4-4
Technical Data
VSB 40.1
DOK-SUPPL*-VSB*40.1***-PR02-EN-P
The devices of the VSB family are basically certified according to
•
UL508 (Industrial Control Equipment) and
•
C22.2 No. 142-M1987 (CSA)
However, it is possible that there are combinations or extension stages
with restricted or missing certification. Thus, verify the registration
according to the UL marking on the device.
Note:
To guarantee an UL/CSA-compliant operation, the following
conditions have to be fulfilled:
•
Use insulated copper wires suitable for at least 60/75
°
C.
•
Use Class 1 wire only or equivalent.
Note:
The UL/CSA marking is only valid for the device in its delivery
status. After modifying the device, e.g. after plugging
additional extension cards, the UL compliance must be
checked.
4.6 Wear
Parts
CMOS battery: 5 to 7 years
•
The hard disk is an electromechanical wear part, that has to be
changed during the operating time. According to the manufacturer's
specifications the hard disk has been developed for a service life of 60
months in consideration of the following conditions:
Operating hours / month
Max. 720
Input cycles and output cycles / month
833
Operating conditions
Temperature
< 60
°
C
Rel. humidity
< 90 %
Height
< 3,000 m
Accesses
50 % of the operating hours
Storage conditions
Temperature
< 70
°
C
Rel. humidity
< 95 %
Duration
< 3 months
Fig. 4-6: Typical operating and storage conditions of the hard disk
The operation out of this typical conditions is permissible, whereby,
however, the service life of the hard disk may reduce. However, the
ambient conditions specified for the overall device in chapter 4.4 have
to be absolutely kept. Different values apply for hard disks of some
devices with special design.
•
Fans are mechanical wear parts whose service life depends mainly on
the temperature. For the fan integrated in the housing, the following
service life is specified by the manufacturer:
Ambient temperature
Service life
40
°
C
70,000 hours
70
°
C
35,000 hours
Fig. 4-7: Service life of the fan
UL/CSA certification
Wear parts without warranty
Summary of Contents for Rexroth VSB 40.1
Page 7: ...IV Contents VSB 40 1 DOK SUPPL VSB 40 1 PR02 EN P ...
Page 27: ...4 6 Technical Data VSB 40 1 DOK SUPPL VSB 40 1 PR02 EN P ...
Page 79: ...12 4 List of Figures VSB 40 1 DOK SUPPL VSB 40 1 PR02 EN P ...
Page 83: ...13 4 Index VSB 40 1 DOK SUPPL VSB 40 1 PR02 EN P ...
Page 85: ...14 2 Service and Support VSB 40 1 DOK SUPPL VSB 40 1 PR02 EN P ...
Page 86: ......