DANGER
Danger without protective separation!
⇒
The 24 VDC input voltage must comply with the
requirements of the "Protective separation".
⇒
Plug and unplug the connector only in no-voltage
condition!
PE
0V
+ 24V
400V + 5%
400V
400V - 5%
L1
L2
L3
Sichertrafo.cdr
Fig. 7-12:
Safety transformer according to EN 60742
Interfering AC voltage components such as resulting from an uncontrolled
3-phase current bridge connection without smoothing with a ripple factor
(see DIN 40110/10.75, section 1.2) of 5 % are permissible.
It follows from the above that as upper voltage limit the greatest absolute
value is 30.2 V and as lower voltage limit the lowest absolute value is
18.5 V.
t
1.05 x 28.8 V = 30.2 V
Upper limit
28.8 V
0.866 x 30.2 V = 26.1 V
1.5 x 20.4 V = 21.4 V
Lower limit
20.4 V
0.866 x 21.4 V = 18.5 V
30 el
cos (30 ) = 0.866
0
Wechsel.cdr
Fig. 7-13:
Illustration of the limit values for the 24 VDC voltage