– They have a counterpressure against the engaging forces when mounting
the modules in series to the control.
●
Do not route cables parallel to motor cables or other strong interference sour-
ces to avoid coupling of interferences
●
The LED displays may not be hidden
●
Observe the bending radius of the cables used when routing the connecting
lines
●
Use strain reliefs for all cables
●
Keep the maximum distance possible from interference sources
●
Provide minimum distances for sufficient cooling. Refer to the operating in-
structions of the XM control, see
fig. 10-3 "Minimum distances for the circula-
tion of ambient air" on page 18
30 mm
30 mm
100 mm
100 mm
30 mm
Fig. 10-3: Minimum distances for the circulation of ambient air
In case of a several line design, the supply air has to be measured under each
line and its limit value has to be observed. For information on ambient tem-
peratures, refer to
chapter 6 "Ambient conditions" on page 7
●
Additionally, provide sufficient distance for mounting, demounting, plugs and
cables
●
Use only cables approved for temperatures of at least +60°C. In case of ambi-
ent temperatures above +55 C, use cables approved for temperatures of at
least +75°C.