Data loss caused by incorrect switch-off with-
out UPS
NOTICE
In case of a missing UPS, switch off the control cabinet PC via the software of
the operating system only and not by interrupting the current supply. This ap-
plies particularly for RAID systems.
12.2 Operating and error displays
There are four LEDs on the connector panel of the IndraControl VPB 40.3 to dis-
play the device states and errors. Apply the specified measure if one of the fol-
lowing LEDs indicates either an error or a note, see
rating and error display on the connector panel" on page 42
.
Some LEDs, e.g. the CPU temperature monitoring, are only active if
the service software has been configured accordingly.
LED
Display
Meaning
Action
V
in
LED green
Normal operation
–
LED off
No supply voltage (24 V DC)
Check the supply voltage at
the power supply unit!
TEMP
LED off
Normal operation
–
LED is flashing
red (flashing
frequency ap-
prox. 2 Hz)
Fan is not rotating or is rotating too slowly
Check fan on the control cabi-
net PC!
LED red
Overtemperature
Reduce the ambient tempera-
ture!
UPS
LED off
Normal operation
–
LED red
The control cabinet PC is currently operating
in battery mode, i. e. no supply voltage is
available!
Restore the power supply and
initiate a controlled restart!
Bosch Rexroth AG
Device description
Control Cabinet PC
42/57
DOK-SUPPL*-VPB*40.3***-IT05-EN-P
Summary of Contents for Rexroth IndraControl VPB 40.3
Page 1: ...IndraControl VPB 40 3 Control Cabinet PC Operating Instructions R911336750 Edition 05 ...
Page 6: ...Bosch Rexroth AG Control Cabinet PC IV DOK SUPPL VPB 40 3 IT05 EN P ...
Page 61: ...Control Cabinet PC Bosch Rexroth AG DOK SUPPL VPB 40 3 IT05 EN P 55 57 ...
Page 62: ...Bosch Rexroth AG Control Cabinet PC 56 57 DOK SUPPL VPB 40 3 IT05 EN P ...