10 Mounting, demounting and electric installation
10.1 Installation notes
10.1.1 Cables routing
●
Lay all connecting cables in loops and use strain reliefs for all cables
●
Keep the maximum distance possible from interference sources
●
Do not lay the CDI cables in parallel to motor cables or to other noise sour-
ces, as the CDI connection can be disturbed
10.1.2 Housing distances for maintenance tasks
Provide a minimum space of 50 mm (exception above: 120 mm) on all sides for
sufficient cooling and for cable routing
Comply with the following housing distances to execute maintenance tasks di-
rectly at the device in the control cabinet:
●
To maintain the fan and exchange the battery, go up by 120 mm
●
For the DVD drive and exchange of the hard disk, go forward by 150 mm
Bosch Rexroth AG
Mounting, demounting and electric installation
Control Cabinet PC
20/57
DOK-SUPPL*-VPB*40.3***-IT05-EN-P