4
Technical Data
4.1
Degree of Protection and Weight
Degree of protection
IP 20
Weight
1 kg
Fig.4-1:
Degree of protection and weight
4.2
Input and Output Voltage
4.2.1
+24 V Input Voltage
Nominal input voltage
24 VDC
Input voltage range
24 VDC +20 %, -15 %
Emitted interference and surge immunity Umax = 35 V (for t < 100 ms)
Power consumption at U
N
2.5 A max.
Input fuse
None
Voltage rise of the supply voltage when
switching on
Max. 500 ms (0 V to UN)
Voltage drop of the supply voltage when
switching off
Max. 500 ms (UN to 0V)
Switch-on threshold
15.5 V ±5 %
Switch-off threshold
20.2 V ±5 %
Maximum power consumption
60 W
①
①
The UPS requires a maximum of 60 W (24 V, 2.5 A) from the 24 VDC
supply.
Fig.4-2:
+24V input voltage
4.2.2
115/230 VAC Input Voltage
Nominal input voltage
115/230 VAC
Input voltage range
85 – 264 VAC
Input frequency
47 – 63 Hz
Power consumption at U
N
115 VAC = 1.00 A typ.
230 VAC = 0.60 A typ.
Recommended protection
5 A
Fig.4-3:
115/230 VAC input voltage
4.2.3
Output Voltage
Nominal output voltage
24 VDC
Output voltage range
24 VDC +20 %, -15 %
Current output at U
N
2.5 A max.
Switching time
< 1 ms
Project Planning Manual | Rexroth IndraControl VAU 01.1Z
Electric Drives
and Controls
| Bosch Rexroth AG
15/45
Technical Data