7
Commissioning
7.1
GSD File
The GSD file is provided by Satisloh.
7.2
PROFIBUS DP Address Settings
The station address is set with 2 BCD rotary switches S1 and S2 (see
"BCD rotary switch: S1 and S2" on page 35
) for the station addresses 1-99.
Thereby, S1 represents the ones digit and S2 the tens digit of the station ad‐
dress.
The address must be set in deenergized status.
Fig.7-1:
BCD rotary switch: S1 and S2
7.3
Baud Rate Setting
The VDP 92.3 recognize automatically the baud rate set at the PROFIBUS DP.
Supported are baud rates ranging from 9.6 kbauds to 12 Mbauds:
9.6 kbauds
19.2 kbauds
45.45 kbauds
93.75 kbauds
187.5 kbauds
500 kbauds
1.5 Mbauds
3 Mbauds
Project Planning Manual | Rexroth IndraControl VDP 92.3
Electric Drives
and Controls
| Bosch Rexroth AG
35/52
Commissioning
PROFIBUS DP Address Settings