Fig.10-21:
Remove the labeling field, removing the connectors
3.
).
4.
Remove the adjacent connectors of the neighboring terminals (C in
).
This ensures that the feathers of the voltage jumpers and the keyway/
feather key connection are prevented from damage. Moreover, the ter‐
minal can be accessed more easily.
Fig.10-22:
Removing the terminal
5.
Push the release mechanism (D1 in
).
6.
Remove the terminal perpendicularly to the top-hat rail (D2 in
To protect the feathers of the voltage routing and the keyway/feather
key connection, the connector of the neighboring terminal to the left now
comes loose unless it has already been loosened.
Changing an Inline terminal
1.
Remove the new terminal (see preceding section).
2.
Do not latch on the adjacent connector of the neighboring terminal to the
left yet.
3.
Fit the new terminal.
4.
Subsequently, refit all connectors.
DOK-CONTRL-IC*LX5*****-IT01-EN-P
Rexroth IndraControl L25, L45, L65 and L85 Controls
Bosch Rexroth AG
37/65