Lines with an average conductor cross-section of 0.2 mm
2
to 1.5 mm
2
(AWG
16 to 24) can be connected.
Unshielded lines:
Use unshielded lines for the digital inputs and outputs as well as for the volt‐
age supply.
Connecting unshielded lines
Fig.10-28:
Connecting lines to tension spring connectors
Proceed as follows to connect unshielded lines to the tension spring connec‐
tor:
1.
Wire the connectors as required according to the application.
2.
Strip the line to a length of 8 mm.
Wiring is provided without wire end sleeves. If wire end sleeves are to
be used nevertheless, ensure that the wire end sleeves are properly
crimped.
3.
Put a screwdriver into the actuation slot of the corresponding terminal
point (A in
) so that the wire can be inserted into the opening of the
spring.
4.
5.
Pull the screwdriver out of the opening. This fixes the wire.
For further information on the connection method, please refer to
the Rexroth Inline PROFIBUS DP; Application Manual (see
).
10.7.8
Notice for Use of the Control above 2700 m above MSL
General Information
The control is designed for use up to 2700 m above MSL according to DIN
60204 (see also
chapter 6 "Ambient Conditions" on page 15
If it is used above 2700 m above MSL, Bosch Rexroth cannot as‐
sume warranty. Therefore the user assumes responsibility if it
used above 2700 m above MSL.
To realize use above 2700 m above MSL, nevertheless, the user has to take
appropriate measures, particularly the track resistance has to be ensured.
For use up to 4000 m above MSL Bosch Rexroth recommends the following
measures:
●
Use an isolating transformer between the AC 400 V and AC 230 V net‐
work.
DOK-CONTRL-IC*LX5*****-IT01-EN-P
Rexroth IndraControl L25, L45, L65 and L85 Controls
Bosch Rexroth AG
43/65
Mounting, Dismounting and Electrical Installation