4-6
Preparation and Assembly
Rexroth IndraMotion MLD
DOK-IM*MLD-F*STEP**V**-KB01-EN-P
Setting IP Address and Network Mask in IndraDrive
To establish Ethernet communication with IndraDrive you have to
parameterize an IP address and the network mask on the control section.
You can make these settings on the control section via IndraWorks or the
control panel.
For local networks, IP addresses can be assigned in the following ranges:
10.0.0.0 to
10.255.255.255
172.16.0.0 to
172.31.255.255
and
192.168.0.0
to
192.168.255.255
Suggestion:
IP address:
192.168.1.
2
Network mask:
255.255.255.0
Default gateway:
0.0.0.0
Note:
Setting the desired IP address, network mask and default
gateway is only possible in the parameter mode.
It might possibly be necessary to switch to the parameter
mode via the control panel; the paragraph below describes
how to do this.
When setting the IP address via the control panel, observe the following
points:
•
Switch on control voltage for IndraDrive controller
•
For approx. 8 s press both "ESC" and "Enter" keys at control panel
•
With "Up/Down" keys select "2. Comand" and confirm selection with
"Enter" key
•
If you have to switch to parameter mode, select "2.11 > PM" with
"Up/Down" keys and start command with "Enter" key
•
Select "2.3 Kom. Ethernet" and confirm selection with "Enter" key
•
Under "2.3.1 P-0-1531" you can now set IP address
Note:
The individual octets are applied by pressing the "Enter" key.
To return press the "Esc" key.
•
Under "2.3.2 P-0-1532" you can set the network mask
•
Under "2.3.3 P-0-1533" you can set the default gateway
Note:
In order that the parameter setting of desired IP address,
network mask and default gateway takes effect, switch the
control voltage for the IndraDrive controller off and on again.
IP Address Range
Setting the IP Address via the