to Start
1..16
-
2: Installer
(86) PID P
0..1275
50
3: Factory
(87) PID I
0..1275
500
3: Factory
(150) PID Slew Rate Up
0..25,5
1
3: Factory
(151) Casc PID Slew Rate Dn
0..25,5
1
3: Factory
(152) PwrMode2 Min Power
0..100
20
%
2: Installer
(153) PwrMode2 Hysteresis
0..100
40
%
2: Installer
(154) Post-Pump period
0..255
30
Sec.
2: Installer
(155) Frost Protection
10...30 (50...86)
15 (59)
°C (°F)
2: Installer
Boiler
Cascade
Settings
(73) Boiler Address
Stand-alone
Managing (1)
Dependent (2..8)
Managing
2: Installer
(156) Permit EmergencyMode
Yes/No
Yes
1: User
(157) Emergency Setpoint
20...90 (68...194)
70 (158)
°C (°F)
2: Installer
(158) Delay Per Start Next Blr.
0..1275
1275
Sec.
2: Installer
(159) Delay Per Stop Next Blr.
0..1275
1275
Sec.
2: Installer
(160) Delay Quick Start Next
0..1275
400
Sec.
2: Installer
(161) Delay Quick Stop Next
0..1275
240
Sec.
2: Installer
(162) Hyst Down Start Boiler
0...40 (0...72)
5 (9)
°C (°F)
2: Installer