Rexroth Diax 04 HVE/HVR
Ratings and Dimensions
3-1
DOK-DIAX04-HVE+HVR*UL*-IB01-EN-P
3
Ratings and Dimensions
3.1 HVE
Description
Symbol
Unit
HVE02.2-
W018N
HVE03.2-
W030N
HVE03.2-
W030L
HVE04.2-
W075N
HVE04.2-
W075L
listing according UL-standard (UL)
UL 508 C
listing according CSA-standard (UL)
Canadian National Standard(s) C22.2 No. 14-05
UL files (UL)
E134201
pollution degree (UL)
Use in a pollution degree 2 environment
maximum ambient temperature
with nominal data (UL)
T
amax
°C
45
maximum ambient temperature
with reduced nominal data (UL)
T
amax_red
°C
55
Weight
m
kg
13
16
16
28
28
Device height (UL)
1)
H
mm
498
Device depth (UL)
2)
T
mm
308
Device width (UL)
3)
B
mm
100
150
150
250
250
minimum distance on the top of the
device
4)
d
top
mm
300
minimum distance on the bottom of
the device
5)
d
bot
mm
100
rated control voltage input (UL)
6)
U
N3
V
3 x 380…480
rated power consumption control
voltage input without holding brake,
without control section at
U
N3
= DC 24 V (UL)
7)
P
N3
W
500
short circuit current rating, SCCR,
symmetrical amperes (UL)
8)
I
SCCR
A
rms
42000
rated input voltage, power (UL)
9)
V
3 x 380…480
tolerance rated input voltage (UL)
%
±10
input number of phases (UL)
3
input frequency (UL)
f
LN
Hz
50…60
tolerance input frequency (UL)
Hz
±2
maximum input current (UL)
10)
I
L_cont
A
30
50
50
120
120
branch circuit protection fuse (UL)
11)
40
70
70
150
150
field wiring material (UL)
12)
Use 60/75 °C copper wire only, use class 1 wire only or
equivalent
required wire size according UL 508
A (internal wiring); at I
L_cont
(UL)
13)
A
LN
AWG 6
AWG 2
AWG 2
AWG 0
AWG 0
maximum output voltage (UL)
U
out
V
670 dc
maximum output current (UL)
I
out_max
A
37
60
60
140
140