1. Only remove the CDI cable jacket on the length required for the connec-
tion.
The CDI cable is sensitive to mechanical load where the jacket was
removed. Ensure that the CDI cable shielding is not damaged when
removing the cable jacket.
Fig. 10-17: CDI cable with RJ45 plug
Fig. 10-18: CDI cable with partially removed jacket
2. Remove the foil shield.
CDI cables are equipped with an additional foil shield. The foil shield
must not be used for the connection. For an improved stability, the
foil shield is usually plastic-coated on one side. The plastic coating is
insulating.
Fig. 10-19: Foil shield of the CDI cable
Bosch Rexroth AG
Mounting, demounting and electric installation
Control Cabinet PC
38/57
DOK-SUPPL*-VPB*40.3***-IT05-EN-P