7-2
Interfaces
VDP 16.1, VDP 40.1 and VDP 60.1
DOK-SUPPL*-VDP16/40/60-PR02-EN-P
24 VDC Power Supply
The VDP is provided with the necessary power via the GIGASTAR
interface of the IPC.
Note:
If Y-Repeaters are used, the VDP must be separately provided
with a voltage of 24 VDC via connection X13.
For this an isolated power supply unit is required.
+24 VDC
N.C.
GND
Isolated power
supply unit
X13
2
3
1
X13
1
2
3
X13.FH9
Fig. 7-4:
24 VDC power supply X13
Pin
Function
1
+24 V
2
GND
3
N.C.
To provide the device with power, you can use a commercially available
24 V industrial power supply unit.
Note:
An isolated power supply unit has to be used, as pin 2 is
internally connected with the housing.