RT Ethernet extension module
24 V supply with FE to XF40
845 V AC, 50 Hz, 1 min
24 V supply with FE to XF41
845 V AC, 50 Hz, 1 min
XF40 to XF41
845 V AC, 50 Hz, 1 min
Sercos extension module
24 V supply with FE to XF3
845 V AC, 50 Hz, 1 min
24 V supply with FE to XF4
845 V AC, 50 Hz, 1 min
XF3 to XF4
845 V AC, 50 Hz, 1 min
CAN extension module
24 V supply to XF70
845 V AC, 50 Hz, 1 min
24 V supply to XF71
845 V AC, 50 Hz, 1 min
24 V supply to FE
845 V AC, 50 Hz, 1 min
XF70 to FE
845 V AC, 50 Hz, 1 min
XF71 to FE
845 V AC, 50 Hz, 1 min
XF70 to XF71
845 V AC, 50 Hz, 1 min
Tab. 7-2: Operating voltage and current consumption
Electronic damage due to polarity reversal or
due to a nominal current that is too low
NOTICE
The power supply unit has to be able to deliver the quadruple nominal current of
the protective fuse to ensure that the fuse reliably triggers in case of an error.
8 Standards
The products have been developed according to the German edition of the
standards published at the time of product engineering.
8.1 Standards used
Standard
Meaning
Edition
IEC 60204-1
Electrical equipment of machines
2007
IEC 61131-2
Programmable controllers
2008
IEC 60529
Degrees of protection provided by enclosures (IP Code)
2014
IEC 61010-2-201
Safety requirements for electrical equipment for measure-
ment, control and laboratory use
2014
UL 61010-2-201
Safety requirements for electrical equipment for measure-
ment, control and laboratory use
2014
Tab. 8-1: Standards used
Extension Modules Profibus, RT-
Ethernet, Sercos, CAN
Bosch Rexroth AG
Standards
DOK-CONTRL-XFE**EXTMOD-IT04-EN-P
9/37