SSB
6720892984 (2019/02) US
Service reminder | 49
B .2
Maximum load on outputs (for hardware 905MN1x_3Rf and up)
Device
Max Current
Max Power
Control and gas valve
0,5 A
60 VA
All pumps together
1,5 A
180 VA
Fan
2,0 A
240 VA
Total external load
4 A
480 VA
All other devices must be powered externally.
B .3
Minimum/Maximum load on air damper output (J3-6)
The output J3-6 is a triac controlled output. This output needs a minimum load of approx. 10VA to work correctly and the max load must be limited to 50VA
@ supply voltage.
Connection an external relay to this output to be able to switch a higher load is only possible when an additional resistor or load is added to make sure the
minimum load requirements are met.
Appendix C - System parameters
C .1
Settings stored in 905PB display
Menu item
Sub item / Parameter Range
Default Value
Units
User Level
Language
English
French
Chinese
Italian
English
1: User
Unit type
Metric
Imperial
Metric
°C, Bar
°F, PSI
1: User
Date &Time
Date
-
dd-mm-year
1: User
Time
-
00:00
1: User
Time Zone Settings
1: User
Time Zone Correction
UTC
X
1: User
Daylight Savings Time Disabled
N,C America, Europe
1: User
Display Settings
1: User
Time Notation
24h, 12h
24h
1: User
Date Order
DMY, MDY, YMD
DMY
1: User
Day of Month
1-2 digits
2 digits
1: User
Month
Short-Full text
1-2 digits
2 digits
1: User
Year
2-4 digits
4 digits
1: User
Date Separation
Character
-, /, .
-
1: User
Day of Week
Disabled
Short Text
Full Text
Short Text
1: User
Seconds
Yes, No
No
1: User
Cascade Mode
Full option (8 module
TS/BMS)
Basic (16 module ZH)
Full
Basic
Full
1: User
Modbus Address
0..255
1
1: User
Modbus Stop bits
1 - 2
2
1: User
Startup Settings
Startup Logo
Default
1: User